CGCOMMUNICATIONS GUIDE
MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
CG67
LOCAL RTD #4
17F0
Local RTD #4 Application
0
4
1
-
F121
0
17F1
Local RTD #4 High Alarm
0
2
1
-
F115
0
17F2
Local RTD #4 High Alarm Relays
0
7
1
-
F113
2
17F3
Local RTD #4 High Alarm Level
1
200
1
°C
F1
130
17F4
Local RTD #4 Alarm
0
2
1
-
F115
0
17F5
Local RTD #4 Alarm Relays
0
7
1
-
F113
1
17F6
Local RTD #4 Alarm Level
1
200
1
°C
F1
130
17F7
Enable RTD #4 Alarms as Events
0
1
1
-
F103
0
17F8
Local RTD #4 Trip
0
2
1
-
F115
0
17F9
Enable RTD #4 Trip Voting
0
13
1
-
F122
1
17FA
Local RTD #4 Trip Relays
0
7
1
-
F111
1
17FB
Local RTD #4 Trip Level
1
200
1
°C
F1
130
17FC
Local RTD #4 RTD Type
0
3
1
-
F120
0
1800
First Character of Local RTD #4 Name
32
127
1
-
F1
’R’
↓
↓
1803
8th Character of Local RTD #4 Name
32
127
1
-
F1
" "
...
Reserved
LOCAL RTD #5
1810
Local RTD #5 Application
0
4
1
-
F121
0
1811
Local RTD #5 High Alarm
0
2
1
-
F115
0
1812
Local RTD #5 High Alarm Relays
0
7
1
-
F113
1
1813
Local RTD #5 High Alarm Level
1
250
1
°C / °F
F1
130
1814
Local RTD #5 Alarm
0
2
1
-
F115
0
1815
Local RTD #5 Alarm Relays
0
7
1
-
F113
1
1816
Local RTD #5 Alarm Level
1
200
1
°C
F1
130
1817
Record RTD #5 Alarms as Events
0
1
1
-
F103
0
1818
Local RTD #5 Trip
0
2
1
-
F115
0
1819
Enable RTD #5 Trip Voting
0
13
1
-
F122
1
181A
Local RTD #5 Trip Relays
0
7
1
-
F111
1
181B
Local RTD #5 Trip Level
1
200
1
°C
F1
130
181C
Local RTD #5 RTD Type
0
3
1
-
F120
0
1820
First Character of Local RTD #5 Name
32
127
1
-
F1
’R’
↓
↓
1823
8th Character of Local RTD #5 Name
32
127
1
-
F1
" "
...
Reserved
LOCAL RTD #6
1830
Local RTD #6 Application
0
4
1
-
F121
0
1831
Local RTD #6 High Alarm
0
2
1
-
F115
0
1832
Local RTD #6 High Alarm Relays
0
7
1
-
F113
2
1833
Local RTD #6 High Alarm Level
1
200
1
°C
F1
130
1834
Local RTD #6 Alarm
0
2
1
-
F115
0
1835
Local RTD #6 Alarm Relays
0
7
1
-
F113
1
1836
Local RTD #6 Alarm Level
1
200
1
°C
F1
130
1837
Record RTD #6 Alarms as Events
0
1
1
-
F103
0
1838
Local RTD #6 Trip
0
2
1
-
F115
0
1839
Enable RTD #6 Trip Voting
0
13
1
-
F122
1
183A
Local RTD #6 Trip Relays
0
7
1
-
F111
1
183B
Local RTD #6 Trip Level
1
200
1
°C
F1
130
183C
Local RTD #6 RTD Type
0
3
1
-
F120
0
1840
First Character of Local RTD #6 Name
32
127
1
-
F1
’R’
↓
↓
1843
8th Character of Local RTD #6 Name
32
127
1
-
F1
" "
...
Reserved
LOCAL RTD #7
1850
Local RTD #7 Application
0
4
1
-
F121
0
1851
Local RTD #7 High Alarm
0
2
1
-
F115
0
1852
Local RTD #7 High Alarm Relays
0
7
1
-
F113
2
1853
Local RTD #7 High Alarm Level
1
200
1
°C
F1
130
Table CG–10: MEMORY MAP (Sheet 22 of 57)
ADDR
(hex)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT