2-186
UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
F104
ENUMERATION: RESET TYPE
0 = Instantaneous, 1 = Timed
F106
ENUMERATION: PHASE ROTATION
0 = ABC, 1 = ACB
F108
ENUMERATION: OFF/ON
0 = Off, 1 = On
F109
ENUMERATION: CONTACT OUTPUT OPERATION
0 = Self-reset, 1 = Latched, 2 = Disabled
F111
ENUMERATION: UNDERVOLTAGE CURVE SHAPES
0 = Definite Time, 1 = Inverse Time
F112
ENUMERATION: RS485 BAUD RATES
F113
ENUMERATION: PARITY
0 = None, 1 = Odd, 2 = Even
F114
ENUMERATION: IRIG-B SIGNAL TYPE
0 = None, 1 = DC Shift, 2 = Amplitude Modulated
F116
ENUMERATION: NEUTRAL OVERVOLTAGE CURVES
0 = Definite Time, 1 = FlexCurve A, 2 = FlexCurve B,
3 = FlexCurve C
F118
ENUMERATION: OSCILLOGRAPHY MODE
0 = Automatic Overwrite, 1 = Protected
F120
ENUMERATION: DISTANCE SHAPE
0 = Mho, 1 = Quad
Fixed at Mho in G60.
F122
ENUMERATION: ELEMENT INPUT SIGNAL TYPE
0 = Phasor, 1 = RMS
F123
ENUMERATION: CT SECONDARY
0 = 1 A, 1 = 5 A
F124
ENUMERATION: LIST OF ELEMENTS
8
IAC Very Inv
Bitmask Value
Bitmask Value
Bitmask Value
0
300
4
9600
8
115200
1
1200
5
19200
9
14400
2
2400
6
38400
10
28800
3
4800
7
57600
11
33600
Bitmask Curve shape
Bitmask Curve shape
Products
Bit
mas
k
Element
All except B90, C30 0
Phase Instantaneous Overcurrent 1
"
1
Phase Instantaneous Overcurrent 2
B30, C60, C70, D60,
F35, F60, G30, G60,
L30, L60, L90, M60,
N60, T35, T60
2
Phase Instantaneous Overcurrent 3
"
3
Phase Instantaneous Overcurrent 4
B30, C60, C70, D60,
F35, F60, L90, M60,
N60, T35, T60
4
Phase Instantaneous Overcurrent 5
"
5
Phase Instantaneous Overcurrent 6
B30, C60, C70, F35,
F60, L90, M60, N60,
T35, T60
6
Phase Instantaneous Overcurrent 7
"
7
Phase Instantaneous Overcurrent 8
B30, C70, F35, N60,
T35, T60
8
Phase Instantaneous Overcurrent 9
"
9
Phase Instantaneous Overcurrent 10
"
10
Phase Instantaneous Overcurrent 11
"
11
Phase Instantaneous Overcurrent 12
B30, C60, C70, D30,
D60, F35, F60, G30,
G60, L30, L60, L90,
M60, N60, T35, T60
16
Phase Time Overcurrent 1
"
17
Phase Time Overcurrent 2
"
18
Phase Time Overcurrent 3