A-4
VersaPoint™ I/O System Profibus-DP NIU User’s Manual – August 2005
GFK-1911B
A
Mechanical Demands
Mechanical Demands
Vibration test
Sinusoidal vibrations according to
IEC 60068-2-6
2g load, 2 hours for each space direction
(Low-level signal)
2g load, 2 hours for each space direction
(Power level)
Shock test according to IEC
60068-2-27
25g load for
11
ms, half sinusoidal wave, three
shocks in each space direction and orientation.
Noise Immunity Test
Noise Immunity Test
Please refer to the module data sheets for additional information.
In Accordance with EN 50082-2
Electrostatic Discharge (ESD)
EN 6
1
000-4-2 / IEC 6
1
000-4-2
Criteria B, 4kV contact discharge, 8kV air
discharge
Electromagnetic Fields
ENV50
1
40 / ENV50204
Criteria A, Field Strength:
1
0V/m
Bursts
EN 6
1
000-4-4 / IEC 6
1
000-4-4 Criteria A, All
Interfaces:2kV
Conducted Interference
ENV 50
1
4
1
, Criteria A, Test voltage
1
0V
In Accordance with EN 50082-2
Noise Emission of the Housing
EN 50
11
, Class A