05-2806A01, Rev. L
MDS iNET Series Reference Manual
63
Invisible place holder
Figure 2-51. Mixed-Modes Application Diagram
Table 2-4. Serial Port Application Configuration
Transceiver Location
Menu Item
Setting
Access Point
Status
Enabled
Baud Rate
9,600
Flow Control
Disabled
IP Protocol
UDP
Send to Address
A multicast IP address such as
224.254.1.1
Send to Port
30011
Receive on Port
30011
Receive on Address
0.0.0.0 (Not Used)
Remote Units 1 & 2 (COM2)
Status
Enabled
Baud Rate
2,400
Flow Control
Disabled
IP Protocol
TCP
Receive on Port
30011
Remote Units 3 & 4 (COM2)
Status
Enabled
Baud Rate
9,600
Flow Control
Disabled
IP Protocol
UDP
Send to Address
IP address of the AP
Send to Port
30011
Receive on Port
30011
Receive on Address
224.254.1.1
(The multicast IP address used
for the AP’s Send To Address
above)
EIA-232
Terminal
or Computer
RTU–C
EIA-232
EIA-232
EIA-232
RTU–D
EIA-232
LA
N
COM
1
COM
2
PW
R
LIN
K
i
NET 900
Remote 4
Ethernet
Crosssover
RTU–B
RTU–A
i
NET 900
Access Point
LA
N
COM
1
COM
2
PW
R
LIN
K
i
NET 900
Remote 1
LA
N
COM
1
COM
2
PW
R
LIN
K
i
NET 900
Remote 2
LA
N
COM
1
COM
2
PW
R
LIN
K
i
NET 900
Remote 3
Summary of Contents for MDS iNET Series
Page 12: ...x MDS iNET Series Reference Manual 05 2806A01 Rev L...
Page 159: ...05 2806A01 Rev L MDS iNET Series Reference Manual 147 Figure A 22 EDS Wizard Completion Screen...
Page 165: ...05 2806A01 Rev L MDS iNET Series Reference Manual 153 NOTES...
Page 166: ...154 MDS iNET Series Reference Manual 05 2806A01 Rev L NOTES...