CHAPTER 4: SETPOINTS
FLEXLOGIC
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–377
Non-Volatile Latch 1 to 16 NV Latch 1 ON
NV Latch 1 OFF
Any PKP
Any OP
Any Trip
Any Alarm
NV Latch 2 to 16
The output of non-volatile latch 1 is On
The output of non-volatile latch 1 is Off
Any enabled protection or control element pickup
Any enabled protection or control element operated
Any operated element with Function selected as “Trip”
Any operated element with Function selected as “Alarm”
The same set of operands as per Non-Volatile Latch 1
Offline Overcurrent
Offline OC PKP
Offline OC PKP A
Offline OC PKP B
Offline OC PKP C
Offline OC OP
Offline OC OP A
Offline OC OP B
Offline OC OP C
Offline overcurrent element pickup.
Offline overcurrent element Ph A pickup.
Offline overcurrent element Ph B pickup.
Offline overcurrent element Ph C pickup.
Offline overcurrent element operate.
Offline overcurrent element Ph A operate.
Offline overcurrent element Ph B operate.
Offline overcurrent element Ph C operate.
Out of Step
OOS OP
OOS Lft Bld PKP
OOS Rgt Bld PKP
OOS Timer PKP
Out-of-step tripping element operated
Positive-sequence impedance in mho and left blinder characteristic
Positive-sequence impedance in mho and right blinder characteristic
Out-of-step timer picked up
Output Relays
Trip ON
Close ON
Aux Relay [X] ON
BKR [X] Manual Open
BKR [X] Manual Close
Trip command to Relay 1 (TRIP) has been issued
Close command to Relay 2 (CLOSE) has been issued
Command to Aux Relay [X] has been issued
Either Local (using PBs) Open or Remote Open command has been issued
to the output relay selected under BKR[X] Trip Relay Select setpoint
Either Local (using PBs) Close or Remote Close command has been issued
to the output relay selected under BKR[X] Close Relay Select setpoint
OverFrequency
Overfreq 1 PKP
Overfreq 1 OP
Overfreq 2
Overfrequency 1 has picked up
Overfrequency 1 has operated
The same set of operands as per Overfreq 1
Overall Percent
Differential
Ovrl Percent Diff PKP A
Ovrl Percent Diff PKP B
Ovrl Percent Diff PKP C
Ovrl Percent Diff PKP
Ovrl Percent Diff OP A
Ovrl Percent Diff OP B
Ovrl Percent Diff OP C
Ovrl Percent Diff OP
Ovrl Percent Diff Warn
Ovrl Percent Diff Blocked
Ovrl Percent Diff Sat A
Ovrl Percent Diff Sat B
Ovrl Percent Diff Sat C
Ovrl Percent Diff Sat
Ovrl Percent Diff Dir A
Ovrl Percent Diff Dir B
Ovrl Percent Diff Dir C
Ovrl Percent Diff Dir
2nd Harm Diff A
2nd Harm Diff B
2nd Harm Diff C
5th Harm Diff A
5th Harm Diff B
5th Harm Diff C
Percent A differential has picked up
Percent B differential has picked up
Percent C differential has picked up
At least one Percent differential element has picked up
Phase A differential has operated
Phase B differential has operated
Phase C differential has operated
At least one Percent differential element has operated
Percent differential current exceeded 0.5 x PKP for 10 seconds
Percent differential protection has been blocked
Percent differential flag triggered on phase A
Percent differential flag triggered on phase B
Percent differential flag triggered on phase C
Percent differential flag triggered
Percent differential directional flag triggered on phase A
Percent differential directional flag triggered on phase B
Percent differential directional flag triggered on phase C
Percent differential directional flag triggered
2
nd
harmonic Phase A diff. current block detected
2
nd
harmonic Phase B diff. current block detected
2
nd
harmonic Phase C diff. current block detected
5
th
harmonic Phase A diff. current block detected
5
th
harmonic Phase B diff. current block detected
5
th
harmonic Phase C diff. current block detected
Overload Alarm
Overload Alarm PKP
Overload Alarm OP
Overload alarm has picked up.
Overload alarm has operated.
ELEMENT
OPERANDS
EVENT DESCRIPTION