Chapter 10. OPC UA Server
178
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
OPC UA Server – Service Request – RESTART
This function stops and then restarts the OPC UA server on a target.
Note:
This request can only be successfully performed when the OPC UA server is started.
Parameters for the START function service request are:
Parameter
Summary
Data Direction
(LD perspective)
16#0001
OPC UA protocol
IN
16#0005
RESTART request
IN
-1440 to 1440
Time Zone Offset
IN
If the SVC_REQ does not pass power, the operation did not complete. The time zone offset adjusts the OPC UA
server time zone. The Controller’s Time of Day clock must be synchronized to ‘local’ time and the time zone
offset is your location’s offset relative to UTC time.
Example:
Note:
In this example a Time Zone Offset of -300 was used, meaning local time is UTC minus
300 minutes (5 hours).