CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-105
3
3.5.2.71 100% stator ground (Statr)
This element is instantiated in the following products: G60.
Table 3-118: Stator ground data objects
Sat
φ
SPS
STATOR DIFF # SAT
θ
operand
R
stVal
BOOLEAN
ST STATOR DIFF # SAT
θ
R
PhDir
φ
SPS
STATOR DIFF # DIR
θ
operand
R
stVal
BOOLEAN
ST STATOR DIFF # DIR
θ
R
BlkRef
γ
ORG
STATOR DIFF BLK for setting group
γ
.
R
setSrcRef
ObjectReference SP STATOR DIFF BLK for group
γ
.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: StatrPHIZ1
LDevice inst: Prot
UR element: 100% stator ground element core functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
100% STATOR PKP operand
R
general
BOOLEAN
ST 100% STATOR PKP
R
dirGeneral
ENUMERATED
ST
0
R
Op
ACT
100% STATOR OP operand
R
general
BOOLEAN
ST 100% STATOR OP
R
Dpo
SPS
100% STATOR DPO operand
R
stVal
BOOLEAN
ST 100% STATOR DPO
R
Ha3NV
MV
STATOR GND 3RD HARM VN in volts
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
STATOR GND 3RD HARM VN
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29, the code for volts (W/A)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF StatrPHIZ1.Ha3NV.db
R/W/C
zeroDb
INT32U
CF
0
R
Ha3ZroV
MV
STATOR GND 3RD HARM V0 in volts
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
STATOR GND 3RD HARM V0
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29, the code for volts (W/A)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF StatrPHIZ1.Ha3ZroV.db
R/W/C
zeroDb
INT32U
CF
0
R
SumHa3N
VZroV
MV
STATOR GND 3RD HARM VN+V0 in volts
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
STATOR GND 3RD HARM VN+V0
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29, the code for volts (W/A)
R
LNName: SttDifPDIF#
LDevice inst: Prot
UR element: Stator Differential Function
data obj. data attribute
Type
FC UR Name
Description
R/W/C