GFK-1911B
Chapter 8 Communications
8-35
8
Error Codes for DP
/
V1 and VC1 Communication
Always observe the individual displays in your working environment.
DP/V1 error:
Function code (response) = DE
hex
(Read error) or DF
hex
(Write error)
Error decode = 80
hex
(DP/V1 communication)
Error with reference to I/O module: Status 44
hex
indicates an error (for DP/V1
on byte 2 of the data block; for VC1 on byte 2 in the response)
Error Code
1 (hex)
Error Code
2
Error Description
A0
hex
0
Module object cannot be read
A1
hex
0
Module object cannot be written
B0
hex
0 Incorrect
module
index
B1
hex
0
PB PDU length is too short
B2
hex
0 Incorrect
slot
B5
hex
0 Module
is
busy
B7
hex
0
Error writing to index 47 or 48
D1
hex
0 No
PCP
connection
D2
hex
0
Module has no PCP
D3
hex
0 Module
timeout
D4
hex
0 Incorrect
service
D5
hex
0 V1
sequence
incorrect
D6
hex
0
VC1 length incorrect
Fx
hex
0
Error writing module parameters
F1
hex
0
Invalid module number was used
F2
hex
0
Parameter block was not complete
F3
hex
0
Data length of the parameter block is too short
F4
hex
0
Data length of the parameter block is too long
F5
hex
0
The internal block for configuration, failsafe value, and PCP is
too small
F6
hex
0
The header byte for the module parameter block is incorrect
F7
hex
0
PCP initialization for a module without PCP functions
F8
0
Too many data blocks for the module
Summary of Contents for VersaPoint IC220PBI002
Page 4: ......
Page 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B...
Page 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5...
Page 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6...
Page 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A...