CHAPTER 4: SETPOINTS
PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–135
Inadvertent
Energization (50/27)
This element provides protection against inadvertent energization also known as
accidental energization. The Inadvertent Energization feature may be armed when all of
the phase voltages fall below the undervoltage pickup level and/or the unit is offline. When
the feature is armed, if any one of the phase currents measured at the output CTs exceeds
the overcurrent level programmed, an operate will occur.
Protection can be provided for poor synchronization by using the "U/V or Offline" arming
signal. During normal synchronization, there should be relatively low current measured. If
however, synchronization is attempted when conditions are not appropriate, a large
current that is measured within 250 ms after the generator is placed online would result in
an operate.
NOTE
NOTE:
This feature requires 5 s to arm, and 250 ms to disarm.
Path
:
Setpoints > Protection > Group 1(6) > Generator > Inadvertent Energization
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
ARMING MODE
Range: U/V and Offline, U/V or Offline
Default: U/V and Offline
The element is armed based on the U/V condition and/or Offline status.
O/C PICKUP
Range: 0.050 to 30.00 x CT in steps of 0.01 x CT
Default: 0.30 x CT
This setting is the overcurrent level of any phase currents required to allow the element
to operate.
U/V PICKUP
Range: 0.00 to 1.50 x VT in steps of 0.01 x VT
Default: 0.50 x VT
This setting sets the undervoltage level of three-phase voltage required to arm the
element. When this setting is zero and ARMING MODE is set to U/V or Offline, the
undervoltage supervision will be bypassed and the arming mode will check the
generator Offline status only.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
EVENTs
Range: Enabled, Disabled
Default: Enabled
TARGETs
Range: Self-reset, Latched, DIsabled
Default: Self-reset