BEFORE YOU BEGIN

Installation Instructions   Zoneline Air Conditioners

Read these instructions completely and carefully.

 

IMPORTANT –

 

Save these instructions for 

local inspector’s use.

 

IMPORTANT –

 

Observe all governing 

codes and ordinances.

• 

Note to Installer –

 Be sure to leave these 

instructions with the owner.

• 

Note to Owner –

 Keep these instructions for 

future reference.

  Proper installation is the responsibility of the installer. 
  Product failure due to improper installation is not 

covered under the Warranty.

Questions?  Call 800.GE.CARES (800.432.2737) or

 

Visit our Website at: 

GEAppliances.com

IMPORTANT ELECTRICAL  

6$)(7<³5($'&$5()8//<

• Follow the National Electrical Code (NEC) or local codes and 

ordinances.

•  For personal safety, this Zoneline must be properly grounded.

•  Protective devices (fuses or circuit breakers) acceptable for 

Zoneline installations are specified on the nameplate of each 

unit.

• Do not use an extension cord with this unit.
‡$OXPLQXPEXLOGLQJZLULQJPD\SUHVHQWVSHFLDOSUREOHPV³

consult a qualified electrician.

•  When the unit is in the OFF position, there is still voltage to 

the electrical controls.

•  Disconnect the power to the unit before servicing by:

  1   Removing the power cord (if it has one) from the wall 

receptacle.  OR

  2   Removing the branch circuit fuses or turning the circuit 

breakers off at the panel.

•  Suivez le Code national de l’électricité (CNE) ou vos ordonnances et 

codes locaux.

•  Pour votre sécurité personnelle, ce Zoneline doit être bien mis à la terre.

•  Les appareils protecteurs (fusibles ou disjoncteurs) acceptables 

pour installer votre Zoneline sont indiqués sur la plaque sig-

nalétique de chaque appar eil.

•  N’utilisez jamais de rallonge électrique avec cet appareil.
‡ /HV¿OVGHEkWLPHQWHQDOXPLQLXPSHXYHQWSRVHUGHVSUREOqPHV

SDUWLFXOLHUV³FRQVXOWH]XQpOHFWULFLHQTXDOL¿p

•  Quand votre appareil est en position OFF (arrêt), il reste de la ten-

sion dans les commandes électriques.

•  Débranchez le courant de votre appareil avant de l’entretenir ou de 

le réparer en:

  1.  Enlevant le cordon d’alimentation (le cas échéant) de la prise 

murale.   OU  

2.   Enlevant les fusibles du circuit de dérivation ou en débranchant 

les disjoncteurs de dérivation au panneau.

•  Siga las instrucciones del National Electrical Code (Código de Electri-

cidad Nacional) (NEC) o los códigos u ordenanzas locales.

•Para su seguridad personal, el acondicionador de aire Zoneline debe 

tener una adecuada conexión a tierra.

•  Los dispositivos de protección (fusibles o disyuntores) adecuados 

SDUDODVLQVWDODFLRQHVGH=RQHOLQHVHHQFXHQWUDQHVSHFL¿FDGRVHQOD

placa de cada unidad.

•  No utilice un cable de extensión con esta unidad.

•  El cableado de aluminio puede presentar problemas especiales: 

FRQVXOWHDXQHOHFWULFLVWDFDOL¿FDGR

•  Cuando la unidad se encuentra en la posición OFF (apagado), to-

davía hay voltaje en los controles eléctricos.

•  Antes de realizar reparaciones en la unidad, desconecte el suminis-

tro de energía de la siguiente manera:

 1 

 Retire el cable eléctrico (si posee uno) del receptáculo de la pared. O

 2 

 Retire los fusibles de la sección o apague el disyuntor desde el panel.

Phillips screwdriver

TOOLS YOU WILL NEED

NOTE – As with any mechanical device with moving parts, 

this unit will have a wear-in period.  AFTER INSTALLATION, 

this unit should be operated for 48 hours to achieve 

optimum efficiency.

AIR CONDITIONER BREAK-IN PERIOD

ZONELINE COMPONENTS

Appearance may vary.

*

*  Shipped with the Zoneline unit

**  Check the “Essential Elements” list 

on the unit located on front of the 

base pan

Exterior grille/louver**

Wall case**

Zoneline unit

Room 

cabinet*

Power 

supply kit**

14

CAUTION

ATTENTION

PRECAUCIÓN

Summary of Contents for Zoneline AZ45

Page 1: ...on Filter 12 Air Filters 13 Installation Instructions Preparation 14 Replacing an Existing Unit 15 Electrical Connection 16 18 Installing the Zoneline 19 20 Optional Drain Kit 21 Troubleshooting Tips...

Page 2: ...TE We strongly recommend that any servicing be performed by a qualified individual These R410A air conditioning systems require contractors and technicians to use tools equipment and safety standards...

Page 3: ...ar les entrepreneurs et les techniciens doivent tre approuv s en fonction du fluide frigorig ne dont le syst me de climatisation R410A du Zoneline est quip N UTILISEZ PAS d quipements certifi s relati...

Page 4: ...r servicio llevado a cabo en este equipo lo realice un individuo calificado Los sistemas de acondicionador de aire R410A requieren que los contratistas y t cnicos utilicen herramientas equipamiento y...

Page 5: ...and Operation Control 1 Sets the fan operation for HIGH or LOW 02 22 For cooling 1 For fan only operation 7 For heating 2 Turns the unit off Power remains connected to the Zoneline The Freeze Heat Sen...

Page 6: ...trol in the closed position The room air will be filtered and circulated Air Direction To change the air direction remove the room front Remove the 4 louver screws that hold the louver insert in place...

Page 7: ...onfirm the selection and exit AUX SET mode 6PDUW DQ RROLQJ HDWLQJ Press MODE until a 1 appears in the first digit of the display for Smart Fan cool mode The COOL LED light on the main control will be...

Page 8: ...t of the display for Freeze Sentinel mode The COOL LEDlight on the main control will be on Press MODE again to change to the Heat Sentinel The HEAT LEDlight on the main control will be on Press the pa...

Page 9: ...The second digit of the display will be between 0 and 7 depending on the limit you want to set The chart shows the limits available Press AUX SET to confirm your selection and exit AUX SET mode or pre...

Page 10: ...stance heat To set All Electric Heat option press MODE until an 8 appears in the first digit of the display Press the or pad to set this switch to OFF or ON This is shown in the second digit of the di...

Page 11: ...thermostat IMPORTANT The Zoneline thermostat connections provide 24 V AConly If using a digital electronic wall thermostat you must set it to the 24 V ACsetting See the Installation Instructions for...

Page 12: ...NT This filter is not removable Trying to remove this filter will damage the unit Use a vacuum to remove debris from the filter Use a damp rag to wipe down the filter and surrounding area after vacuum...

Page 13: ...lters Vacuum off the heavy soil Run water through the filters from the back side Dry thoroughly before replacing NOTE The air filters are interchangeable and will fit in either the right or left side...

Page 14: ...kWLPHQW HQ DOXPLQLXP SHXYHQW SRVHU GHV SUREOqPHV SDUWLFXOLHUV FRQVXOWH XQ pOHFWULFLHQ TXDOL p Quand votre appareil est en position OFF arr t il reste de la ten sion dans les commandes lectriques D bra...

Page 15: ...area as calculated by ASHRAE See the Architects and Engineers Data Manual for more detailed information Any vertical deflectors in the existing rear grille should be removed to decrease condenser air...

Page 16: ...or leakage current detection device on the power cord except direct connect Be sure to select the correct cord for your installation Branch Circuit and Proper GE Power Cord Unit Amperage Rating with...

Page 17: ...La conexi n de este producto de 265 voltios de CA a un circuito derivado DEBE realizarse mediante una conexi n directa de acuerdo a las indicaciones del NEC El c digo no permite enchufar esta unidad a...

Page 18: ...Fan 3 80 3 11 KW Low Fan 230 208 Volt Power Supply Kits 1 Circuit Protective Device Heater Wattage 230 208 Volts RAK315D RAK320D RAK330D 15 Amp Time Delay Fuse or Breaker 20 Amp Time Delay Fuse or Bre...

Page 19: ...the room side of the case The RAB71A B series wall cases are already insulated NOTE For installation with a subbase or duct adapter see the instructions packed with those kits 2 PREPARE THE UNIT Care...

Page 20: ...op 1 then pushing it in at the bottom 2 NOTE There are several extra holes in the unit side flanges for installation in wall cases other than GE To avoid damaging the flange insulation the installer s...

Page 21: ...walls we recommend the use of RAD10 Drain Kit External Drain See the Installation Instructions in the RAD10 kit Internal Drain See the Installation Instructions in the RAD10 kit Type A screw for metal...

Page 22: ...ug interrupter device is tripped or the box near the plug If the RESET button will not stay engaged discontinue use of the Zoneline and contact a qualified service technician Zoneline does not cool In...

Page 23: ...desired NOTE Use of this option will result in increased energy consumption The unit is not The Smart Fan Auxiliary See Smart Fan Cooling Heating on page 5 blowing out air Controls may be set to cycl...

Page 24: ...set up to be in continuous fan the indoor fan will run regardless if the unit may be cooling or heating Other times the fan will run longer than the heating cooling cycle or kick on occasionally This...

Page 25: ...RGL FDWLRQ After mailing the registration below store this document in a safe place It contains information you will need should you require service Our service number is 800 GE CARES 800 432 2737 Rea...

Page 26: ...Please place in envelope and mail to Please place in envelope and mail to Veuillez mettre dans une enveloppe et envoyez 26 Product Registration...

Page 27: ...her rights which vary from state to state or province to province To know what your legal rights are consult your local state or provincial consumer affairs office or your state s Attorney General War...

Page 28: ...hearing impaired please call 800 TDD GEAC 800 833 4322 Parts and Accessories GEAppliances com Individuals qualified to service their own appliances can have parts or accessories sent directly to their...

Reviews: