CG81
22E4
RRTD 2 - RTD #8 Alarm
0
2
1
-
F115
0
22E5
RRTD 2 - RTD #8 Alarm Relays
0
7
1
-
F113
1
22E6
RRTD 2 - RTD #8 Alarm Level
1
200
1
°C
F1
130
22E7
Record RRTD 2 - RTD #8 Alarms as Events 0
1
1
-
F103
0
22E8
RRTD 2 - RTD #8 Trip
0
2
1
-
F115
0
22E9
Enable RRTD 2 - RTD #8 Trip Voting
0
13
1
-
F122
1
22EA
RRTD 2 - RTD #8 Trip Relays
0
7
1
-
F111
1
22EB
RRTD 2 - RTD #8 Trip Level
1
200
1
°C
F1
130
22EC
RRTD 2 - RTD #8 RTD Type
0
3
1
-
F120
0
22F0
First Character of RRTD 2 - RTD #8 Name 32
127
1
-
F1
’R’
↓
↓
22F3
8th Character of RRTD 2 - RTD #8 Name
32
127
1
-
F1
’ ’
...
Reserved
RRTD 2 – RTD #9
2300
RRTD 2 - RTD #9 Application
0
4
1
-
F121
0
2301
RRTD 2 - RTD #9 High Alarm
0
2
1
-
F115
0
2302
RRTD 2 - RTD #9 High Alarm Relays
0
7
1
-
F113
2
2303
RRTD 2 - RTD #9 High Alarm Level
1
200
1
°C
F1
130
2304
RRTD 2 - RTD #9 Alarm
0
2
1
-
F115
0
2305
RRTD 2 - RTD #9 Alarm Relays
0
7
1
-
F113
1
2306
RRTD 2 - RTD #9 Alarm Level
1
200
1
°C
F1
130
2307
Record RRTD 2 - RTD #9 Alarms as Events 0
1
1
-
F103
0
2308
RRTD 2 - RTD #9 Trip
0
2
1
-
F115
0
2309
Enable RRTD 2 - RTD #9 Trip Voting
0
13
1
-
F122
1
230A
RRTD 2 - RTD #9 Trip Relays
0
7
1
-
F111
1
230B
RRTD 2 - RTD #9 Trip Level
1
200
1
°C
F1
130
230C
RRTD 2 - RTD #9 RTD Type
0
3
1
-
F120
0
2310
First Character of RRTD 2 - RTD #9 Name 32
127
1
-
F1
’R’
↓
↓
2313
8th Character of RRTD 2 - RTD #9 Name
32
127
1
-
F1
" "
...
Reserved
RRTD 2 – RTD #10
2320
RRTD 2 - RTD #10 Application
0
4
1
-
F121
0
2321
RRTD 2 - RTD #10 High Alarm
0
2
1
-
F115
0
2322
RRTD 2 - RTD #10 High Alarm Relays
0
7
1
-
F113
2
2323
RRTD 2 - RTD #10 High Alarm Level
1
200
1
°C
F1
130
2324
RRTD 2 - RTD #10 Alarm
0
2
1
-
F115
0
2325
RRTD 2 - RTD #10 Alarm Relays
0
7
1
-
F113
1
2326
RRTD 2 - RTD #10 Alarm Level
1
200
1
°C
F1
130
2327
Record RRTD 2 - RTD #10 Alarms as
Events
0
1
1
-
F103
0
2328
RRTD 2 - RTD #10 Trip
0
2
1
-
F115
0
2329
Enable RRTD 2 - RTD#10 Trip Voting
0
13
1
-
F122
1
232A
RRTD 2 - RTD #10 Trip Relays
0
7
1
-
F111
1
232B
RRTD 2 - RTD #10 Trip Level
1
200
1
°C
F1
130
232C
RRTD 2 - RTD #10 RTD Type
0
3
1
-
F120
0
2330
First Character of RRTD 2 - RTD #10 Name 32
127
1
-
F1
’R’
↓
↓
2333
8th Character of RRTD 2 - RTD #10 Name 32
127
1
-
F1
" "
...
Reserved
RRTD 2 – RTD #11
2340
RRTD 2 - RTD #11 Application
0
4
1
-
F121
0
2341
RRTD 2 - RTD #11 High Alarm
0
2
1
-
F115
0
2342
RRTD 2 - RTD #11 High Alarm Relays
0
7
1
-
F113
2
2343
RRTD 2 - RTD #11 High Alarm Level
1
200
1
°C
F1
130
2344
RRTD 2 - RTD #11 Alarm
0
2
1
-
F115
0
2345
RRTD 2 - RTD #11 Alarm Relays
0
7
1
-
F113
1
2346
RRTD 2 - RTD #11 Alarm Level
1
200
1
°C
F1
130
2347
Record RRTD 2 - RTD #11 Alarms as
Events
0
1
1
-
F103
0
Table CG–10: MEMORY MAP (Sheet 36 of 57)
ADDR
(hex)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT