Technical data: Ambient temperatures
Designation
Description
- Valve
0 to 45 °C (32 ... 113 °F), standard
< 0 °C (32 °F): use control air with a
low dew point. Protect valve stems
against freezing.
< −15 °C: no solenoid valves in the
control top
> +50 °C: no solenoid valves in the
control top
- Proximity switch
-20 to +80 °C (-4 ... +176 °F)
- Control top type T.VIS M-15, A-15,
P-15
-20 to +50 °C (-4 ... +122 °F)
Product temperature and operating
temperature
Depending on the sealing material
Technical data: Compressed air supply
Designation
Description
Air hose
- Metric
Material PE-LD outside Ø 6 mm
Inside Ø 4 mm
- Inch
Material PA outside-Ø 6.35 mm
Inside Ø 4.3 mm
Product pressure
5 bar (72.5 psi) standard
> 5 bar (72.5 psi) on request
Control air pressure
6 bar, max. 8 bar
Control air
acc. to ISO 8573-1
- Solid particle content:
Quality class 6
Particle size max. 5 µm
Particle density max. 5 mg/m
3
- Water content:
Quality class 4
max. dew point +3 °C
If the unit is used at higher altitudes or
at low ambient temperatures, the dew
point must be adapted accordingly.
- Oil content:
Quality class 3,
preferably oil free
Max. 1 mg oil to 1 m
3
air
Technical data
Technical data
430BAL008430EN_4
08.03.2022
23