Chapter 2 Monitor Level Commands
2-63
2
Field
Description
Phase
Determines which time slot within an IO update cycle an I/O
frame is sent when the Reduction Ration is greater than 1. See
PROFINET Application Layer Services for Decentralized
Periphery and Distributed Automation Specification
, Version 2.2,
October 2007, for definition of Phase.
FrmOffset
Frame Send Offset. The relative time offset from the start of a
Send Clock Time cycle to transmit the RTC Frame associated
with this IOCR in nanosecond units. See
PROFINET Application
Layer Services for Decentralized Periphery and Distributed
Automation Specification
, Version 2.2, October 2007. for
definition of Frame Send Offset.
WatchDg
Watchdog Factor. See PROFINET Application Layer Services for
Decentralized Periphery and Distributed Automation
Specification, Version 2.2, October 2007. for definition of
Watchdog Factor.
DataHold
Data Hold Factor. See PROFINET Application Layer Services
for Decentralized Periphery and Distributed Automation
Specification, Version 2.2, October 2007, for definition of Data
Hold Factor.
APIs
The number of Application Relationships contained within this
IOCR. The value can be 1 or 2.
<<< API 0 >>>
API number of the following data, 0 in this example indicates the
API number.
ObjType
The type of data located at the Frame Offset within the RTC
frame associated with this IO Communication Relationship
(IOCR). The possible meaning and values are:
InData – Input data transferred from the IO module to the
controller. This data also includes IO Provider Status (IOPS)
associated with the input data.
OutData – Output data transferred from the controller to the IO
module. This data also includes the IOPS associated with the
output data.
InIOCS – the IO Consumer Status (IOCS) status associated with
the input data of the IO module transferred from the controller to
the IO Device.
OutIOCS – the IOCS status associated with the output data of
the output module transferred from the IO-Device to the
controller.
Slot#
The slot number of the module associated with the ObjType.
Subslot#
The subslot number of the module associated with the ObjType.
FrmOffset
The offset in the RTC frame associated with the IOCR where the
module’s Input/Output data or IOCS data is transmitted.
ModId
The Module Identification value associated with the IO Module.
For GE Intelligent Platforms modules, the lowest word contains
the major and minor types for the module.