10PA / 10PE
P. 1 / 2
EM-0838 Rev.2
INSTRUCTION MANUAL
MODEL
10PA/10PE
PT TRANSMITTER
COMPONENT IDENTIFICATION
INSTALLATION
Use Standard Rack (model: 10BX
❑
).
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the
connection diagram label on the unit side.
CHECKING
1) Terminal wiring: Check that all cables are correctly
connected according to the connection diagram.
2) Power input voltage: Check voltage supplied to the rack
(model: 10BX
❑
). For the DC power source, be sure that
the ripple level is within 10% p-p.
3) Input: Check that the input signal is within 0 – 120% of
the full-scale.
Be sure that the input waveform is sinusoidal to obtain
proper accuracy for model 10PA.
4) Output: Check that the load resistance meets the de-
scribed specifications.
Zero Adj.
Span Adj.
Output 1
Body
Specification Label
Connection Diagram
Label
(side)
Zero Adj.
Output 2
*
Span Adj.
Terminal Cover
*
Provided only when the second output is selected.
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
package you received as below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■
PACKAGE INCLUDES:
Signal conditioner ................................................... (1)
■
MODEL NO.
Check that model No. described on specification label is
exactly what you ordered.
■
INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, installation, connection and basic mainte-
nance procedures.
POINTS OF CAUTION
■
POWER INPUT RATINGS
• Power input ratings are specified by the model number
suffix code. Check the power input voltage for the unit on the
specification label.
24V DC
±
10%, approx. 35mA with Voltage Output 1
approx. 55mA with Current Output 1
■
GENERAL
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■
ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +55
°
C (23
to 131
°
F) with relative humidity within 30 to 90% RH in order
to ensure adequate life span and operation.
■
WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
■
AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
V
U
v
u
FUSE
PT
LOAD
SOURCE
+
–
1
OUTPUT 1
2
7
8
+
–
OUTPUT 2
5
6
CONNECTOR
*
1 output type has the output 1 connected to the
card-edge connector in parallel.
OUTPUT 2
*
POWER