3-212
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
CompLevel
MV
Indicates the level of the broken rotor bar spectral component relative to the
spectral component of the system frequency.
The COMPONENT LEVEL in dB.
BknRotSVBR
ConfRev
ING
Expected value of confRev field in messages subscribed to by RxGOOSE#
LGOS
CrcFail1
SPS
The CRC error threshold has been exceeded.
The 87L DIFF CH 1 CRCFAIL operand, which becomes On when the differential
element has detected the CRC error threshold has been exceeded on channel 1.
LinDfPDIF
Ctrl
SPS
Asserted for one second upon any transition in any mode
LoVStrGAPC
CurUnb
MV
% UNBALANCE CURRENT
AmpUnbPTOC
Day1
SPS
Current day, where 1 = Sunday. The DAY operand.
TmDayGAPC
DayofMonth
INS
Represents the day of current month (range 1 to 31).
The DayOfMonth Actual Value to represent in date of month in number form.
TmDayGAPC
DayofYear
INS
Represents the day of the year (range 1 to 366).
The DayOfYear Actual Value to represent day of year in number form.
TmDayGAPC
DbMax1
ASG
Value of “max.” in deadband calculations
FTDRsGGIO1, GGIO4
DbMin1
ASG
Value of “min.” in deadband calculations
FTDRsGGIO1, GGIO4
Deactivated
SPS
Indicates PUSHBUTTON # OFF state. When user pushbutton is asserted, status is
"false"; when user pushbutton is released, status is "true."
The PUSHBUTTON 1 OFF operand.
UsrPbIHMI
DeaV1
SPS
This data object indicates that V1 is below the DeaVal1 setting.
The SYNC 1 V1 BELOW MAX operand.
SynChkRSYN
DeltaOut
MV
PID Delta Output value
PIDRegFPID
DifA2ndH
WYE
Phase differential current
PctDifPDIF
DifA5thH
WYE
Phase differential current
PctDifPDIF
DifVPh
WYE
Differential voltage in per unit for phase A, B, and C
VDifPDIF
DirSupn
SPS
Directional overcurrent supervision status (not instantiated for zone 1
GndDisPDIS1).
The GND DIST Z2 DIR SUPN operand.
GndDisPDIS
Disabled
SPS
Function is disabled
Rec13pRREC, Rec3pRREC
DisArmed
SPS
Indicates the high impedance fault detection element is in disarmed state
HiZPHIZ
DischargeTms
MV
Capacitor discharge time in seconds.
CAP 1 DISCHARGE TIME in seconds.
CapCtlGAPC
Discharging
SPS
Capacitor bank is discharging.
CAP 1 DISCHARGING operand.
CapCtlGAPC
DistDet
SPS
Sensitive current disturbance detector.
For PwrSwgRPSB1, power swing element detected disturbance other than power
swing.
The 50DD SV operand, which becomes On when the 87L disturbance detector has
operated.
The POWER SWING 50DD operand.
LinDfPDIF, PwrSwgRPSB
Data object
name
CDC
Semantics
Used in logical nodes…