889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL
CHAPTER 4: SETPOINTS
Figure 4-142: Navigation and SLD component selection
PB “Block” (Hardcoded SLD Pushbutton)
Blocking of a breaker or switch can be used for simply inhibiting the close or open
operation while in Local Mode. The selected breaker or disconnect switch can be blocked.
If block was not applied to the selected component, pressing “Block” PB will block either
the Open or Close command depending on the existing state (see
Pushbutton “Block” logic diagram
). For example, if the selected component is in opened
state, pressing the PB “Block” will block the closing command, and vice versa (see figures:
Local Control for breakers/Local Control for switches). When the block is active, the letter
“B” appears in the SLD next to the controlled component
894195A1.cdr
MESSAGE
SLD Breaker Selection
5 min
Timer
Clears the selection
Setpoint
Bkr/Sw Select Timeout
OR
AN
D
OR
SLD Switch Selection
PB “ESCAPE”
BKR 1
BKR 2
BKR 3
Local Mode ON
FLEXLOGIC OPERAND
BKR 1 Selected
FLEXLOGIC OPERANDS
BKR 2 Selected
BKR 3 Selected
SW 1 Selected
SW 2 Selected
SW 3 Selected
SW 4 Selected
SW 5 Selected
SW 6 Selected
SW 7 Selected
SW 8 Selected
NOTE: The selection of Breakers and Switches is
available only to those of them configured and included in
the SLD. Not used breakers and switches are skipped
from the sequence during navigation.
ESCAPE
ENTER
Navigation Pushbuttons
AN
D
AN
D
AN
D
AN
D
AN
D
AN
D
AN
D
AN
D
AN
D
AN
D
AN
D
SW 1
SW 2
SW 3
SW 4
SW 5
SW 6
SW 7
SW 8
AN
D
PB “ENTER”
FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND
SBO Enabled