2-162
UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
B307
Wattmetric Ground Fault 1 Power Pickup
0.001 to 1.2
pu
0.001 F001
100
"
B308
Wattmetric Ground Fault 1 ECA
0 to 360
° Lag
1
F001
0
"
B309
Wattmetric Ground Fault 1 Power Pickup
Delay
0 to 600
s
0.01
F001
20
"
B30A
Wattmetric Ground Fault 1 Curve
0 to 5
---
1
F236
0 (Definite
Time)
"
B30B
Wattmetric Ground Fault 1 Multiplier
0.01 to 2
s
0.01
F001
100
"
B30C
Wattmetric Ground Fault 1 Block
0 to 4294967295
---
1
F300
0
"
B30E
Wattmetric Ground Fault 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
B30F
Wattmetric Ground Fault 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
B310
Wattmetric Ground Fault 1 Reference
Power
0.001 to 1.2
pu
0.001 F001
500
"
B311
Wattmetric Ground Fault 1 Reserved
0 to 1
---
1
F001
0
"
B312
...Repeated for Wattmetric Ground Fault 2
F35
B324
...Repeated for Wattmetric Ground Fault 3
"
B336
...Repeated for Wattmetric Ground Fault 4
Wattmetric Ground Fault Actual Values (Read Only) (2 or 4 Modules)
D30, D60, F35,
F60, L60, L90
B360
Wattmetric Ground Fault 1 Operating
Power
0 to 999999.999
W
0.001 F060
0
"
B362
...Repeated for Wattmetric Ground Fault 2
F35
B364
...Repeated for Wattmetric Ground Fault 3
"
B366
...Repeated for Wattmetric Ground Fault 4
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
All
B400
Number of Status Indications in GGIO1
8 to 128
---
8
F001
8
"
B402
IEC 61850 GGIO1 Indication FlexLogic
operands (128 items)
0 to 4294967295
---
1
F300
0
Contact Input Thresholds (Read/Write Setting)
All
B982
Contact Input x Threshold (48 items)
0 to 3
---
1
F128
2 (84 Vdc)
Virtual Inputs (Read/Write Setting) (64 Modules)
All
B9B2
Virtual Input 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
B9B3
Virtual Input 1 Name
---
---
---
F636
“Virt Ip 1“
"
B9BD
Virtual Input 1 Programmed Type
0 to 1
---
1
F127
0 (Latched)
"
B9BE
Virtual Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
B9BF
Reserved (3 items)
---
---
---
F001
0
"
B9C2
...Repeated for Virtual Input 2
"
B9D2
...Repeated for Virtual Input 3
"
B9E2
...Repeated for Virtual Input 4
"
B9F2
...Repeated for Virtual Input 5
"
BA02
...Repeated for Virtual Input 6
"
BA12
...Repeated for Virtual Input 7
"
BA22
...Repeated for Virtual Input 8
"
BA32
...Repeated for Virtual Input 9
"
BA42
...Repeated for Virtual Input 10
"
BA52
...Repeated for Virtual Input 11
"
BA62
...Repeated for Virtual Input 12
"
BA72
...Repeated for Virtual Input 13
"
BA82
...Repeated for Virtual Input 14
"
BA92
...Repeated for Virtual Input 15
Products
Address Register name
Range
Units
Step
Format
Default