CHAPTER 3: IEC 61850 COMMUNICATION
CONFIGURING THE UR USING SCL
UR FAMILY – COMMUNICATIONS GUIDE
3-23
3
UR devices and EnerVista UR Setup automatically detect whether an imported CID file uses the G3 or the E3-2.0 model. UR
devices do not generate CID files, they only make available a copy of the most recently received and accepted CID file. The
model used when EnerVista UR Setup generates a CID file is determined by the Configuration Type setting.
ICD files generated by UR devices and EnerVista UR Setup have factory default settings that do not have GOOSE
subscription configured, and so implement both the G2 and the E3-2.0 model. IID files generated by UR devices and
EnerVista UR Setup are constrained by the standard to have only one IED element, and so for IID files the G2 model and the
E3-2.0 model are equivalent, provided the E3-2.0 extensions are populated, which they are. Thus only CID files generated
by EnerVista UR Setup are sensitive to the Configuration Type setting.
3.2.1 Merge SCL file
The EnerVista UR Setup software includes a function to merge SCL files with UR settings. ICD, CID, IID, and SCD files are
accepted as input and output.
To merge an SCL file:
1.
In EnerVista, select the device in the Offline Window area.
2.
Select the
Offline > Merge SCL Files
menu item. The window opens.
Figure 3-12: Merge settings files
3.
Complete the fields.
Input file 1
— Select the source file to import. Valid file types are ICD, CID, IID, and SCD.
Input file 2
— Select a second source file to import. An example is when IP addresses or Private settings are to be
imported from another source file. Valid file types are ICD, CID, IID, and SCD.