CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE
2-185
2
F086
ENUMERATION: CONTACT INPUT DEFAULT STATE
0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On
F088
ENUMERATION: 87PC PHASE COMPARISON SCHEME
SELECTION
F089
ENUMERATION: 87PC SIGNAL SOURCE
1 = One Source Current, 2 = Two Sources Current
F090
ENUMERATION: LATCHING OUTPUT TYPE
0 = Operate-dominant, 1 = Reset-dominant
F091
ENUMERATION: VOLTAGE DIFFERENTIAL BANK GROUND
TYPE
0 = Grounded, 1 = Ungrounded
F092
ENUMERATION: AUTOMATIC SETTING FUNCTION
0 = Disabled, 1 = Manual, 2 = Auto
F093
ENUMERATION: BANK OVERVOLTAGE GROUND TYPE
0 = Grounded, 1 = Ungrounded, 2 = Ungrounded without Vn
F094
ENUMERATION: BANK OVERVOLTAGE CURVE TYPE
0 = FlexCurve A, 1 = FlexCurve B, 2 = FlexCurve C,
3 = FlexCurve D
F095
ENUMERATION: REDUCED VOLTAGE START TRANSITION
MODE
0 = Current Only, 1 = Current or Timer, 2 = Current and Timer
F096
ENUMERATION: THERMAL MODEL CURVE EFFECT
0 = Cutoff, 1 = Shift
F097
ENUMERATION: MOTOR ACCELERATION MODE
0 = Definite Time, 1 = Adaptive
F098
ENUMERATION: MOTOR STATUS
0 = Offline, 1 = Starting, 2 = Running, 3 = Overload
F099
ENUMERATION: MOTOR CURVES
0 = Motor, 1 = FlexCurve A, 2 = FlexCurve B,
3 = FlexCurve C, 4 = FlexCurve D, 5 = IEC
F100
ENUMERATION: VT CONNECTION TYPE
0 = Wye, 1 = Delta
F101
ENUMERATION: MESSAGE DISPLAY INTENSITY
0 = 25%, 1 = 50%, 2 = 75%, 3 = 100%
F102
ENUMERATION: DISABLED/ENABLED
0 = Disabled, 1 = Enabled
F103
ENUMERATION: CURVE SHAPES
Value
Scheme
0
2TL-TR-SPC-2FC
1
2TL-BL-SPC-2FC
2
2TL-UB-DPC-2FC
3
2TL-TR-DPC-3FC
4
2TL-BL-DPC-3FC
5
3TL-TR-SPC-2FC
6
3TL-BL-SPC-2FC
7
3TL-TR-DPC-3FC
8
3TL-BL-DPC-3FC
Bitmask Curve shape
Bitmask Curve shape
0
IEEE Mod Inv
9
IAC Inverse
1
IEEE Very Inv
10
IAC Short Inv
2
IEEE Ext Inv
11
I2t
3
IEC Curve A
12
Definite Time
4
IEC Curve B
13
FlexCurve A
5
IEC Curve C
14
FlexCurve B
6
IEC Short Inv
15
FlexCurve C
7
IAC Ext Inv
16
FlexCurve D