Chapter 4. Configuration
GFK-2224Q
January 2017
35
Configuring the Ethernet Interface Parameters
First, establish communications between the computer hosting PME and the CPU. Consider the following
methods:
Default IP Addresses for
CPE305/CPE310/CPE330/CPE400
Embedded Ethernet
Initial Ethernet communication with the CPU may be established using
the default IP addresses programmed at the factory:
Note
that the IP subnet 192.168.180.x is reserved on the CPE400. It is
not available for configuration on any of the CPU’s Ethernet ports.
CPE305/CPE310 and
CPE330/CPE400 LAN1
CPE330/CPE400 LAN2
CPE400
LAN3
IP
Address:
192.168.0.100
10.10.0.100
0.0.0.0
Subnet
Mask:
255.255.255.0
255.255.255.0
0.0.0.0
Gateway:
0.0.0.0
0.0.0.0
0.0.0.0
Connecting to CPE305/CPE310
Embedded Ethernet when
IP Addresses are not known
If the IP address of the CPE305/CPE310 embedded Ethernet interface is
not known, communication may be established using one of these
methods to set a permanent IP addresses:
•
Connect to the CPE305/CPE310 via its serial port and assign an IP
Address to the embedded Ethernet interface by downloading a
hardware configuration.
•
Connect to the CPE305/CPE310 with PME using an IC695ETM001
module with a known IP address and located in the same rack.
Download a new hardware configuration with the desired IP
address for the embedded Ethernet interface.
Connecting to CPE330 Embedded
Ethernet when IP Addresses are
not known
If the IP addresses of the CPE330 embedded LAN 1 and LAN 2 Ethernet
interfaces are not known, communication may be established using
one of these methods to set new IP addresses:
•
Setting a Temporary IP Address using the
Set Temporary IP Address
tool in Proficy Machine Edition (PME). After setting the temporary
address, connect to the selected CPE330 LAN using PME and
download a new hardware configuration with the desired
permanent IP addresses.
•
Connect to the CPE330 with PME using an IC695ETM001 module
with a known IP address and located in the same rack. Download a
new hardware configuration with the desired permanent IP
addresses for the CPE330 embedded Ethernet interfaces.
Connecting to CPE400 Embedded
Ethernet when IP Addresses are
not known
Use the OLED display to read the IP Address of any LAN. Note: the
Set
Temporary IP Address
tool is not available for CPE400.
7
LAN3 is disabled in the initial release of CPE400 (firmware version 9.00).
Summary of Contents for PACSystems RX7i
Page 45: ......
Page 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Page 81: ......
Page 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Page 147: ......
Page 211: ......
Page 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Page 263: ......