Setting the NIU Switches
Configure the hardware using the
1
0-position DIP switch on the NIU module.
Switches
Meaning
1
to 7
Profibus Address in binary format (= 0 to
1
27 in decimal format)
Switch
1
defines the least significant bit (2
0
) and
switch 7 defines the most significant bit (2
6
).
For Module IC220PBI002: Sets the operating mode. With this switch in
the Off position, this module can directly replace module version
IC220PBI00
1
.
With this switch in the On position, this module operates in DP/V
1
mode.
The On position matches the NIU’s default configuration.
8
For Module IC220PBI00
1
: Behavior if a data error occurs in the station
(local bus error):
ON = data transmission is stopped after a number of attempts.
OFF = the station constantly attempts to start data transmission.
If DIP switch 8 is in the ON position, a POWER DOWN/POWER UP must
be executed on the NIU so that it will restart. There is no
automatic
restart after the error has been removed.
9 to
1
0
Reserved, both switches
must
be in the OFF position.