background image

 

10 

Aries Installation and Commissioning manual 

system, which distributes it to heat the building and the 
domestic hot water with the help of a change-over valve. 
The  refrigerant  condenses  into  a  liquid  state  in  the 
condenser as it loses heat energy.  

The pressure of the refrigerant remains high as the liquid 
refrigerant  is  transferred  to  the  expansion  valve.  The 
pressure  of  the  refrigerant  decreases  in  the  expansion 
valve, and the temperature drops to approximately -10°C. 
The  expansion  valve  injects  the  correct  amount  of 
refrigerant  into  the  evaporator,  where  the  heat  energy 
transferred  from  the  brine  causes  the  refrigerant  to 
evaporate. 

 

 

Figure: Functional description 

1: Heat pump 

2: Condenser 

3: Compressor 

4: Evaporator 

5: Change-over valve 

6:  Water  circulation  pump,  heating/domestic  hot  water 
charge 

7: Expansion valve 

9: Collection pump 

9: Heat collection pipe, ground loop 

10: Heat collection pipe, bored well 

11: Underfloor heating 

12: Radiator heating 

13: Hot water tank 

 

2.4

 

Heating functions 

Domestic hot water 

The heat pump outputs domestic hot water based on the 
tank’s  operational  measurement  sensor  (B3).  The 
temperature of domestic hot water can be selected from 
the  options, 

Eco

Normal

  or 

Comfort

.

 

This  selection 

affects  the  amount  of  hot  domestic  hot  water.  When 

Comfort

 is selected, the heat pump also uses an electric 

heater to heat domestic hot water. 

Heating 

The  heat  pump  outputs  heating  water  directly  into  the 
building’s  heating  network.  Automatic  regulation 
determines  the  set  point  for  the  supply  water  from  the 
heating  circuit  based  on  the  set  heating  curve  and  the 
outdoor temperature measurement. The controller uses the 
set value for the supply water to determine the set point 
for  the  heat  pump,  and  the  frequency-controlled 
compressor  uses  this  value  to  set  itself  to  the  correct 
rotation  speed  in  order  to  keep  the  temperature  of  the 
supply water at the set point. The room temperature sensor 
also affects the set point.  

In  order  for  the  heat  pump  to  operate  at  maximum 
efficiency, the heating system and the collector must be 
under  ideal  conditions.  The  difference  between  the 
heating system’s output and return temperatures must be 
5–8°C, and the difference between the collector’s output 
and return temperatures must be 3–4°C. If the temperature 
differences deviate from these values, the efficiency will 
decrease,  along  with  the  savings.  The  heat  pump’s 
controller ensures the correct temperature difference for 
the heat supply and the collection pump. 

Factory settings: 

Heating temperature difference: 5°C 

Domestic  hot  water  preparation  temperature  difference: 
8°C 

Collector temperature difference: 3°C 

2.5

 

Tips for making savings 

The heat pump is intended to generate the desired heat and 
domestic  hot  water.  The  system  attempts  to  meet  these 
desires by all available means within the limits of the set 
values.  

Important  factors  affecting  energy  consumption  are  the 
indoor temperature, the domestic hot water consumption, 
the temperature of the domestic hot water, the quality of 
the house’s insulation, and the desired level of comfort.  

Keep the aforementioned factors in mind when changing 
the device’s settings. 

 

IMPORTANT: 

Floor heating and radiator thermostats can have a negative 
impact on energy consumption. They reduce the flow rate 
in the heating system, and the heat pump compensates for 
this by raising the temperature of the network. This affects 
the device’s operation by causing more electrical energy 
to  be  consumed.  Thermostats  are  only  intended  for 
adjustments  due  to  “free  heat”  (from  the  sun,  people, 
fireplaces, etc.)  

 

 

Summary of Contents for Aries 12

Page 1: ...Installation and Commissioning manual Aries ground source heat p ump WWW GEBWELL COM...

Page 2: ...sors 17 6 PIPE INSTALLATION 18 6 1 Collector 18 6 2 Heat supply circuit 20 6 3 Domestic hot water system 21 7 ELECTRICAL CONNECTIONS 22 7 1 General 22 7 2 Power supply 22 7 3 Connecting the sensors 23...

Page 3: ...33 12 3 HEATING 34 13 HEAT PUMP MAINTENANCE AND SERVICING 36 13 1 Inspections 36 13 2 Drainage of the hot water tank LVV1 36 13 3 Drainage of the heating system 36 13 4 Drainage of the collector 36 1...

Page 4: ...an installation log Fill in the details below If there are failures with the device these details must be available Ground source heat pump model Serial number HVAC company Name Installation date Phon...

Page 5: ...installation instructions given by the manufacturer of the product The warranty does not extend to or is not valid in case the product is used in any other way than required by the sizing The customer...

Page 6: ...th the instructions in the manuals before submitting a warranty repair request ensure that the warranty period is still valid read the warranty terms carefully and find out the product s model and ser...

Page 7: ...essure of the expansion tank 0 5 bar Strainer flow direction Safety valve checked Shut off valves checked Length of the collector m If there are several loops record the lengths m Checked by date HEAT...

Page 8: ...set Minimum set point for supply water to the heating circuit Maximum set point for supply water to the heating circuit Checked by date GENERAL Wiring in accordance with the installation instructions...

Page 9: ...2 2 Ground cooling The low temperature of the brine can also be used to cool your home In the summer free cooling energy can be transferred from the ground using only a water circulation pump The grou...

Page 10: ...etermine the set point for the heat pump and the frequency controlled compressor uses this value to set itself to the correct rotation speed in order to keep the temperature of the supply water at the...

Page 11: ...nt that is harmful and hazardous to the environment The refrigerant is in a hermetically sealed refrigerant circuit in the compressor module If the refrigerant leaks into indoor premises the room must...

Page 12: ...the lip at the bottom of the door goes into the slot on the bottom of the heat pump and the lip on the top of the door sits at the top of the heat pump 4 6 Detaching the cover of the control unit The...

Page 13: ...he intended installation location Lift the heat pump off the shipping pallet Use the adjustable feet to get the heat pump into a horizontal and stable position Make sure the frame is not in contact wi...

Page 14: ...oor that is separated from the building s other areas can prevent noise from travelling through the floor and into residential premises At least 700 mm of clearance should be reserved in front of the...

Page 15: ...ons Aries 6 Aries 12 BO1 Brine to the ground 28mm 28mm BI2 Brine from the ground 28mm 28mm WO1 Heating supply 22mm 28mm WI2 Heating return 22mm 28mm CI1 Cold water 22mm 22mm HW2 Domestic hot water 22m...

Page 16: ...CHARGE RETURN SHUT OFF VALVE VS4 BRINE FROM THE GROUND INSIDE THE COMPRESSOR UNIT HEAT SUPPLY PUMP Q9 SOURCE PUMP Q8 COMPRESSOR K1 FREQUENCY CONVERTER TM1 EXPANSION VALVE PV1 EVAPORATOR LS1 CONDENSER...

Page 17: ...d insulated from external heat Some of the sensors are located in the compressor unit module B2 Domestic hot water tank B3 Domestic hot water operation B21 Charge heating water supply heating supply B...

Page 18: ...when you make changes to the pipe network 3 Detach the collection pipes from the elbow fitting by pressing down on the plastic collar on the claw coupling using a spanner 4 Detach the pipes from the...

Page 19: ...ve must be installed in such a way that it is easy to regulate and inspect and it does not freeze Purge the circuits of air one at a time and regulate the flow rate in relation to the lengths of the c...

Page 20: ...he safety valve can be a maximum of 2 5 bar and it should be installed in the heating system s return pipe It is advisable to lead the safety valve overflow pipe to the nearest floor drain The overflo...

Page 21: ...heat pump rinse the building s domestic hot water pipe network to remove any impurities that may remain after installation Install shut off valves in pipe connections as close to the heat pump as pos...

Page 22: ...d with water This could cause damage to the electric heater pumps protective devices or compressor All of the electrical devices except the outdoor temperature sensor and the room temperature sensor a...

Page 23: ...ted on the user interface Room temperature sensor placement Connect the room temperature sensor B5 to the T3 connectors X8 and M on the controller 7 4 Connecting the domestic hot water circulation pum...

Page 24: ...the controller using a connector or cable attached to the end of the module First attach the connector to the expansion module before attaching the expansion module to the DIN rail When the module is...

Page 25: ...ch a way that air is able to escape from the collector s level tank via valve G The expansion tank must therefore be located at the highest point and the collection pipes must not allow air pockets to...

Page 26: ...e accumulator coil The heating system water circulates in the heat transfer coil inside the accumulator The coil should be carefully purged of air during deployment to ensure the correct operation of...

Page 27: ...Create account The password will be sent to the e mail address you gave when registering The e mail address is also your username NOTE Please check the spam if you cannot find the e mail in Inbox 11 3...

Page 28: ...necting to the heat pump s Wi Fi network In order to gain access to the Aries heat pump via application you are to connect to the heat pump s Wi Fi network Below is an example of the heat pump s ID pl...

Page 29: ...ile data and Wi Fi networks Open smart device s settings menu and the Wi Fi settings Android Turn on Wi Fi switch in the On position Select Add network Select Security and choose WPA WPA2 Enter the ne...

Page 30: ...ettings on the device Once you have entered the Network name SSID 1 and security settings and the Password Wifi key 2 choose Additional settings 3 Do the following changes on Additional settings Mark...

Page 31: ...off the automatic connection to Wi Fi networks on your smart device turn the sliders off Open the app window and enter the address where the Aries heat pump is located Then enter the data of the hous...

Page 32: ...ups listed on device testing and mark them done Then choose Quit Go to main menu and choose Settings and on settings menu open Device management The device is on Stop as operationmode Choose Automatic...

Page 33: ...nclude the settings in the event that the app is not working or is unavailable for other reasons Some of the settings can only be configured at the expert level If you are unable to access a setting p...

Page 34: ...g circuits Heating circuit 1 is always the heat pump s internal pump heating circuit for which a mixing function cannot be configured Heating Circuit 2 is an optional mixing heating circuit that can b...

Page 35: ...ng 40 45 C Radiator heating 50 65 C Lower limit Minimum supply water temperature Example values Underfloor heating 18 25 C Radiator heating 15 18 C Summer winter heating threshold The summer winter he...

Page 36: ...n increase correspondingly when the pump shuts off Any other behaviour is indicative of air in the system the wrong circulation direction or a blocked filter In a pressurised brine circuit the liquid...

Page 37: ...the Heating area menu The heating circuit s time programme is on o Go to the Time programme heating circuit menu and adjust the time programme Air in the heating system o Release the air from the heat...

Page 38: ...ctly connected Contact Gebwell maintenance if necessary 50 Domestic hot water sensor 1 B3 Fault in the domestic hot water accumulator sensor Fault in the electrical system Contact an authorised techni...

Page 39: ...up domestic hot water Flow rate too low in the charging circuit Air in the heating network The pressures in the heating system are too low Blocked sanitary trap Bleed the heating network Check the net...

Page 40: ...tector SV2 The overheating protector SV2 prevents the electric heater SV1 from overheating If the protector triggers a failure is reported to the controller and it must be manually acknowledged The SV...

Page 41: ...088 2 088 Quantity of refrigerant kg 0 82 1 40 CO2 equivalence ton CO e 1 712 2 923 Disconnection overpressure MPa 4 4 44 bar Difference overpressure MPa 0 7 7 bar Disconnection underpressure MPa 0 17...

Page 42: ...w Factory setting Floor heating Radiator heating Air heating LP1 LP2 710 1010 Comfort operation set point 20 712 1012 Diminished set point 15 720 1020 Heating curve gradient 0 5 0 3 0 5 0 8 0 5 1 0 0...

Page 43: ...v 1 4 05022019 43 17 SERVICE LOG Date Action Fault code Technician Fault code If the device has reported an operating failure enter the fault code provided by the controller in this column...

Page 44: ...44 Aries Installation and Commissioning manual 18 ENERGY LABEL...

Page 45: ...Directive PED 2014 68 EU shall not apply to this pressurized equipment according to item 2 f iii in Article 1 ja seuraavia yhdenmukaistettuja standardeja ja teknisi eritelmi on sovellettu and the foll...

Page 46: ...OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF...

Page 47: ......

Page 48: ......

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ...OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF...

Page 53: ......

Page 54: ......

Page 55: ......

Page 56: ......

Page 57: ......

Page 58: ......

Page 59: ......

Page 60: ...Gebwell Ltd Business ID 2008956 7 Patruunapolku 5 FI 79100 Lepp virta FINLAND Tel 358 20 1230 800 info gebwell www gebwell com...

Reviews: