4–300
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING
CHAPTER 4: SETPOINTS
MINIMUM VOLTAGE
Range: 0.00 to 1.25 x VT in steps of 0.01 x VT
Default: 0.30 x VT
This setting sets the minimum voltage for the Power Factor element operation specified
times VT.
MINIMUM CURRENT
Range: 0.00 to 10.00 x CT in steps of 0.01 x CT
Default: 0.20 x CT
This setting sets the minimum current for the Power Factor element operation specified
times CT.
MINIMUM CURRENT
Range: 0.00 to 10.00 x CT in steps of 0.01 x CT
Default: 0.20 x CT
This setting sets the minimum current for the Power Factor element operation specified
times CT.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The element is blocked when the selected operand is asserted.
EVENTS
Range: Enabled, Disabled
Default: Enabled
The selection of the Enabled setting enables the events of the function.
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset