34 

Aries Installation and Commissioning manual 

indicates the charging status of hot domestic water 

Operating mode HMI 

The operating mode is used to choose the functional status 
of hot domestic water. In the 

AUTO

 mode, the heat pump 

prepares domestic water normally within the framework 
of the set value and the connection difference. The heat 
pump does not heat domestic water in 

OFF

 mode. 

AUTO / OFF 

Set value Temperature 

The set value of hot domestic water has an effect on the 
sub  sensor  of  the  functional  accumulator.  Due  to 
accumulator layering, the actual temperature of domestic 
water raises 5–10°C higher than the set value. 

Factory setting 50˚C 

You can change the domestic water set in the HOT DOM 
WATER > SET VALUE TEMP menu. 

COMFORT

:  The  normal  set  value  for  domestic  water. 

This value changes, if you toggle the status of domestic 
water COMFORT/NORMAL/ECO in the application 

ECO

: The domestic water temperature drop used in time 

control 

Legionella 

The  anti-bacterial  function  of  hot  domestic  water.  The 
Legionella function raises the domestic water accumulator 
temperature to the Legionella set value once a week. The 
heat pump uses an electric heater for Legionella charging. 

Set value temperature: 

The  set  value  to  which  the  heat  pump  will  charge  the 
accumulator temperature.  

factory setting 55°C 

Legionella function: 

The weekday when the charging takes place. 

Mon/Tue/Wed/Thu/Fri/Sat/Sun 

Start time: 

The time of day when the Legionella function starts 

Legionella overcharge: 

The time by which the Legionella charging exceeds the set 
value. 

Domestic hot water circulation pump 

The  domestic  hot  water  circulation  pump  can  be 
controlled  using  the  heat  pump’s  controller.  The 
circulation pump follows the schedule set for domestic hot 
water. If domestic hot water is on, the circulation pump 
will also be on. 

12.3

 

HEATING 

The heating system is circuit-specifically configured. The 
heat pump regulator is capable of controlling two heating 
circuits.  Heating  circuit  1  is  always  the  heat  pump’s 

internal pump heating circuit for which a mixing function 
cannot  be  configured.  Heating  Circuit  2  is  an  optional 
mixing heating circuit that can be used to adjust a lower 
temperature, for instance, to heat a garage. If you use two 
heating circuits, circuit 1 should always have the higher 
temperature. 

Operating mode HMI 

In  the  Operating  Mode  menu,  you  can  turn  a  heating 
circuit  ON  or  OFF.  The  correct  operating  mode  for 
heating a property is the 

AUTO

 mode. 

MAIN  MENU  >  HEATING  CIRCUIT  1  (2)  > 
OPERATING MODE HMI 

Set point room temperature 

The room temperature can be controlled according to the 
room  set  point.  The  room  temperature  sensor  must  be 
placed  in  a  central  part  of  the  building  in  order  for 
regulation to function optimally. 

The controller uses 

COMFORT 

-setting in normal heating 

control and 

ECO

 -setting in time control reduced setting 

period. 

If the heating circuit does not include a room sensor, you 
should disable the room sensor in the 

Service Menu

. In 

this  case,  the  regulator  will  use  a  20-degree  reference 
value for heat control. 

 

Control curve 

The control curve is used to calculate the set point for 
the  supply  water  temperature,  and  this  set  point  is 
used  to  regulate  the  supply  water  temperature 
according  to  the  prevailing  weather  conditions. 

The 

control  curve  can  be  changed  at  five  different  external 
temperature  points  so  that  the  heating  output  and  room 
temperature can be adjusted as required. 

A  steeper  control  curve  gradient  means  that  the 
temperature of the supply water changes more when the 
outdoor temperature decreases. In other words, if the room 
temperature is wrong when the outdoor temperature is low 
but not when the outdoor temperature is high, the gradient 
of the curve needs to be changed. 

 

Increasing the setting: 

Increases the temperature 
of  the  supply water, par-
ticularly  at  low  outdoor 
temperatures. 

Decreasing the setting: 

Decreases  the  tempera-
ture  of  the  supply  water, 
particularly  at  high  out-
door temperatures. 

 

The end user can make minor changes to the control curve 
during the first heating period. See the 

User manual

 for 

instructions on this. 

Summary of Contents for Aries 12

Page 1: ...Installation and Commissioning manual Aries ground source heat p ump WWW GEBWELL COM...

Page 2: ...sors 17 6 PIPE INSTALLATION 18 6 1 Collector 18 6 2 Heat supply circuit 20 6 3 Domestic hot water system 21 7 ELECTRICAL CONNECTIONS 22 7 1 General 22 7 2 Power supply 22 7 3 Connecting the sensors 23...

Page 3: ...33 12 3 HEATING 34 13 HEAT PUMP MAINTENANCE AND SERVICING 36 13 1 Inspections 36 13 2 Drainage of the hot water tank LVV1 36 13 3 Drainage of the heating system 36 13 4 Drainage of the collector 36 1...

Page 4: ...an installation log Fill in the details below If there are failures with the device these details must be available Ground source heat pump model Serial number HVAC company Name Installation date Phon...

Page 5: ...installation instructions given by the manufacturer of the product The warranty does not extend to or is not valid in case the product is used in any other way than required by the sizing The customer...

Page 6: ...th the instructions in the manuals before submitting a warranty repair request ensure that the warranty period is still valid read the warranty terms carefully and find out the product s model and ser...

Page 7: ...essure of the expansion tank 0 5 bar Strainer flow direction Safety valve checked Shut off valves checked Length of the collector m If there are several loops record the lengths m Checked by date HEAT...

Page 8: ...set Minimum set point for supply water to the heating circuit Maximum set point for supply water to the heating circuit Checked by date GENERAL Wiring in accordance with the installation instructions...

Page 9: ...2 2 Ground cooling The low temperature of the brine can also be used to cool your home In the summer free cooling energy can be transferred from the ground using only a water circulation pump The grou...

Page 10: ...etermine the set point for the heat pump and the frequency controlled compressor uses this value to set itself to the correct rotation speed in order to keep the temperature of the supply water at the...

Page 11: ...nt that is harmful and hazardous to the environment The refrigerant is in a hermetically sealed refrigerant circuit in the compressor module If the refrigerant leaks into indoor premises the room must...

Page 12: ...the lip at the bottom of the door goes into the slot on the bottom of the heat pump and the lip on the top of the door sits at the top of the heat pump 4 6 Detaching the cover of the control unit The...

Page 13: ...he intended installation location Lift the heat pump off the shipping pallet Use the adjustable feet to get the heat pump into a horizontal and stable position Make sure the frame is not in contact wi...

Page 14: ...oor that is separated from the building s other areas can prevent noise from travelling through the floor and into residential premises At least 700 mm of clearance should be reserved in front of the...

Page 15: ...ons Aries 6 Aries 12 BO1 Brine to the ground 28mm 28mm BI2 Brine from the ground 28mm 28mm WO1 Heating supply 22mm 28mm WI2 Heating return 22mm 28mm CI1 Cold water 22mm 22mm HW2 Domestic hot water 22m...

Page 16: ...CHARGE RETURN SHUT OFF VALVE VS4 BRINE FROM THE GROUND INSIDE THE COMPRESSOR UNIT HEAT SUPPLY PUMP Q9 SOURCE PUMP Q8 COMPRESSOR K1 FREQUENCY CONVERTER TM1 EXPANSION VALVE PV1 EVAPORATOR LS1 CONDENSER...

Page 17: ...d insulated from external heat Some of the sensors are located in the compressor unit module B2 Domestic hot water tank B3 Domestic hot water operation B21 Charge heating water supply heating supply B...

Page 18: ...when you make changes to the pipe network 3 Detach the collection pipes from the elbow fitting by pressing down on the plastic collar on the claw coupling using a spanner 4 Detach the pipes from the...

Page 19: ...ve must be installed in such a way that it is easy to regulate and inspect and it does not freeze Purge the circuits of air one at a time and regulate the flow rate in relation to the lengths of the c...

Page 20: ...he safety valve can be a maximum of 2 5 bar and it should be installed in the heating system s return pipe It is advisable to lead the safety valve overflow pipe to the nearest floor drain The overflo...

Page 21: ...heat pump rinse the building s domestic hot water pipe network to remove any impurities that may remain after installation Install shut off valves in pipe connections as close to the heat pump as pos...

Page 22: ...d with water This could cause damage to the electric heater pumps protective devices or compressor All of the electrical devices except the outdoor temperature sensor and the room temperature sensor a...

Page 23: ...ted on the user interface Room temperature sensor placement Connect the room temperature sensor B5 to the T3 connectors X8 and M on the controller 7 4 Connecting the domestic hot water circulation pum...

Page 24: ...the controller using a connector or cable attached to the end of the module First attach the connector to the expansion module before attaching the expansion module to the DIN rail When the module is...

Page 25: ...ch a way that air is able to escape from the collector s level tank via valve G The expansion tank must therefore be located at the highest point and the collection pipes must not allow air pockets to...

Page 26: ...e accumulator coil The heating system water circulates in the heat transfer coil inside the accumulator The coil should be carefully purged of air during deployment to ensure the correct operation of...

Page 27: ...Create account The password will be sent to the e mail address you gave when registering The e mail address is also your username NOTE Please check the spam if you cannot find the e mail in Inbox 11 3...

Page 28: ...necting to the heat pump s Wi Fi network In order to gain access to the Aries heat pump via application you are to connect to the heat pump s Wi Fi network Below is an example of the heat pump s ID pl...

Page 29: ...ile data and Wi Fi networks Open smart device s settings menu and the Wi Fi settings Android Turn on Wi Fi switch in the On position Select Add network Select Security and choose WPA WPA2 Enter the ne...

Page 30: ...ettings on the device Once you have entered the Network name SSID 1 and security settings and the Password Wifi key 2 choose Additional settings 3 Do the following changes on Additional settings Mark...

Page 31: ...off the automatic connection to Wi Fi networks on your smart device turn the sliders off Open the app window and enter the address where the Aries heat pump is located Then enter the data of the hous...

Page 32: ...ups listed on device testing and mark them done Then choose Quit Go to main menu and choose Settings and on settings menu open Device management The device is on Stop as operationmode Choose Automatic...

Page 33: ...nclude the settings in the event that the app is not working or is unavailable for other reasons Some of the settings can only be configured at the expert level If you are unable to access a setting p...

Page 34: ...g circuits Heating circuit 1 is always the heat pump s internal pump heating circuit for which a mixing function cannot be configured Heating Circuit 2 is an optional mixing heating circuit that can b...

Page 35: ...ng 40 45 C Radiator heating 50 65 C Lower limit Minimum supply water temperature Example values Underfloor heating 18 25 C Radiator heating 15 18 C Summer winter heating threshold The summer winter he...

Page 36: ...n increase correspondingly when the pump shuts off Any other behaviour is indicative of air in the system the wrong circulation direction or a blocked filter In a pressurised brine circuit the liquid...

Page 37: ...the Heating area menu The heating circuit s time programme is on o Go to the Time programme heating circuit menu and adjust the time programme Air in the heating system o Release the air from the heat...

Page 38: ...ctly connected Contact Gebwell maintenance if necessary 50 Domestic hot water sensor 1 B3 Fault in the domestic hot water accumulator sensor Fault in the electrical system Contact an authorised techni...

Page 39: ...up domestic hot water Flow rate too low in the charging circuit Air in the heating network The pressures in the heating system are too low Blocked sanitary trap Bleed the heating network Check the net...

Page 40: ...tector SV2 The overheating protector SV2 prevents the electric heater SV1 from overheating If the protector triggers a failure is reported to the controller and it must be manually acknowledged The SV...

Page 41: ...088 2 088 Quantity of refrigerant kg 0 82 1 40 CO2 equivalence ton CO e 1 712 2 923 Disconnection overpressure MPa 4 4 44 bar Difference overpressure MPa 0 7 7 bar Disconnection underpressure MPa 0 17...

Page 42: ...w Factory setting Floor heating Radiator heating Air heating LP1 LP2 710 1010 Comfort operation set point 20 712 1012 Diminished set point 15 720 1020 Heating curve gradient 0 5 0 3 0 5 0 8 0 5 1 0 0...

Page 43: ...v 1 4 05022019 43 17 SERVICE LOG Date Action Fault code Technician Fault code If the device has reported an operating failure enter the fault code provided by the controller in this column...

Page 44: ...44 Aries Installation and Commissioning manual 18 ENERGY LABEL...

Page 45: ...Directive PED 2014 68 EU shall not apply to this pressurized equipment according to item 2 f iii in Article 1 ja seuraavia yhdenmukaistettuja standardeja ja teknisi eritelmi on sovellettu and the foll...

Page 46: ...OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF...

Page 47: ......

Page 48: ......

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ...OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF...

Page 53: ......

Page 54: ......

Page 55: ......

Page 56: ......

Page 57: ......

Page 58: ......

Page 59: ......

Page 60: ...Gebwell Ltd Business ID 2008956 7 Patruunapolku 5 FI 79100 Lepp virta FINLAND Tel 358 20 1230 800 info gebwell www gebwell com...

Reviews: