CGCOMMUNICATIONS GUIDE
MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
CG61
11C9
Assign Start Control Relays
0
7
1
-
F113
2
...
Reserved
REDUCED VOLTAGE
11CF
Start Control Relay Timer
10
100
5
s
F2
10
11D0
Reduced Voltage Starting
0
1
1
-
F103
0
11D1
Assign Start Control Relays
0
7
1
-
F113
4
11D2
Transition On
0
2
1
-
F108
0
11D3
Incomplete Sequence Trip Relays
0
6
1
-
F111
0
11D4
Reduced Voltage Start Level
25
300
1
% FLA
F1
100
11D5
Reduced Voltage Start Timer
1
500
1
s
F1
200
AUTORESTART
11D6
Autorestart
0
1
1
-
F103
0
11D7
Total Restarts
0
65000
1
starts
F1
1
11D8
Restart Delay
0
20000
1
sec.
F1
60
11D9
Progressive Delay
0
20000
1
sec.
F1
0
11DA
Hold Delay
0
20000
1
sec.
F1
0
11DB
Bus Valid
0
1
1
-
F103
0
11DC
Bus Valid Level
15
100
1
%VT
F1
100
11DD
Reserved
-
-
-
-
-
-
11DE
Autorestart Attempt Events
0
1
1
-
F103
0
11DF
Autorestart Success Events
0
1
1
-
F103
0
11E0
Autorestart Aborted Events
0
1
1
-
F103
0
...
Reserved
UNDERVOLTAGE AUTORESTART
11F0
Enable UVR
0
1
1
-
F30
0 (Off)
11F1
UVR Pickup Level
50
100
1
x RATED
F3
65
11F2
UVR Assign Trip Relays
0
7
1
-
F111
0
11F3
UVR Trip Delay
0
2550
1
x 0.1s
F2
0
11F4
UVR Restoration Level
50
100
1
x RATED
F3
90
11F5
Immediate Restart Power Loss Time
0
500
100
ms
F1
0 (Off)
11F6
Delay1 Restart Power Loss Time
0
100
1
x 0.1s
F2
0 (Off)
11F7
Delay2 Restart Power Loss Time
0
3601
1
s
F1 (3601=
Unlimited)
0 (Off)
11F8
Delay1 Restart Time Delay
0
12000
2
x 0.1s
F2
20
11F9
Delay2 Restart Time Delay
0
12000
2
x 0.1s
F2
100
11FA
UVR Setup Time
0
12000
1
x 0.1s
F2
100
DIGITAL COUNTER
12E6
First Character of Counter Name
32
127
1
-
F1
“G”
12F2
First Character of Counter Unit Name
32
127
1
-
F1
‘U’
12F8
Counter Type
0
1
1
-
F114
0
12F9
Digital Counter Alarm
0
2
1
-
F115
0
12FA
Assign Alarm Relays
0
6
1
-
F113
0
12FB
Counter Alarm Level
0
65535
1
-
F1
100
12FD
Reserved
-
-
-
-
-
-
12FE
Record Alarms as Events
0
1
1
-
F103
0
EMERGENCY
1330
1st & 2nd Character of Emergency Switch
Name
32
127
1
-
F22
’G’
1340
General Emergency Switch Type
0
1
1
-
F116
0
1341
General Emergency Switch Block Input
From Start
0
5000
1
s
F1
0
1342
General Emergency Switch Alarm
0
2
1
-
F115
0
1343
General Emergency Switch Alarm Relays
0
6
1
-
F113
0
1344
General Emergency Switch Alarm Delay
1
50000
1
100ms
F2
50
1345
General Emergency Switch Alarm Events
0
1
1
-
F103
0
1346
General Emergency Switch Trip
0
2
1
-
F115
0
1347
General Emergency Switch Trip Relays
0
6
1
-
F111
0
1348
General Emergency Switch Trip Delay
1
50000
1
100ms
F2
50
1349
Emergency Switch Assignable Function
0
7
1
-
F110
0
...
Reserved
Table CG–10: MEMORY MAP (Sheet 16 of 57)
ADDR
(hex)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT