Chapter 5. Ethernet Global Data
GFK-2224Q
January 2017
85
Command Block for Enable/Disable PLC Time Update COMMREQ
Word Offset Value
Description
Word 1
Length of command data block.
Always 2
Word 2
0
Always 0 (Wait/No Wait mode request).
Word 3
For a list of memory type codes, see
“COMMREQ Status for the EGD
Commands” in Chapter 6.
Memory type of the COMMREQ status word.
Word 4
0-based
Offset of COMMREQ status word. For CRS word
values, refer to page 86.
Word 5
0
Always 0.
Word 6
0
Always 0.
Word 7
5002
Enable/Disable Time Update command number
Word 8
1 = Enable PLC time update
0 = Disable PLC time update
This word contains the value to enable or disable
this Ethernet interface to update the PLC clock. This
word must be set to 0 to disable PLC clock updates,
and set to 1 to enable PLC clock updates. All other
values will cause COMMREQ to return a failure
status.