![GE Multilin 889 Instruction Manual Download Page 43](http://html.mh-extra.com/html/ge/multilin-889/multilin-889_instruction-manual_123014043.webp)
CHAPTER 1: INTRODUCTION
SPECIFICATIONS
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
1–33
Physical
DIMENSIONS
Size: ...........................................................................
Refer to Chapter 2
Weight:..................................................................... 9 kg [20.0 lbs]
Environmental
Make and Carry
IEEE C37.90
30A /200 ops
Electrostatic Discharge (ESD)
IEEE/ANSI C37.90.3
8kV CD/ 15 kV AD
Product Safety
IEC60255-27
As per Normative sections
Rated Burden,
IEC60255-1
Sec 6.10
Contact Performance
IEC60255-1
Sec 6.11
Ambient temperatures:
Storage/Shipping:
-40°C to 85°C
Operating:
-40°C to 60°C
Humidity:
Operating up to 95% (non condensing) @ 55°C (As per
IEC60068-2-30 Variant 2, 6 days)
Altitude:
2000m (standard base reference evaluated altitude)
5000m (maximum achievable altitude)
Pollution Degree:
II
Overvoltage Category:
II
Ingress Protection:
IP54 Front
Insulation Class:
1
Noise:
0 dB