DIRECT CONNECTION

   Order the following Kit for 230/208-volt direct 

connection as required:

 

 

 

*Not approved for use on 7000 BTU models.

   Review installation instructions provided with power 

cord or direct connect kits for detailed assembly 

instructions.  

   If using a sub-base connection, the RAK4002C Junction 

Box is also necessary for a complete installation.

17

Installation Instructions

 

265 VOLT ELECTRICAL CONNECTION OPTIONS

 

    

Connection of this 265 V AC product to a branch circuit MUST 

be done by direct connection in accordance with the National 

Electrical Code. Plugging this unit into a building-mounted exposed 

receptacle is not permitted by code.

   These models must be installed using the appropriate GE power 

supply kit for the branch circuit amperage and the electrical 

resistance heater wattage desired. Use the POWER CONNECTION 

CHART on page 18 to determine the correct kit required. One of 

the following installation methods must be used:

   Vous DEVEZ brancher ce produit alimenté par courrant alternatif 

de 265 volts au circuit de dérivation par branchement direct 

conformément au Code national d’électricité. Le Code n’autorise 

pas le branche men td evotr eappareil à une prise exposée 

montée sur le bâtiment. 

   Vous devez installer ces modèles à l’aide de la bonne trousse 

d’alimentation électrique GE pour l’ampérage du circuit de 

GpULYDWLRQHWODSXLVVDQFHGXFKDXȺDJHjUpVLVWDQFHpOHFWULTXH

désirée. Utilisez le Tableau de contact électrique, page 18, pour 

déterminer la bonne trousse requise. Vous devez utiliser l’une des 

méthodes suivantes d’installation.

   La conexión de este producto de 265 voltios de CA a un circuito 

derivado DEBE realizarse mediante una conexión directa de 

acuerdo a las indicaciones del NEC. El código no permite enchufar 

esta unidad a una caja externa.

   Estos modelos deben instalarse utilizando el kit de GE de 

suministro de energía adecuado para el amperaje de circuito 

derivado y el vatiaje deseado para el calefactor de resistencia 

eléctrica. Utilice la TABLA DE CONEXIONES ELÉCTRICAS en la 

página 18 para determinar cuál es el kit necesario. Debe utilizarse 

uno de los siguientes métodos de instalación.

 

 

A.   FOR SUBBASE  

        INSTALLATION

   Electrical subbase kits are available to provide a flexible 

enclosure for direct connection.

 

 *Not approved for use on 7000 BTU models.

   The instructions provided with the selected subbase kit 

must be carefully followed. It is the responsibility of the 

installer to ensure the connection of components is done 

in accordance with these instructions and all electrical 

codes.

 

Branch Circuit and 

Proper GE 

Power 

  Unit Amperage Rating 

Subbase Kit 

Supply Kit

 15 

RAK204E15 

RAK515P

 20 

RAK204E20 

RAK520P

 30 

RAK204E30 

RAK530P*

 

  B.  FOR DIRECT CONNECT  

INSTALLATION

    If an electrical subbase is not used, direct connection to 

branch circuit wiring inside the provided junction box must 

be done in accordance with the following steps.

   Order the following Kit for 265-volt direct connection  

as required:

 

 

 

         

 

 

    

 

*Not approved for use on 7000 BTU models.

Review installation instructions provided with power 

cord or direct connect kits for detailed assembly 

instructions.

 

Branch Circuit and 

Power 

 

Unit Amperage Rating 

Supply Kit

 15 

RAK515D

 20 

RAK520D

 30 

RAK530D*

Branch Circuit and  

Unit Amperage Rating

Power  

Supply Kit

15

RAK315D

20

RAK320D

30

RAK330D*

WARNING

AVERTISSEMENT

ADVERTENCIA

Summary of Contents for Zoneline AZ45

Page 1: ...on Filter 12 Air Filters 13 Installation Instructions Preparation 14 Replacing an Existing Unit 15 Electrical Connection 16 18 Installing the Zoneline 19 20 Optional Drain Kit 21 Troubleshooting Tips...

Page 2: ...TE We strongly recommend that any servicing be performed by a qualified individual These R410A air conditioning systems require contractors and technicians to use tools equipment and safety standards...

Page 3: ...ar les entrepreneurs et les techniciens doivent tre approuv s en fonction du fluide frigorig ne dont le syst me de climatisation R410A du Zoneline est quip N UTILISEZ PAS d quipements certifi s relati...

Page 4: ...r servicio llevado a cabo en este equipo lo realice un individuo calificado Los sistemas de acondicionador de aire R410A requieren que los contratistas y t cnicos utilicen herramientas equipamiento y...

Page 5: ...and Operation Control 1 Sets the fan operation for HIGH or LOW 02 22 For cooling 1 For fan only operation 7 For heating 2 Turns the unit off Power remains connected to the Zoneline The Freeze Heat Sen...

Page 6: ...trol in the closed position The room air will be filtered and circulated Air Direction To change the air direction remove the room front Remove the 4 louver screws that hold the louver insert in place...

Page 7: ...onfirm the selection and exit AUX SET mode 6PDUW DQ RROLQJ HDWLQJ Press MODE until a 1 appears in the first digit of the display for Smart Fan cool mode The COOL LED light on the main control will be...

Page 8: ...t of the display for Freeze Sentinel mode The COOL LEDlight on the main control will be on Press MODE again to change to the Heat Sentinel The HEAT LEDlight on the main control will be on Press the pa...

Page 9: ...The second digit of the display will be between 0 and 7 depending on the limit you want to set The chart shows the limits available Press AUX SET to confirm your selection and exit AUX SET mode or pre...

Page 10: ...stance heat To set All Electric Heat option press MODE until an 8 appears in the first digit of the display Press the or pad to set this switch to OFF or ON This is shown in the second digit of the di...

Page 11: ...thermostat IMPORTANT The Zoneline thermostat connections provide 24 V AConly If using a digital electronic wall thermostat you must set it to the 24 V ACsetting See the Installation Instructions for...

Page 12: ...NT This filter is not removable Trying to remove this filter will damage the unit Use a vacuum to remove debris from the filter Use a damp rag to wipe down the filter and surrounding area after vacuum...

Page 13: ...lters Vacuum off the heavy soil Run water through the filters from the back side Dry thoroughly before replacing NOTE The air filters are interchangeable and will fit in either the right or left side...

Page 14: ...kWLPHQW HQ DOXPLQLXP SHXYHQW SRVHU GHV SUREOqPHV SDUWLFXOLHUV FRQVXOWH XQ pOHFWULFLHQ TXDOL p Quand votre appareil est en position OFF arr t il reste de la ten sion dans les commandes lectriques D bra...

Page 15: ...area as calculated by ASHRAE See the Architects and Engineers Data Manual for more detailed information Any vertical deflectors in the existing rear grille should be removed to decrease condenser air...

Page 16: ...or leakage current detection device on the power cord except direct connect Be sure to select the correct cord for your installation Branch Circuit and Proper GE Power Cord Unit Amperage Rating with...

Page 17: ...La conexi n de este producto de 265 voltios de CA a un circuito derivado DEBE realizarse mediante una conexi n directa de acuerdo a las indicaciones del NEC El c digo no permite enchufar esta unidad a...

Page 18: ...Fan 3 80 3 11 KW Low Fan 230 208 Volt Power Supply Kits 1 Circuit Protective Device Heater Wattage 230 208 Volts RAK315D RAK320D RAK330D 15 Amp Time Delay Fuse or Breaker 20 Amp Time Delay Fuse or Bre...

Page 19: ...the room side of the case The RAB71A B series wall cases are already insulated NOTE For installation with a subbase or duct adapter see the instructions packed with those kits 2 PREPARE THE UNIT Care...

Page 20: ...op 1 then pushing it in at the bottom 2 NOTE There are several extra holes in the unit side flanges for installation in wall cases other than GE To avoid damaging the flange insulation the installer s...

Page 21: ...walls we recommend the use of RAD10 Drain Kit External Drain See the Installation Instructions in the RAD10 kit Internal Drain See the Installation Instructions in the RAD10 kit Type A screw for metal...

Page 22: ...ug interrupter device is tripped or the box near the plug If the RESET button will not stay engaged discontinue use of the Zoneline and contact a qualified service technician Zoneline does not cool In...

Page 23: ...desired NOTE Use of this option will result in increased energy consumption The unit is not The Smart Fan Auxiliary See Smart Fan Cooling Heating on page 5 blowing out air Controls may be set to cycl...

Page 24: ...set up to be in continuous fan the indoor fan will run regardless if the unit may be cooling or heating Other times the fan will run longer than the heating cooling cycle or kick on occasionally This...

Page 25: ...RGL FDWLRQ After mailing the registration below store this document in a safe place It contains information you will need should you require service Our service number is 800 GE CARES 800 432 2737 Rea...

Page 26: ...Please place in envelope and mail to Please place in envelope and mail to Veuillez mettre dans une enveloppe et envoyez 26 Product Registration...

Page 27: ...her rights which vary from state to state or province to province To know what your legal rights are consult your local state or provincial consumer affairs office or your state s Attorney General War...

Page 28: ...hearing impaired please call 800 TDD GEAC 800 833 4322 Parts and Accessories GEAppliances com Individuals qualified to service their own appliances can have parts or accessories sent directly to their...

Reviews: