889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
BREAKERS
CHAPTER 5: STATUS
Breakers
Path:
Status > Breaker > Breaker X
STATE
Range: Not Configured, Opened, Closed, Unknown
The Unknown state is displayed upon discrepancy of the 52a and 52b contacts for more
than 30 milliseconds.
TRIP COIL
The Trip Coil state is displayed when Form -A output relays are used, and Trip Coil
monitoring is enabled.
CLOSE COIL
The Close coil state is displayed when Form -A output relays are used, and Close Coil
monitoring is enabled.
TOTAL ARCING CURRENT
The measure of arcing current from all three phases during breaker trips. Refer to the
Breaker Arcing Current element description for more details.
Switches
The status of each switch is displayed in a table under Status\ Switches menu.
Path:
Status > Switches
SWITCH 1(X)
Range: Not Configured, Opened, Closed, Intermittent, Discrepancy
Default: Not Configured
Last Trip Data
There is no Enabling/Disabling of this feature. It is always ‘ON’.
Path
:
Status > Last Trip Data
CAUSE
Range: Off, any FlexLogic Operand
Default: No trip to Date
EVENT
Range: 0 to 4294967295 in steps of 1
Default: 0
DATE
Range: MM/DD/YYYY HH:MM
Default: 01/01/08 00:00:00
PARAMETER 1 to 64
Range: -2147483648 to 2147483647 in steps of 1
Default: 0