Chapter 2. Installation and Start-up: RX3i Embedded Interface
18
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
Note:
When a CPE330 is configured as a CPU320, Ethernet properties cannot be configured.
However, the embedded Ethernet ports may be used with the default IP Addresses.
Connection to a 10Base-T / 100Base Tx Network
Either shielded or unshielded twisted pair cable may be attached to a port. The 10Base-T/100Base Tx twisted
pair cable must meet the applicable IEEE 802 standards. Category 5 cable is required for 100BaseTX operation.
The Ethernet port automatically senses the speed (10Mbps or 100Mbps), duplex mode (half-duplex or full-
duplex) and cable configuration (straight-through or crossover) attached to it with no intervention required.
10Base-T/100Base Tx Port Pinouts
Pin Number
Signal
Description
1
TD+
Transmit Data +
2
TD–
Transmit Data –
3
RD+
Receive Data +
4
NC
No connection
5
NC
No connection
6
RD–
Receive Data –
7
NC
No connection
8
NC
No connection
Note:
Pin assignments are provided for troubleshooting purposes only. 10Base-T/100Base-Tx
cables are readily available from commercial distributors. We recommend purchasing
rather than making 10Base-T/100Base-Tx cables.
The programmer is connected to the Ethernet Interface through a 10Base-T or 100Base-Tx network.
10BaseT/100Base Tx Twisted Pair Cable
Hub/Switch/Repeater
To other network devices
Ethernet Port
on RX3i CPExxx
Programmer
Figure 5: Ethernet Cable Routing
4
Pin 1 is at the bottom right of the Station Manager port connector as viewed from the front of the module.
Summary of Contents for PACSystems RX7i
Page 45: ......
Page 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Page 81: ......
Page 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Page 147: ......
Page 211: ......
Page 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Page 263: ......