GFK-1911B
Chapter 6 Diagnostics
6-9
6
Error Type
(FS on, # of
FN pulses)
Error No.
(FS off, #
of FN
pulses)
Meaning
Remedy
Module Errors
1
An error has occurred in
your I/O circuit (e.g.,
short-circuit or overload at
the actuator).
The station and the VersaPoint
module where the I/O error has
occurred can be located using the
Profibus address and the device
number. The error location can
also be detected at the flashing
LED of the VersaPoint module, or
using the device-specific
diagnostics in your control
system. Using the module data
sheet, check which error this error
message can trigger. Remove the
error from your I/O devices.
5
2
Module is not ready.
(IC670PBI002 only)
Determine the exact location
using the device-specific
diagnostics of the control system.
Check the device.
Backplane Errors (IC670PBI002)
6
1
General parameter error
Memory Access Errors (IC670PBI002)
1
Memory not available.
2 Checksum
error
3 Read
error
4 Write
error
5 Initialization
7
6
Saved structure differs from the actual structure.