CG70
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP
CGCOMMUNICATIONS GUIDE
UNDERVOLTAGE
1B60
Undervoltage Active If Motor Stopped
0
1
1
-
F103
0
1B61
Undervoltage Alarm
0
2
1
-
F115
0
1B62
Assign Alarm Relays
0
7
1
-
F113
1
1B63
Undervoltage Alarm Pickup
50
99
1
×
Rated
F3
85
1B64
Starting Undervoltage Alarm Pickup
50
99
1
×
Rated
F3
85
1B65
Undervoltage Alarm Delay
0
2550
1
0.1s
F2
30
1B66
Undervoltage Alarm Events
0
1
1
-
F103
0
1B67
Undervoltage Trip
0
2
1
-
F115
0
1B68
Undervoltage Trip Relays
0
7
1
-
F111
1
1B69
Undervoltage Trip Pickup
50
99
1
×
Rated
F3
80
1B6A
Starting Undervoltage Trip Pickup
50
99
1
×
Rated
F3
80
1B6B
Undervoltage Trip Delay
0
2550
1
0.1s
F2
10
...
Reserved
OVERVOLTAGE
1B80
Overvoltage Alarm
0
2
1
-
F115
0
1B81
Overvoltage Alarm Relays
0
7
1
-
F113
1
1B82
Overvoltage Alarm Pickup
101
125
1
x Rated
F3
105
1B83
Overvoltage Alarm Delay
0
2550
1
s
F2
10
1B84
Overvoltage Alarm Events
0
1
1
-
F103
0
1B85
Overvoltage Trip
0
1
1
-
F103
0
1B86
Overvoltage Trip Relays
0
7
1
-
F111
1
1B87
Overvoltage Trip Pickup
101
125
1
x Rated
F3
110
1B88
Overvoltage Trip Delay
0
2550
1
s
F2
10
...
Reserved
PHASE REVERSAL
1BA0
Phase Reversal Trip
0
2
1
-
F115
0
1BA1
Assign Trip Relays
0
7
1
-
F111
1
...
Reserved
-
-
-
-
-
-
OVERFREQUENCY
1BB0
Block Overfrequency on Start
0
5000
1
s
F1
1
1BB1
Overfrequency Alarm
0
2
1
-
F115
0
1BB2
Assign Alarm Relays
0
7
1
-
F113
1
1BB3
Overfrequency Alarm Level
2000
7000
1
Hz
F3
6050
1BB4
Overfrequency Alarm Delay
0
2550
1
s
F2
10
1BB5
Overfrequency Alarm Events
0
1
1
-
F103
0
1BB6
Overfrequency Trip
0
1
1
-
F103
0
1BB7
Assign Trip Relays
0
7
1
-
F111
1
1BB8
Overfrequency Trip Level
2000
7000
1
Hz
F3
6050
1BB9
Overfrequency Trip Delay
0
2550
1
s
F2
10
...
Reserved
-
-
-
-
-
-
UNDERFREQUENCY
1BC0
Block Underfrequency on Start
0
5000
1
s
F1
1
1BC1
Underfrequency Alarm
0
2
1
-
F115
0
1BC2
Assign Alarm Relays
0
7
1
-
F113
1
1BC3
Underfrequency Alarm Level
2000
7000
1
Hz
F3
5950
1BC4
Underfrequency Alarm Delay
0
2550
1
s
F2
10
1BC5
Underfrequency Alarm Events
0
1
1
-
F103
0
1BC6
Underfrequency Trip
0
2
1
-
F115
0
1BC7
Assign Trip Relays
0
7
1
-
F111
1
1BC8
Underfrequency Trip Level
2000
7000
1
Hz
F3
5950
1BC9
Underfrequency Trip Delay
0
2550
1
s
F2
10
...
Reserved
LEAD POWER FACTOR
1BD0
Block Lead Power Factor From Start
0
5000
1
s
F1
1
1BD1
Lead Power Factor Alarm
0
2
1
-
F115
0
1BD2
Assign Lead Power Factor Alarm Relays
0
7
1
-
F113
1
1BD3
Lead Power Factor Alarm Level
5
99
1
-
F3
30
1BD4
Lead Power Factor Alarm Delay
1
2550
1
s
F2
10
Table CG–10: MEMORY MAP (Sheet 25 of 57)
ADDR
(hex)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT