CHAPTER 4: SETPOINTS
MONITORING
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–291
ALARM LEVEL
Range: 0 to 50000 kA2-c in steps of 1 kA2-c
Default: 1000 kA2-c
The setpoint specifies the threshold value (kA2-cycle) above which the output operand is
set.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAYS X
For details see
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset