8-30
VersaPoint™ I/O System Profibus-DP NIU User’s Manual – August 2005
GFK-1911B
8
Module Parameters
Bit 7 to bit 6
00
Start block ID for the device
Configuration
Bit 5 to bit 4
00
No configuration (discrete output modules, no
configuration value block
01 Permanent
configuration
10 Temporary
configuration
Bit 3 to bit 2
Failsafe value
00
No failsafe value (discrete input modules, no failsafe
value block)
01
Zero is output
10
Value is maintained
11
Value from data field is used
Bit 1
PCP
0
No PCP block
1 PCP
block
Byte 1
Bit 0
0
Module activated
1 Module
deactivated
Bit 7 to bit 6
01
ID for configuration block
Byte 2
Bit 5 to bit 0
Length of the data block
Byte 3 to n
N data bytes
Byte x
Bit 7 to bit 6
10
ID for failsafe value block
Bit 5 to bit 0
Length of the data block
Byte x to y
N data bytes
Byte x
Bit 7 to bit 6
11
ID for PCP block
Bit 5 to bit 0
Length of the data block (including index/subindex)
Byte x+1
Index high byte
Byte x+2
Index low byte
Byte x+3
Subindex
Byte x+4 to
y
N data bytes
Summary of Contents for VersaPoint IC220PBI002