3-136
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF PIDRegFPID#.DeltaOut.db
R/W/C
zeroDb
INT32U
CF
0
R
Spt
MV
PID # Setpoint value
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
PID # Setpoint
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF PIDRegFPID#.Spt.db
R/W/C
zeroDb
INT32U
CF
0
R
PIDAlg
ENG
Algorithm, which is fixed at PID
R
setVal
ENUMERATED
SP
7, the code for PID
R
KP
ASG
PID # PROPORTIONAL GAIN setting
R
setMag
AnalogueValue SP
R
setMag.i
INT32
PID # PROPORTIONAL GAIN
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
sVC
ScaledValue
Config
CF
R
sVC.scaleFactor
FLOAT32
1/100
R
sVC.offset
FLOAT32
0
R
KI
ASG
PID # Integral gain value
R
setMag
AnalogueValue SP
R
setMag.i
INT32
PID # PROPORTIONAL GAIN
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
sVC
ScaledValue
Config
CF
R
sVC.scaleFactor
FLOAT32
1/100
R
sVC.offset
FLOAT32
0
R
ITmms
ING
PID # INTEG. TIME CONST. setting in
milliseconds
R
setVal
INT32
SP PID # INTEG. TIME CONST. scaled
to make the result in
milliseconds
R
minVal
INT32
CF
0
R
maxVal
INT32
CF
600,000
R
stepSize
INT32
CF
10
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
4, the code for time in seconds
R
units.multiplier
ENUMERATED
-3, the code for a multiplier of 0.001 (i.e.
Milli)
R
KD
ASG
PID # Derivative gain value
R
setMag
AnalogueValue SP
R
LNName: PIDRegFPID#
LDevice inst: Ctrl
UR element: PID Regulator element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C