2-120
UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
7E65
Hi-Z Event Count Time
5 to 180
min
1
F001
15
"
7E66
Hi-Z OC Protection Coord Timeout
10 to 200
seconds 1
F001
15
"
7E67
Hi-Z Phase OC Min Pickup
0.01 to 10
pu
0.01
F001
150
"
7E68
Hi-Z Neutral OC Min Pickup
0.01 to 10
pu
0.01
F001
100
"
7E69
Hi-Z Phase Rate of Change
1 to 999
A/2cycle 1
F001
150
"
7E6A
Hi-Z Neutral Rate of Change
1 to 999
A/2cycle 1
F001
150
"
7E6B
Hi-Z Loss of Load Threshold
5 to 100
%
1
F001
15
"
7E6C
Hi-Z Three-Phase Event Threshold
1 to 1000
A
1
F001
25
"
7E6D
Hi-Z Voltage Supv Threshold
0 to 100
%
1
F001
5
"
7E6E
Hi-Z Voltage Supv Delay
0 to 3000
cycles
2
F001
60
"
7E6F
Hi-Z Even Harmonic Restraint
0 to 100
%
1
F001
20
"
7E70
Hi-Z Target
0 to 2
---
1
F109
0 (Self-reset)
"
7E71
Hi-Z Events
0 to 1
---
1
F102
0 (Disabled)
"
7E72
Hi-Z Arcing Reset Time
0 to 6000
seconds 0.1
F001
0
Field Current (Read/Write Grouped Setting)
G60
7E74
Field Current Function
0 to 1
---
1
F102
0 (Disabled)
"
7E75
Field Current Origin
0 to 48
---
1
F151
0 (NONE)
"
7E76
Field Current Over Current (OC) Pickup
0.05 to 1
pu
0.01
F001
80
"
7E77
Field Current Over Current (OC) Delay
0 to 600
seconds 0.01
F001
100
"
7E78
Field Current Under Current (UC) Pickup
0.05 to 1
pu
0.01
F001
20
"
7E79
Field Current Under Current (UC) Delay
0 to 600
seconds 0.01
F001
100
"
7E7A
Field Current Block
0 to 4294967295
---
1
F300
0
"
7E7C
Field Current Target
0 to 2
---
1
F109
0 (Self-reset)
"
7E7D
Field Current Events
0 to 1
---
1
F102
0 (Disabled)
Field Ground (Read/Write Grouped Setting)
G60
7E7E
Field Ground Function
0 to 1
---
1
F102
0 (Disabled)
"
7E7F
Field Ground Injection Frequency
0.1 to 3
Hz
0.01
F001
100
"
7E80
Field Ground Injection Connection Type
0 to 1
---
1
F613
0 (Single
Point)
"
7E81
Field Ground STG1 Pickup
1 to 500
kOhm
1
F001
20
"
7E82
Field Ground STG1 Delay
0.1 to 600
seconds 0.1
F001
100
"
7E83
Field Ground STG2 Pickup
1 to 500
kOhm
1
F001
5
"
7E84
Field Ground STG2 Delay
0.1 to 600
seconds 0.1
F001
30
"
7E85
Field Ground UC Pickup
0.05 to 100
mA
0.01
F001
100
"
7E86
Field Ground UC Delay
0.1 to 600
seconds 0.01
F001
100
"
7E87
Field Ground Block
0 to 4294967295
---
1
F300
0
"
7E89
Field Ground Target
0 to 2
---
1
F109
0 (Self-reset)
"
7E8A
Field Ground Events
0 to 1
---
1
F102
0 (Disabled)
Distance (Read/Write Grouped Setting)
D30, D60, G60,
L60, L90, T60
7E8C
Distance Signal Source
0 to 5
---
1
F167
0 (SRC 1)
"
7E8D
Memory Duration
5 to 25
cycles
1
F001
10
"
7E8E
Force Self-Polarization
0 to 4294967295
---
1
F300
0
"
7E90
Force Memory Polarization
0 to 4294967295
---
1
F300
0
D30, D60, G60,
L90, T60
7E92
Fast Distance
0 to 1
---
1
F102
1 (Enabled)
D30, D60, G60,
L60, L90, T60
7E93
Ph Dist Ph Select Supv
0 to 1
---
1
F102
1 (Enabled)
Products
Address Register name
Range
Units
Step
Format
Default