CG48
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP
CGCOMMUNICATIONS GUIDE
LAST TRIP DATA
0220
Cause of Last Trip
0
276
1
-
F134
0
0221
Last Trip Time (2 words)
N/A
N/A
N/A
N/A
F19
-
0223
Last Trip Date (2 words)
N/A
N/A
N/A
N/A
F18
-
0225
Last Trip Motor Speed
0
2
1
N/A
F186
-
0226
Phase A Pre-Trip Current
0
65535
1
A
F1
0
0228
Phase B Pre-Trip Current
0
65535
1
A
F1
0
022A
Phase C Pre-Trip Current
0
65535
1
A
F1
0
022C
Motor Load Pre - Trip
0
2000
1
FLA
F3
0
022D
Current Unbalance Pre - Trip
0
100
1
%
F1
0
022E
Ground Current Pre - Trip
0
50000
1
A
F2
0
...
Reserved
-
-
-
-
-
-
0233
Hottest Stator RTD Owner During Trip
0
5
1
N/A
F165
0
0234
Hottest Stator RTD During Trip
0
12
1
-
F1
0
0235
Pre-Trip Temperature of Hottest Stator
RTD
-40
200
1
°C
F4
0
0236
Pre-Trip Voltage Vab
0
65000
1
V
F1
0
0237
Pre-Trip Voltage Vbc
0
65000
1
V
F1
0
0238
Pre-Trip Voltage Vca
0
65000
1
V
F1
0
0239
Pre-Trip Voltage Van
0
65000
1
V
F1
0
023A
Pre-Trip Voltage Vbn
0
65000
1
V
F1
0
023B
Pre-Trip Voltage Vcn
0
65000
1
V
F1
0
023C
Pre-Trip System Frequency
0
12000
1
Hz
F3
0
023D
Pre-Trip Real Power
-32000
32000
1
kW
F4
0
023E
Pre-Trip Reactive Power
-32000
32000
1
kvar
F4
0
023F
Pre-Trip Apparent Power
0
50000
1
kVA
F1
0
0240
Pre-Trip Power Factor
-99
100
1
-
F21
0
...
Reserved
-
-
-
-
-
-
ALARM STATUS
0260
General Spare Switch Alarm Status
or
Starter Monitor Alarm/Trip Status
0
4
1
-
F123
0
0261
General Emergency Restart Switch Alarm
Status
0
4
1
-
F123
0
0262
General Differential Switch Alarm Status
0
4
1
-
F123
0
0263
General Speed Switch Alarm Status
0
4
1
-
F123
0
0264
General Reset Switch Alarm Status
0
4
1
-
F123
0
...
Reserved
0267
Thermal Capacity Alarm
0
4
1
-
F123
0
0268
Overload Alarm Status
0
4
1
-
F123
0
0269
Mechanical Jam Alarm Status
0
4
1
-
F123
0
026A
Undercurrent Alarm Status
0
4
1
-
F123
0
026B
Current Unbalance Alarm Status
0
4
1
-
F123
0
026C
Ground Fault Alarm Status
0
4
1
-
F123
0
...
Reserved
026F
Undervoltage Alarm Status
0
4
1
-
F123
0
0270
Overvoltage Alarm Status
0
4
1
-
F123
0
0271
Overfrequency Alarm Status
0
4
1
-
F123
0
0272
Underfrequency Alarm Status
0
4
1
-
F123
0
...
Reserved
0275
Lead Power Factor Alarm Status
0
4
1
-
F123
0
0276
Lag Power Factor Alarm Status
0
4
1
-
F123
0
0277
Positive kvar Alarm Status
0
4
1
-
F123
0
0278
Negative kvar Alarm Status
0
4
1
-
F123
0
0279
Underpower Alarm Status
0
4
1
-
F123
0
027A
Reverse Power Alarm Status
0
4
1
-
F123
0
...
Reserved
027D
Local RTD #1 Alarm Status
0
4
1
-
F123
0
027E
Local RTD #2 Alarm Status
0
4
1
-
F123
0
027F
Local RTD #3 Alarm Status
0
4
1
-
F123
0
0280
Local RTD #4 Alarm Status
0
4
1
-
F123
0
Table CG–10: MEMORY MAP (Sheet 3 of 57)
ADDR
(hex)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT