CHAPTER 4: SETPOINTS
PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–193
DIRECTION
Range: Disabled, Forward, Reverse
Default: Disabled
This setting defines the operation direction of the Sensitive Ground TOC element.
Entering the direction for the Sensitive Ground TOC element does not automatically
apply the selection. The direction detection is performed by the element Sensitive
Ground Directional OC, which must be enabled and configured according to the
directionality criteria of the feeder currents.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The Sensitive Ground TOC is blocked, when the selected operand is asserted.
OUTPUT RELAY X
For details see
EVENTS
Range: Enabled, Disabled
Default: Enabled
The selection of the Enabled setting enables the events of Sensitive Ground TOC function.
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
The selection of Self-reset or Latched settings enables the targets of the Sensitive
Ground TOC function.