CHAPTER 4: SETPOINTS
OUTPUTS
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–105
BLOCK
Range: Disabled, Any FlexLogic operand
Default: Disabled
This setting defines a Block to the Trip output relay. When the selected input is asserted,
the Trip output relay is blocked.
TYPE
Range: Self-Reset, Latched, Pulsed
Default: Latched
This setting defines the sequence type of the Trip output relay. The functionality is
described in the Outputs > Output Relays > Trip and Close Relays section.
OPERATION
Range: Non-Failsafe, Failsafe
Default: Non-Failsafe
Failsafe operation causes the output relay to be energized when the Trip condition
signal is low and de-energized when the same signal is high. A failsafe relay also
changes state (if not already activated by an operand driving this output relay) when
control power is removed from the 889. Conversely a non-failsafe relay is de-energized
in its normal non-activated state and will not change state when control power is
removed from the 889 (if not already activated by a protection element).
EVENTS
Range: Disabled, Enabled
Default: Enabled
NOTE
NOTE:
When the setpoint Function in the protection element menu is set to "Trip", the output
relays selected under the Breaker menu for breaker tripping need to be re-selected from
the protection element menu. These output relays will not be operational even if selected
to operate from the protection element menu, if the function is set to "Alarm", "Latched
Alarm", or “Configurable”.