background image

GE Multilin

215 Anderson Avenue, Markham, Ontario, Canada  L6E 1B3

Tel: (905) 294-6222, 1-800-547-8629 (North America)
Fax: (905) 201-2098

Internet: 

http://www.GEmultilin.com

369 Motor Management Relay
Communications Guide

369 Revision: 3.2x

Manual P/N: 1601-9046-A1 (GEK-113493)

Copyright © 2008 GE Multilin

GE Consumer & Industrial

Multilin

*1601-9046-A1*

GE Multilin's Quality Management 

System is registered to 

ISO9001:2000
QMI # 005094

UL # A3775

Summary of Contents for 369

Page 1: ...ax 905 201 2098 Internet http www GEmultilin com 369 Motor Management Relay Communications Guide 369 Revision 3 2x Manual P N 1601 9046 A1 GEK 113493 Copyright 2008 GE Multilin GE Consumer Industrial Multilin 1601 9046 A1 GE Multilin s Quality Management System is registered to ISO9001 2000 QMI 005094 UL A3775 ...

Page 2: ... the property of GE Multilin Inc This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin The content of this manual is for informational use only and is subject to change without notice Part numbers contained in this manual are subject to change without notice and should therefore be verified by GE Multilin before ordering Part...

Page 3: ...TA 18 369 RELAY PROFIBUS DIAGNOSTICS 19 369 RELAY PROFIBUS DPV1 ACYCLICAL COMMUNICATION 19 369 RELAY PROFIBUS DPV1 LOSS OF COMMUNICATION TRIP 20 DEVICENET PROTOCOL 20 DEVICENET COMMUNICATIONS 20 POLL DATA 21 CHANGE OF STATE COS 23 IDENTITY OBJECT CLASS CODE 01H 23 MESSAGE ROUTER CLASS CODE 02H 24 DEVICENET OBJECT CLASS CODE 03H 24 ASSEMBLY OBJECT CLASS CODE 04H 25 DEVICENET CONNECTION OBJECT CLASS...

Page 4: ...AY INSTRUCTION MANUAL TABLE OF CONTENTS MEMORY MAP 43 MEMORY MAP INFORMATION 43 USER DEFINABLE MEMORY MAP AREA 43 EVENT RECORDER 44 WAVEFORM CAPTURE 44 MOTOR START DATA LOGGER 44 DATA LOGGER 45 MODBUS MEMORY MAP 46 FORMAT CODES 103 ...

Page 5: ...nating network installed at each end of the link i e at the master end and at the slave farthest from the master The terminating network should consist of a 120 ohm resistor in series with a 1 nF ceramic capacitor when used with Belden 9841 RS485 wire The value of the terminating resistors should be equal to the characteristic impedance of the line This is approximately 120 ohms for standard 22 AW...

Page 6: ...and IEC 61784 Acyclic read write between a Master Class1 Class2 and the 369 slave according to the DPV1 extensions of IEC 61158 Output Data 2 bytes cyclical Sections 3 1 to 3 6 of this manual pertain to the Profibus DPV1 option 1 3 DeviceNet Communications The 369 Motor Management Relay supports the optional DeviceNet protocol as slave that can be read by a DeviceNet master The device can be added...

Page 7: ...s document This description contains information to the location of Setting registers for configuring the 369 for a LAN connection and the physical connection of the 369 Information pertaining to the application of an IED over Ethernet is beyond the scope of this manual and users should consult their Network Administrators for configuration details Note The implementation of this option is for the...

Page 8: ...in to the Profibus DPV1 option 2 2 369 Relay Profibus DP Parameterization The 369 Motor Management Relay supports mandatory parametrization The relay keeps its user parameter data setpoints in a non volatile memory and does not need device related parametrization during startup of the DP master The EnerVista 369 Setup software is the best tool for user parametrization of the 369 device 2 3 369 Rel...

Page 9: ...configuration are contained in 369_090C gs which is used by a network configuration program The 369 Motor Management Relay as a DP slave transfers fast process data to the DP master according to master slave principle The 369 Motor Management Relay is a modular device supporting up to 8 input modules During the configuration session all modules have to be selected in order to get the entire area o...

Page 10: ...F131 0 22 DiffSwitch Status 2 0 0000 1 0001 1 F131 0 24 EmergencySwitch status 2 0 0000 1 0001 1 F131 0 26 ResetSwitch Status 2 0 0000 1 0001 1 F131 0 28 TripRelayStatus 2 0 0000 1 0001 1 N A F150 2 30 AlarmRelayStatus 2 0 0000 1 0001 1 N A F150 2 32 Aux1RelayStatus 2 0 0000 1 0001 1 N A F150 2 34 Aux2RelayStatus 2 0 0000 1 0001 1 N A F150 2 36 Ia 2 0 0000 65535 FFFF 1 A F1 0 38 Ib 2 0 0000 65535 ...

Page 11: ... FFD8 200 00C8 1 C F4 42 96 LocalRtd3 2 40 FFD8 200 00C8 1 C F4 42 98 LocalRtd4 2 40 FFD8 200 00C8 1 C F4 42 100 LocalRtd5 2 40 FFD8 200 00C8 1 C F4 42 102 LocalRtd6 2 40 FFD8 200 00C8 1 C F4 42 104 LocalRtd7 2 40 FFD8 200 00C8 1 C F4 42 106 LocalRtd8 2 40 FFD8 200 00C8 1 C F4 42 108 LocalRtd9 2 40 FFD8 200 00C8 1 C F4 42 110 LocalRtd10 2 40 FFD8 200 00C8 1 C F4 42 112 LocalRtd11 2 40 FFD8 200 00C...

Page 12: ...62 NumberOfStarts 2 0 0000 50000 C350 1 F1 0 164 NumberOfRestarts 2 0 0000 50000 C350 1 F1 0 166 DigitalCounter 2 0 0000 65535 FFFF 1 F1 0 168 MotorRunningHours 2 0 0000 65535 FFFF 1 hr F1 0 170 RelayOperatingHours 2 0 0000 65535 FFFF 1 hr F1 0 172 Last trip Cause 2 0 0000 169 00A9 1 F134 0 174 Last trip Date 4 N A N A N A N A N A N A F18 N A 178 Last trip Time 4 N A N A N A N A N A N A F19 N A 18...

Page 13: ...0000 65000 FDE8 1 V F1 0 206 Last pre trip Vbn 2 0 0000 65000 FDE8 1 V F1 0 208 Last pre trip Vcn 2 0 0000 65000 FDE8 1 V F1 0 210 Last pre trip Frequency 2 0 0000 12000 2EE0 1 Hz F3 0 212 Last pre trip KiloWatts 2 32000 8300 32000 7D00 1 kW F4 0 214 Last pre trip KiloVAR 2 32000 8300 32000 7D00 1 kvar F4 0 216 Last pre trip KiloVA 2 0 0000 50000 C350 1 kVA F1 0 218 Last pre trip PowerFactor 2 99 ...

Page 14: ...roundFaultTrip 14 9 GroundFaultBackupTrip 15 9 Reserved 16 10 AccelerationTimerTrip 17 10 Rtd1Trip 18 10 Rtd2Trip 19 10 Rtd3Trip 20 10 Rtd4Trip 21 10 Rtd5Trip 22 10 Rtd6Trip 23 10 Rtd7Trip 24 11 Rtd8Trip 25 11 Rtd9Trip 26 11 Rtd10Trip 27 11 Rtd11Trip 28 11 Rtd12Trip 29 11 UnderVoltageTrip 30 11 OverVoltageTrip 31 11 VoltagePhaseReversalTrip 32 12 UnderfrequencyTrip 33 12 OverfrequencyTrip 34 12 Le...

Page 15: ...anicalJamAlarm 50 14 UndercurrentAlarm 51 14 CurrentUnbalanceAlarm 52 14 GroundFaultAlarm 53 14 UndervoltageAlarm 54 14 OvervoltageAlarm 55 14 OverfrequencyAlarm 56 15 UnderfrequencyAlarm 57 15 LeadPowerFactorAlarm 58 15 LagPowerFactorAlarm 59 15 PositivekvarAlarm 60 15 NegativekvarAlarm 61 15 UnderpowerAlarm 62 15 ReversePowerAlarm 63 15 Rtd1Alarm 64 16 Rtd2Alarm 65 16 Rtd3Alarm 66 16 Rtd4Alarm 6...

Page 16: ...9 ShortRTDAlarm 89 19 TripCountersAlarm 90 19 StarterFailureAlarm 91 19 CurrentDemandAlarm 92 19 KWDemandAlarm 93 19 KVARDemandAlarm 94 19 KVADemandAlarm 95 19 DigitalCounterAlarm 96 20 OverloadLockoutBlock 97 20 StartInhibitBlock 98 20 StartsHourBlock 99 20 TimeBetweenStartsBlock 100 20 RestartBlock 101 20 Reserved 102 20 BackSpinBlock 103 20 LossofRemoteRTDCommunication 104 21 RemoteRTD1Rtd1Trip...

Page 17: ...oteRTD2Rtd8Trip 124 23 RemoteRTD2Rtd9Trip 125 23 RemoteRTD2Rtd10Trip 126 23 RemoteRTD2Rtd11Trip 127 23 RemoteRTD2Rtd12Trip 128 24 RemoteRTD3Rtd1Trip 129 24 RemoteRTD3Rtd2Trip 130 24 RemoteRTD3Rtd3Trip 131 24 RemoteRTD3Rtd4Trip 132 24 RemoteRTD3Rtd5Trip 133 24 RemoteRTD3Rtd6Trip 134 24 RemoteRTD3Rtd7Trip 135 24 RemoteRTD3Rtd8Trip 136 25 RemoteRTD3Rtd9Trip 137 25 RemoteRTD3Rtd10Trip 138 25 RemoteRTD...

Page 18: ...td8Alarm 160 28 RemoteRTD1Rtd9Alarm 161 28 RemoteRTD1Rtd10Alarm 162 28 RemoteRTD1Rtd11Alarm 163 28 RemoteRTD1Rtd12Alarm 164 28 RemoteRTD2Rtd1Alarm 165 28 RemoteRTD2Rtd2Alarm 166 28 RemoteRTD2Rtd3Alarm 167 28 RemoteRTD2Rtd4Alarm 168 29 RemoteRTD2Rtd5Alarm 169 29 RemoteRTD2Rtd6Alarm 170 29 RemoteRTD2Rtd7Alarm 171 29 RemoteRTD2Rtd8Alarm 172 29 RemoteRTD2Rtd9Alarm 173 29 RemoteRTD2Rtd10Alarm 174 29 Re...

Page 19: ...ofibus communications is offline and not communicating with a master then the Profibus Loss of Comms function if enabled will activate This feature can be programmed for Latched or Unlatched operation If programmed as Latched The Profibus Loss of Comms trip will remain latched until the communication with the Master is re established AND the latched trip is manually reset or remotely reset via Mod...

Page 20: ... for more information on these setpoints 3 Profibus DPV1 Communications 3 1 369 Relay Profibus DPV1 Parameterization The 369 Motor Management Relay supports mandatory parametrization as well as three bytes of user parameter data necessary for DPV1 devices The relay keeps its user parameter data setpoints in a non volatile memory and does not require device related parametrization during startup of...

Page 21: ...ing from offset zero Adding modules in your Master configuration increases the size of the total block of data that the Master will read making it easy to choose a total block size of data that matches the user s requirements 3 3 369 Relay Profibus Input Data There are two options for configuring what data is made available through Profibus Input Data based on the value of the PROFIBUS CYCLIC IN D...

Page 22: ...figuration Example 2 220 Bytes of Input Data 3 4 369 Relay Profibus Output Data The capability to force the output relays states has been implemented in cyclic output data As cyclic data is continuously written the 369 looks for a change in the value to execute the force relays command Refer to the 369 Instruction Manual chapter 5 for more information about the force output relays feature ...

Page 23: ...ostic information is available and the master initiates a diagnostics read the six slave mandatory bytes are read 3 6 369 Relay Profibus DPV1 Acyclical Communication The following items have been made available through Profibus DPV1 acyclical communication Data is addressed through the use of slot and index addressing Three parameters are required to read or write data from the 369 Relay using a P...

Page 24: ...rip 369 Instruction Manual chapter 5 369 Communications for information regarding the setpoints for this feature 4 DeviceNet Protocol 4 1 DeviceNet Communications The device profile is an extension of the Generic Device Profile 0x00 It is a group 2 only server The MAC ID and baud rate are programmable through relay front panel or the EnerVista 369 Setup software The polling function consumes one b...

Page 25: ...oup 2 or the User Defined poll data The control data format is as follows For execution of DeviceNet control commands one of the switch assignments should be set to DeviceNet Control and be closed The motor start command energizes the output relay set with the START CONTROL RELAY setpoint The motor stop command energizes the trip relay The fault reset command resets the latched trip and alarm cond...

Page 26: ...eviceNet Input Poll Data Group setpoint The list of parameters in each group is given below Table CG 8 Poll Data Group 1 Byte Description Length Units Format Default 1 Motor Status 1 F172 0 2 Digital Input Status 1 F172 0 3 Digital Output Status 1 F172 0 4 Flag Change State 1 F172 0 5 Thermal Capacity Used 1 UINT 0 6 low 7 high Time to Trip 2 seconds F20 1 Table CG 9 Poll Data Group 2 Byte Descrip...

Page 27: ...int When the DeviceNet master reads the Poll Input data 4 bytes of Input data will be read Note that the Explicit message data provided both via Class 04 Instance 64h Attribute 03 and Class A0h Instance 01 Attribute 01 will match the the Poll data configuration 4 3 Change of State COS The COS data is described under class 4 instance 66h attribute 3 The following data is provided 4 4 Identity Objec...

Page 28: ...ta types are defined as follows USINT Unsigned integer byte range 0 to 255 UINT Unsigned integer word range 0 to 65535 ATTRIBUTE ACCESS NAME DESCRIPTION DATA TYPE VALUE 01h Get Revision of Identity object UINT 1 ATTRIBUTE ACCESS NAME DESCRIPTION DATA TYPE VALUE 01h Get Vendor ID UINT 928 02h Get Device Type UINT 0 03h Get Product Code UINT 53 04h Get Revision Major Minor USINT 2 2 20 05h Get Statu...

Page 29: ...object UINT 2 02h Get Maximum instance number UINT 150 ATTRIBUTE ACCESS NAME DESCRIPTION DATA TYPE VALUE 03h Get Motor data1 1 The data available through this Class Instance Attribute will depend on which Poll Group is used see section 4 2 Poll Data bytes 7 see below ATTRIBUTE ACCESS NAME DESCRIPTION DATA TYPE VALUE 03h Get Flag change state byte see below DATA FORMATS FLAG CHANGE STATE BIT POSITI...

Page 30: ... 1 Motor stop 2 Fault reset 3 Motor start The corresponding command bit should be high for more than 500 ms to execute the command 4 8 DeviceNet Connection Object class code 05h The connection objects manage the characteristics of each communication connection There are two instances of the connection object in the device explicit connection 50 ms response and input output connection poll 10 ms re...

Page 31: ...te 0Dh Get Produced path length UINT 0x0000 0Eh Get Produced path BYTE 6 null 0Fh Get Consumed path length UINT 0x0000 10h Get Consumed path BYTE 6 null 11h Get Production inhibit timer UINT 0x0000 ATTRIBUTE ACCESS NAME DESCRIPTION DATA TYPE VALUE 01h Get State BYTE 0x03 02h Get Instance_type BYTE 0x01 03h Get Export class trigger BYTE 0x80 0x82 04h Get Produced connection ID UINT MAC ID 05h Get C...

Page 32: ...CRIPTION DATA TYPE VALUE 01h Get Revision of I O Data Input Mapping object UINT 1 ATTRIBUTE ACCESS NAME DESCRIPTION DATA TYPE DATA FORMAT 01h Get Motor data1 1 The data available through this Class Instance Attribute will depend on which Poll Group is used see section 4 2 Poll Data bytes 7 see below 02h Get Flag change state byte F175 03h Get Digital data bytes 4 see below 04h Get Thermal capacity...

Page 33: ...bject Class code B0h Services Parameter Data Input Mapping object Class code B0h Attributes 3 Reserved 4 Reserved 5 Reserved 6 Reserved 7 Reserved DATA FORMATS CONTROL BYTE BIT POSITION NAME VALUES CODE NAME DESCRIPTION 0x0E Get_Attribute_Single Returns the contents of the given attribute ATTRIBUTE ACCESS NAME DESCRIPTION DATA TYPE VALUE 01h Get Revision of Identity object UINT 1 ...

Page 34: ...ator RTD and temperature bytes 4 see below 16h Get Last pre trip line voltages bytes 6 see below 17h Get Last pre trip phase voltages bytes 6 see below 18h Get Last pre trip frequency bytes 2 see below 19h Get Last pre trip power bytes 8 see below 1Ah Get Trip diagnostic data bytes 6 see below 1Bh Get Alarm diagnostic data bytes 8 see below 1Ch Get Start block status data bytes 18 see below 1Dh Ge...

Page 35: ...ator RTD 16 bits UINT 3 4 low high Local hottest stator RTD temperature 16 bits F4 C 0Ch LOCAL RTD TEMP ERATURE 1 2 low high Local RTD 1 temperature 16 bits F4 C 3 4 low high Local RTD 2 temperature 16 bits F4 C 5 6 low high Local RTD 3 temperature 16 bits F4 C 7 8 low high Local RTD 4 temperature 16 bits F4 C 9 10 low high Local RTD 5 temperature 16 bits F4 C 11 12 low high Local RTD 6 temperatur...

Page 36: ...re trip hottest stator RTD 16 bits UINT 3 4 low high Local pre trip hottest stator RTD temperature 16 bits F4 C 16h LAST PRE TRIP LINE VOLTAGES 1 2 low high Last pre trip Vab 16 bits UINT volts 3 4 low high Last pre trip Vbc 16 bits UINT volts 5 6 low high Last pre trip Vca 16 bits UINT volts 17h LAST PRE TRIP PHASE VOLTAGES 1 2 low high Last pre trip Van 16 bits UINT volts 3 4 low high Last pre t...

Page 37: ...s F3 0 01 Hz 47 48 low high BSD state 16 bits F27 49 50 low high Backspin frequency 16 bits F3 0 01 Hz 51 52 low high Backspin prediction timer 16 bits F1 seconds 53 54 low high Power factor 16 bits F21 0 01 PF 55 56 low high Real power kW 16 bits F4 kW 57 58 low high Real power hp 16 bits UINT hp 59 60 low high Reactive power 16 bits F4 kvar 61 62 low high Apparent power 16 bits UINT kVA 63 64 lo...

Page 38: ...te 32 bits F18 141 to 144 low high Last trip time 32 bits F19 145 146 low high Last pre trip Ia 16 bits UINT A 147 148 low high Last pre trip Ib 16 bits UINT A 149 150 low high Last Pre trip Ic 16 bits UINT A 151 152 low high Last Pre trip Ig 16 bits F2 0 1 A 153 154 low high Last pre trip motor load 16 bits F3 0 01 FLA 155 156 low high Last pre trip unbalance 16 bits UINT 157 158 low high Last pr...

Page 39: ... F167 Network status unsigned 16 bit integer 0 Power off Not online 1 Online Connected 2 Link failure 3 Not defined F168 Connection status unsigned 16 bit integer 0 Nonexistent 1 Configuring 2 Not used 3 Established 4 Timed out 5 Deferred delete F170 DeviceNet baud rate unsigned 16 bit integer 0 125 kbps 1 250 kbps 2 500 kbps F172 Motor status Unsigned 8 bit integer Bit 0 Stopped Bit 1 Starting Bi...

Page 40: ...served Bit 7 Overload Trip Byte 2 Bit 0 Short Circuit Trip Bit 1 Short Circuit Backup Trip Bit 2 Mechanical Jam Trip Bit 3 Undercurrent Trip Bit 4 Current Unbalance Trip Bit 5 Ground Fault Trip Bit 6 Ground Fault Backup Trip Bit 7 Reserved Byte 3 Bit 0 Acceleration Timer Trip Bit 1 RTD 1 Trip Bit 2 RTD 2 Trip Bit 3 RTD 3 Trip Bit 4 RTD 4 Trip Bit 5 RTD 5 Trip Bit 6 RTD 6 Trip Bit 7 RTD 7 Trip Byte...

Page 41: ...rm Bit 3 Ground Fault Alarm Bit 4 Undervoltage Alarm Bit 5 Overvoltage Alarm Bit 6 Overfrequency Alarm Bit 7 Underfrequency Alarm Byte 3 Bit 0 Lead Power Factor Alarm Bit 1 Lag Power Factor Alarm Bit 2 Positive kvar Alarm Bit 3 Negative kvar Alarm Bit 4 Underpower Alarm Bit 5 Reverse Power Alarm Bit 6 RTD 1 Alarm Bit 7 RTD 2 Alarm F177 ctd Byte 4 Bit 0 RTD 3 Alarm Bit 1 RTD 4 Alarm Bit 2 RTD 5 Ala...

Page 42: ...00 2400 4800 9600 and 19200 baud Bit 2 RTD 9 High Alarm Bit 3 RTD 10 High Alarm Bit 4 RTD 11 High Alarm Bit 5 RTD 12 High Alarm Bit 6 Open RTD Sensor Alarm Bit 7 Short RTD Alarm Byte 7 Bit 0 Trip Counters Alarm Bit 1 Starter Failure Alarm Bit 2 Current Demand Alarm Bit 3 kW Demand Alarm Bit 4 kvar Demand Alarm Bit 5 kVA Demand Alarm Bit 6 Digital Counter Alarm Bit 7 Overload Lockout Block Byte 8 B...

Page 43: ...es of 1 to 127 The 369 implements some of these functions In a master request transmission the FUNCTION CODE tells the slave what action to perform In a slave response transmission if the FUNCTION CODE sent from the slave is the same as the FUNCTION CODE sent from the master indicating the slave performed the function as requested If the high order bit of the FUNCTION CODE sent from the slave is a...

Page 44: ...r A will contain the CRC value to be transmitted Note that this algorithm requires the characteristic polynomial to be reverse bit ordered The MSbit of the characteristic polynomial is dropped since it does not affect the value of the remainder The following symbols are used in the algorithm data transfer A 16 bit working register AL low order byte of A AH high order byte of A CRC 16 bit CRC 16 va...

Page 45: ...efer to the Modicon Modbus Protocol Reference guide 5 7 Error Responses When an 369 detects an error other than a CRC error a response will be sent to the master The MSbit of the FUNCTION CODE byte will be set to 1 i e the function code sent from the slave will be equal to the function code sent from the master plus 128 The following byte will be an exception code indicating the type of error that...

Page 46: ...nd data RTD maximums data motor statistics data Data Logger data and all energy data Command 20 Protection Function Blocking This command must be sent using Modbus function code 10h Store Multiple Setpoints This allows the 369 to accept the two required 16 bit values in one transmission The first data word is the command number 20 The 2nd data word contains the bitmask information for which functi...

Page 47: ...ing one Modbus packet It is often necessary for a master computer to continuously poll various values in each of the connected slave relays If these values are scattered throughout the memory map reading them would require numerous transmissions and would burden the communication link The User Definable Memory Map can be programmed to join any memory map address to one in the block of consecutive ...

Page 48: ...9 Relay relay to 0 6 4 Waveform Capture The 369 stores 16 cycles of A D samples each time a trip occurs in a trace buffer The Trace Memory Trigger is set up in S1 Preferences and determines how many pre trip and post trip cycles are stored The trace buffer is time and date stamped and may be correlated to a trip in the event record 7 waveforms are captured this way when a trip occurs These are the...

Page 49: ...s up to 16 channels of data parameters refer to Modbus format code F189 for the available parameters to be continually recorded at a defined rate of between 1 and 3600 seconds The 369 has allocated 32k bytes of RAM for Data Log storage All data will be lost upon loss of the 369 control power Internal to the 369 the memory structure is partitioned into 256 blocks containing 64 two byte registers Bl...

Page 50: ... the location of each of the potential 50 records Log 1 50 Number of Records This value provides the number of records that each of the 50 potential Logs contain Log 1 50 Start Stop Method This value is used to indicate the method by which each log was started and stopped If the bit value for the Start is zero it was started by a motor start event Refer to Modbus format code F191 for more informat...

Page 51: ...0 4 1 F31 0 0083 RRTD 2 Command Function Code 0 4 1 F31 0 0084 RRTD 3 Command Function Code 0 4 1 F31 0 0085 RRTD 4 Command Function Code 0 4 1 F31 0 Reserved REAL TIME CLOCK 00F0 Time 2 words valid time N A F19 00F2 Date 2 words valid date N A F18 Reserved PROFIBUS COMMUNICATIONS 00FC Profibus Loss of Comms Enable 0 2 1 F115 0 Off 00FD Profibus Loss of Comms Delay 25 1000 1 250 ms F2 25 00FE Assi...

Page 52: ...p Power Factor 99 100 1 F21 0 Reserved ALARM STATUS 0260 General Spare Switch Alarm Status or Starter Monitor Alarm Trip Status 0 4 1 F123 0 0261 General Emergency Restart Switch Alarm Status 0 4 1 F123 0 0262 General Differential Switch Alarm Status 0 4 1 F123 0 0263 General Speed Switch Alarm Status 0 4 1 F123 0 0264 General Reset Switch Alarm Status 0 4 1 F123 0 Reserved 0267 Thermal Capacity A...

Page 53: ...97 Reserved 0298 Trip Counter Alarm Status 0 4 1 F123 0 0299 Starter Failure Alarm 0 4 1 F123 0 029A Current Demand Alarm Status 0 4 1 F123 0 029B kW Demand Alarm Status 0 4 1 F123 0 029C kvar Demand Alarm Status 0 4 1 F123 0 029D kVA Demand Alarm Status 0 4 1 F123 0 029E Self Test Alarm 0 4 1 F123 0 START BLOCK STATUS 02C0 Overload Lockout Timer 0 9999 1 min F1 0 02C1 Start Timer 1 0 60 1 min F1 ...

Page 54: ...erature 40 200 1 C F4 40 0322 Local RTD 2 Temperature 40 200 1 C F4 40 0323 Local RTD 3 Temperature 40 200 1 C F4 40 0324 Local RTD 4 Temperature 40 200 1 C F4 40 0325 Local RTD 5 Temperature 40 200 1 C F4 40 0326 Local RTD 6 Temperature 40 200 1 C F4 40 0327 Local RTD 7 Temperature 40 200 1 C F4 40 0328 Local RTD 8 Temperature 40 200 1 C F4 40 0329 Local RTD 9 Temperature 40 200 1 C F4 40 032A Lo...

Page 55: ...Last Acceleration Time 1 2500 1 s F2 0 03C8 Average Motor Load Learned 0 2000 1 x FLA F3 0 03C9 Learned Unbalance k factor 0 29 1 F1 0 03CA Average Run Time After Start Days 0 65535 1 days F1 0 03CB Average Run Time After Start Minutes 1440 1 minutes F1 0 03CC Date of Record F19 03CE Number of Enhanced Learned Records 0 65535 1 F1 0 LOCAL RTD MAXIMUMS 03E0 Local RTD 1 Max Temperature 40 200 1 C F4...

Page 56: ... F1 0 0471 Number of Emergency Restarts 0 50000 1 F1 0 0472 Reserved 0473 Digital Counter 0 65535 1 F1 0 Reserved 04A0 Motor Running Hours 0 65535 1 hr F1 0 Reserved PHASORS 0500 Va Angle 0 359 1 degrees F1 0 0501 Vb Angle 0 359 1 degrees F1 0 0502 Vc Angle 0 359 1 degrees F1 0 0503 Ia Angle 0 359 1 degrees F1 0 0504 Ib Angle 0 359 1 degrees F1 0 0505 Ic Angle 0 359 1 degrees F1 0 Reserved REMOTE ...

Page 57: ...ture 40 200 1 C F4 40 062A RRTD 3 RTD 9 Temperature 40 200 1 C F4 40 062B RRTD 3 RTD 10 Temperature 40 200 1 C F4 40 062C RRTD 3 RTD 11 Temperature 40 200 1 C F4 40 062D RRTD 3 RTD 12 Temperature 40 200 1 C F4 40 Reserved RRTD 4 TEMPERATURES 0630 RRTD 4 RTD Hottest Stator Number 0 12 1 F1 0 0631 RRTD 4 RTD Hottest Stator Temperature 40 200 1 C F4 40 0632 RRTD 4 RTD 1 Temperature 40 200 1 C F4 40 0...

Page 58: ... RTD 2 Alarm Status 0 4 1 F123 0 0672 RRTD 2 RTD 3 Alarm Status 0 4 1 F123 0 0673 RRTD 2 RTD 4 Alarm Status 0 4 1 F123 0 0674 RRTD 2 RTD 5 Alarm Status 0 4 1 F123 0 0675 RRTD 2 RTD 6 Alarm Status 0 4 1 F123 0 0676 RRTD 2 RTD 7 Alarm Status 0 4 1 F123 0 0677 RRTD 2 RTD 8 Alarm Status 0 4 1 F123 0 0678 RRTD 2 RTD 9 Alarm Status 0 4 1 F123 0 0679 RRTD 2 RTD 10 Alarm Status 0 4 1 F123 0 067A RRTD 2 RT...

Page 59: ...F123 0 06AB RRTD 3 Digital Input 2 Alarm Status 0 4 1 F123 0 06AC RRTD 3 Digital Input 5 Alarm Status 0 4 1 F123 0 06AD RRTD 3 Digital Input 4 Alarm Status 0 4 1 F123 0 06AE RRTD 3 Digital Input 1 Alarm Status 0 4 1 F123 0 06AF RRTD 3 Digital Input 3 Alarm Status 0 4 1 F123 0 RRTD 4 ALARM STATUS 06B0 RRTD 4 RTD 1 Alarm Status 0 4 1 F123 0 06B1 RRTD 4 RTD 2 Alarm Status 0 4 1 F123 0 06B2 RRTD 4 RTD...

Page 60: ... 2 RTD 6 Max Temperature 40 200 1 C F4 40 0716 RRTD 2 RTD 7 Max Temperature 40 200 1 C F4 40 0717 RRTD 2 RTD 8 Max Temperature 40 200 1 C F4 40 0718 RRTD 2 RTD 9 Max Temperature 40 200 1 C F4 40 0719 RRTD 2 RTD 10 Max Temperature 40 200 1 C F4 40 071A RRTD 2 RTD 11 Max Temperature 40 200 1 C F4 40 071B RRTD 2 RTD 12 Max Temperature 40 200 1 C F4 40 Reserved RRTD 3 MAXIMUM TEMPERATURES 0720 RRTD 3 ...

Page 61: ... F1 0 Reserved RRTD 4 TRIP COUNTER 0830 RRTD 4 Stator RTD Trips 0 50000 1 F1 0 0831 RRTD 4 Bearing RTD Trips 0 50000 1 F1 0 0832 RRTD 4 Other RTD Trips 0 50000 1 F1 0 0833 RRTD 4 Ambient RTD Trips 0 50000 1 F1 0 0834 RRTD 4 Digital Input Trips 0 50000 1 F1 0 Reserved RRTD 1 DIGITAL INPUT STATUS 0840 Digital Input 3 0 1 1 F131 0 0841 Digital Input 4 0 1 1 F131 0 0842 Digital Input 6 0 1 1 F131 0 08...

Page 62: ...D 3 DIGITAL INPUT AND OUTPUT RELAY STATUS 08A4 RRTD3 Digital Input Output Relay Status N A N A N A N A F193 0 Reserved RRTD 4 OUTPUT RELAY STATUS 08B0 RRTD 4 Trip 0 2 1 N A F150 2 08B1 RRTD 4 Alarm 0 2 1 N A F150 2 08B2 RRTD 4 Aux 1 0 2 1 N A F150 2 08B3 RRTD 4 Aux 2 0 2 1 N A F150 2 RRTD 4 DIGITAL INPUT AND OUTPUT RELAY STATUS 08B4 RRTD4 Digital Input Output Relay Status N A N A N A N A F193 0 Re...

Page 63: ...ay Address Octet 4 0 255 1 F1 1 1028 DeviceNet MAC ID 0 63 1 F1 63 1029 DeviceNet Baud Rate 0 2 1 F170 0 Reserved REAL TIME CLOCK 1030 Date 2 words valid date N A F18 1034 Time 2 words valid time N A F19 Reserved DEFAULT MESSAGES 1041 Default to Current Metering 0 1 1 F103 0 1042 Default to Motor Load 0 1 1 F103 0 1043 Default to Delta Voltage Metering 0 1 1 F103 0 1044 Default to Power Factor 0 1...

Page 64: ...reset Motor Running Hours 0 65535 1 F1 0 113C Preset Autorestart Start Attempts 0 50000 1 F1 0 Reserved 1140 Clear Motor Data 0 1 1 F103 0 1141 Reserved 1142 Clear All Data 0 1 1 F103 0 1143 RRTD 1 Preset Digital Counter 0 65535 1 F1 0 1144 RRTD 2 Preset Digital Counter 0 65535 1 F1 0 1145 RRTD 3 Preset Digital Counter 0 65535 1 F1 0 1146 RRTD 4 Preset Digital Counter 0 65535 1 F1 0 1147 Clear Ene...

Page 65: ...100 ms F1 0 Off 11F6 Delay1 Restart Power Loss Time 0 100 1 x 0 1s F2 0 Off 11F7 Delay2 Restart Power Loss Time 0 3601 1 s F1 3601 Unlimited 0 Off 11F8 Delay1 Restart Time Delay 0 12000 2 x 0 1s F2 20 11F9 Delay2 Restart Time Delay 0 12000 2 x 0 1s F2 100 11FA UVR Setup Time 0 12000 1 x 0 1s F2 100 DIGITAL COUNTER 12E6 First Character of Counter Name 32 127 1 F1 G 12F2 First Character of Counter U...

Page 66: ...8 General Speed Switch Trip Delay 1 50000 1 100ms F2 50 13B9 Speed Switch Assignable Function 0 7 1 F158 0 13BA Speed Switch Delay 5 1000 5 100ms F2 20 13BB Assign Speed Switch Trip Relays 0 7 1 F111 1 Reserved RESET 13D0 1st 2nd Character of Reset Switch Name 32 127 1 F22 G 13E0 General Reset Switch Type 0 1 1 F116 0 13E1 General Reset Switch Block Input From Start 0 5000 1 s F1 0 13E2 General Re...

Page 67: ...100 ms F2 5 Reserved PROTECTION FUNCTION BLOCKING 1520 Log Blocking Events 0 1 1 N A F30 0 1521 Block Undercurrent Underpower 0 1 1 N A F30 0 1522 Block Current Unbalance 0 1 1 N A F30 0 1523 Block Incomplete Sequence 0 1 1 N A F30 0 1524 Block Thermal Model 0 1 1 N A F30 0 1525 Block Short Circuit and Backup 0 1 1 N A F30 0 1526 Block Overload Alarm 0 1 1 N A F30 0 1527 Block Ground Fault 0 1 1 N...

Page 68: ...s F1 12 15DC Time to Trip at 6 00 x FLA 0 65534 1 s F1 10 15DE Time to Trip at 6 50 x FLA 0 65534 1 s F1 9 15E0 Time to Trip at 7 00 x FLA 0 65534 1 s F1 7 15E2 Time to Trip at 7 50 x FLA 0 65534 1 s F1 6 15E4 Time to Trip at 8 00 x FLA 0 65534 1 s F1 6 15E6 Time to Trip at 10 0 x FLA 0 65534 1 s F1 6 15E8 Time to Trip at 15 0 x FLA 0 65534 1 s F1 6 15EA Time to Trip at 20 0 x FLA 0 65534 1 s F1 6...

Page 69: ...lt Alarm 0 2 1 F115 0 16A2 Assign Ground Fault Alarm Relays 0 7 1 F113 1 16A3 Ground Fault Alarm Pickup 10 100 1 0 1 CT F3 10 16A4 GF Alarm Pickup for GE Multilin 50 0 025 CT 25 2500 1 Amps F3 25 16A5 Ground Fault Alarm Delay 0 255 00 0 01 s F3 0 16A6 Ground Fault Alarm Events 0 1 1 F103 0 16A7 Ground Fault Trip 0 2 1 F 115 0 16A8 Assign Ground Fault Trip Relays 0 7 1 F 111 1 16A9 Ground Fault Tri...

Page 70: ... C F1 130 17B4 Local RTD 2 Alarm 0 2 1 F115 0 17B5 Local RTD 2 Alarm Relays 0 7 1 F113 1 17B6 Local RTD 2 Alarm Level 1 200 1 C F1 130 17B7 Record RTD 2 Alarms as Events 0 1 1 F103 0 17B8 Local RTD 2 Trip 0 2 1 F 115 0 17B9 Enable RTD 2 Trip Voting 0 13 1 F122 1 17BA Local RTD 2 Trip Relays 0 7 1 F111 1 17BB Local RTD 2 Trip Level 1 200 1 C F1 130 17BC Local RTD 2 RTD Type 0 3 1 F120 0 17C0 First ...

Page 71: ...ts 0 1 1 F103 0 1818 Local RTD 5 Trip 0 2 1 F115 0 1819 Enable RTD 5 Trip Voting 0 13 1 F122 1 181A Local RTD 5 Trip Relays 0 7 1 F111 1 181B Local RTD 5 Trip Level 1 200 1 C F1 130 181C Local RTD 5 RTD Type 0 3 1 F120 0 1820 First Character of Local RTD 5 Name 32 127 1 F1 R 1823 8th Character of Local RTD 5 Name 32 127 1 F1 Reserved LOCAL RTD 6 1830 Local RTD 6 Application 0 4 1 F121 0 1831 Local...

Page 72: ... 3 1 F120 0 1880 First Character of Local RTD 8 Name 32 127 1 F1 R 1883 8th Character of Local RTD 8 Name 32 127 1 F1 1884 Reserved LOCAL RTD 9 1890 Local RTD 9 Application 0 4 1 F121 0 1891 Local RTD 9 High Alarm 0 2 1 F115 0 1892 Local RTD 9 High Alarm Relays 0 7 1 F113 2 1893 Local RTD 9 High Alarm Level 1 200 1 C F1 130 1894 Local RTD 9 Alarm 0 2 1 F115 0 1895 Local RTD 9 Alarm Relays 0 7 1 F1...

Page 73: ... RTD 12 18F0 Local RTD 12 Application 0 4 1 F121 0 18F1 Local RTD 12 High Alarm 0 2 1 F115 0 18F2 Local RTD 12 High Alarm Relays 0 7 1 F113 2 18F3 Local RTD 12 High Alarm Level 1 200 1 C F1 130 18F4 Local RTD 12 Alarm 0 2 1 F115 0 18F5 Local RTD 12 Alarm Relays 0 7 1 F113 1 18F6 Local RTD 12 Alarm Level 1 200 1 C F1 130 18F7 Record RTD 12 Alarms as Events 0 1 1 F103 0 18F8 Local RTD 12 Trip 0 2 1 ...

Page 74: ... Trip Relays 0 7 1 F111 1 Reserved OVERFREQUENCY 1BB0 Block Overfrequency on Start 0 5000 1 s F1 1 1BB1 Overfrequency Alarm 0 2 1 F115 0 1BB2 Assign Alarm Relays 0 7 1 F113 1 1BB3 Overfrequency Alarm Level 2000 7000 1 Hz F3 6050 1BB4 Overfrequency Alarm Delay 0 2550 1 s F2 10 1BB5 Overfrequency Alarm Events 0 1 1 F103 0 1BB6 Overfrequency Trip 0 1 1 F103 0 1BB7 Assign Trip Relays 0 7 1 F111 1 1BB8...

Page 75: ...1 F103 0 1BF7 Assign Trip Relays 0 7 1 F111 1 1BF8 Positive kvar Trip Level 1 25000 1 kvar F1 25 1BF9 Positive kvar Trip Delay 1 2550 1 s F2 10 Reserved NEGATIVE REACTIVE POWER 1C00 Block Negative kvar Element from Start 0 5000 1 s F1 1 1C01 Negative kvar Alarm 0 2 1 F115 0 1C02 Assign Alarm Relays 0 7 1 F113 1 1C03 Negative kvar Alarm Level 1 25000 1 kvar F1 10 1C04 Negative kvar Alarm Delay 1 25...

Page 76: ...2 Assign Alarm Relays 0 7 1 F113 1 1CD3 Current Demand Alarm Limit 0 65000 1 A F1 100 1CD5 Current Demand Alarm Events 0 1 1 F103 0 Reserved KW DEMAND 1CE0 kW Demand Period 5 90 1 min F1 15 1CE1 kW Demand Alarm 0 2 1 F115 0 1CE2 Assign Alarm Relays 0 7 1 F113 1 1CE3 kW Demand Alarm Limit 1 50000 1 kW F1 100 1CE4 kW Demand Alarm Events 0 1 1 F103 0 Reserved KVAR DEMAND 1CF0 kvar Demand Period 5 90 ...

Page 77: ...d 2 Time to Trip at 2 50 x FLA 0 65534 1 s F1 67 1DCC Speed 2 Time to Trip at 2 75 x FLA 0 65534 1 s F1 53 1DCD Speed 2 Time to Trip at 3 00 x FLA 0 65534 1 s F1 44 1DCE Speed 2 Time to Trip at 3 25 x FLA 0 65534 1 s F1 37 1DCF Speed 2 Time to Trip at 3 50 x FLA 0 65534 1 s F1 31 1DD0 Speed 2 Time to Trip at 3 75 x FLA 0 65534 1 s F1 27 1DD1 Speed 2 Time to Trip at 4 00 x FLA 0 65534 1 s F1 23 1DD...

Page 78: ...annel 12 Log Assignment 0 102 1 F189 0 None 1E30 Channel 13 Log Assignment 0 102 1 F189 0 None 1E31 Channel 14 Log Assignment 0 102 1 F189 0 None 1E32 Channel 15 Log Assignment 0 102 1 F189 0 None 1E33 Channel 16 Log Assignment 0 102 1 F189 0 None Reserved TEST OUTPUT RELAYS 1F80 Force Trip Relay 0 2 1 F150 0 1F81 Force Trip Relay Duration 1 300 1 s F1 0 1F82 Force AUX1 Relay 0 2 1 F150 0 1F83 For...

Page 79: ...Trip Level 1 200 1 C F1 130 202C RRTD 1 RTD 2 RTD Type 0 3 1 F120 0 Reserved 2030 First Character of RRTD 1 RTD 2 Name 32 127 1 F1 R 2033 8th Character of RRTD 1 RTD 2 Name 32 127 1 F1 2034 Reserved RRTD 1 RTD 3 2040 RRTD 1 RTD 3 Application 0 4 1 F121 0 2041 RRTD 1 RTD 3 High Alarm 0 2 1 F115 0 2042 RRTD 1 RTD 3 High Alarm Relays 0 7 1 F113 2 2043 RRTD 1 RTD 3 High Alarm Level 1 200 1 C F1 130 20...

Page 80: ...erved RRTD 1 RTD 6 20A0 RRTD 1 RTD 6 Application 0 4 1 F121 0 20A1 RRTD 1 RTD 6 High Alarm 0 2 1 F115 0 20A2 RRTD 1 RTD 6 High Alarm Relays 0 7 1 F113 1 20A3 RRTD 1 RTD 6 High Alarm Level 1 200 1 C F1 130 20A4 RRTD 1 RTD 6 Alarm 0 2 1 F115 0 20A5 RRTD 1 RTD 6 Alarm Relays 0 7 1 F113 1 20A6 RRTD 1 RTD 6 Alarm Level 1 200 1 C F1 130 20A7 Record RRTD 1 RTD 6 Alarms as Events 0 1 1 F103 0 20A8 RRTD 1 ...

Page 81: ... 2104 RRTD 1 RTD 9 Alarm 0 2 1 F115 0 2105 RRTD 1 RTD 9 Alarm Relays 0 7 1 F113 1 2106 RRTD 1 RTD 9 Alarm Level 1 200 1 C F1 130 2107 Record RRTD 1 RTD 9 Alarms as Events 0 1 1 F103 0 2108 RRTD 1 RTD 9 Trip 0 2 1 F115 0 2109 Enable RRTD 1 RTD 9 Trip Voting 0 13 1 F122 1 210A RRTD 1 RTD 9 Trip Relays 0 7 1 F111 1 210B RRTD 1 RTD 9 Trip Level 1 200 1 C F1 130 210C RRTD 1 RTD 9 RTD Type 0 3 1 F120 0 ...

Page 82: ...ms as Events 0 1 1 F103 0 2168 RRTD 1 RTD 12 Trip 0 2 1 F115 0 2169 Enable RRTD 1 RTD 12 Trip Voting 0 13 1 F122 1 216A RRTD 1 RTD 12 Trip Relays 0 7 1 F111 1 216B RRTD 1 RTD 12 Trip Level 1 200 1 C F1 130 216C RRTD 1 RTD 12 RTD Type 0 3 1 F120 0 2170 First Character of RRTD 1 RTD 12 Name 32 127 1 F1 R 2173 8th Character of RRTD 1 RTD 12 Name 32 127 1 F1 Reserved RRTD 1 OPEN RTD ALARM 2180 RRTD A ...

Page 83: ...1 C F1 130 2244 RRTD 2 RTD 3 Alarm 0 2 1 F115 0 2245 RRTD 2 RTD 3 Alarm Relays 0 7 1 F113 1 2246 RRTD 2 RTD 3 Alarm Level 1 200 1 C F1 130 2247 Record RRTD 2 RTD 3 Alarms as Events 0 1 1 F103 0 2248 RRTD 2 RTD 3 Trip 0 2 1 F115 0 2249 Enable RRTD 2 RTD 3 Trip Voting 0 13 1 F122 1 224A RRTD 2 RTD 3 Trip Relays 0 7 1 F111 1 224B RRTD 2 RTD 3 Trip Level 1 200 1 C F1 130 224C RRTD 2 RTD 3 RTD Type 0 3...

Page 84: ... 0 1 1 F103 0 22A8 RRTD 2 RTD 6 Trip 0 2 1 F115 0 22A9 Enable RRTD 2 RTD 6 Trip Voting 0 13 1 F122 1 22AA RRTD 2 RTD 6 Trip Relays 0 7 1 F111 1 22AB RRTD 2 RTD 6 Trip Level 1 200 1 C F1 130 22AC RRTD 2 RTD 6 RTD Type 0 3 1 F120 0 22B0 First Character of RRTD 2 RTD 6 Name 32 127 1 F1 R 22B3 8th Character of RRTD 2 RTD 6 Name 32 127 1 F1 Reserved RRTD 2 RTD 7 22C0 RRTD 2 RTD 7 Application 0 4 1 F121...

Page 85: ...D 9 RTD Type 0 3 1 F120 0 2310 First Character of RRTD 2 RTD 9 Name 32 127 1 F1 R 2313 8th Character of RRTD 2 RTD 9 Name 32 127 1 F1 Reserved RRTD 2 RTD 10 2320 RRTD 2 RTD 10 Application 0 4 1 F121 0 2321 RRTD 2 RTD 10 High Alarm 0 2 1 F115 0 2322 RRTD 2 RTD 10 High Alarm Relays 0 7 1 F113 2 2323 RRTD 2 RTD 10 High Alarm Level 1 200 1 C F1 130 2324 RRTD 2 RTD 10 Alarm 0 2 1 F115 0 2325 RRTD 2 RTD...

Page 86: ...N RTD ALARM 2380 RRTD B Open RTD Alarm 0 2 1 F115 0 2381 RRTD B Assign Alarm Relays 0 7 1 F113 1 2382 RRTD B Open RTD Alarm Events 0 1 1 F103 0 RRTD 2 SHORT LOW TEMPERATURE RTD ALARM 2383 RRTD B Short Low Temp RTD Alarm 0 2 1 F115 0 2384 RRTD B Assign Alarm Relays 0 7 1 F113 1 2385 RRTD B Short Low Temp Alarm Events 0 1 1 F103 0 Reserved RRTD 3 RTD 1 2400 RRTD 3 RTD 1 Application 0 4 1 F121 0 2401...

Page 87: ...RTD Type 0 3 1 F120 0 2450 First Character of RRTD 3 RTD Name 32 127 1 F1 R 2453 8th Character of RRTD 3 RTD 3 Name 32 127 1 F1 Reserved RRTD 3 RTD 4 2460 RRTD 3 RTD 4 Application 0 4 1 F121 0 2461 RRTD 3 RTD 4 High Alarm 0 2 1 F115 0 2462 RRTD 3 RTD 4 High Alarm Relays 0 7 1 F113 2 2463 RRTD 3 RTD 4 High Alarm Level 1 200 1 C F1 130 2464 RRTD 3 RTD 4 Alarm 0 2 1 F115 0 2465 RRTD 3 RTD 4 Alarm Rel...

Page 88: ... F115 0 24C2 RRTD 3 RTD 7 High Alarm Relays 0 7 1 F113 2 24C3 RRTD 3 RTD 7 High Alarm Level 1 200 1 C F1 130 24C4 RRTD 3 RTD 7 Alarm 0 2 1 F115 0 24C5 RRTD 3 RTD 7 Alarm Relays 0 7 1 F113 1 24C6 RRTD 3 RTD 7 Alarm Level 1 200 1 C F1 130 24C7 Record RRTD 3 RTD 7 Alarms as Events 0 1 1 F103 0 24C8 RRTD 3 RTD 7 Trip 0 2 1 F115 0 24C9 Enable RRTD 3 RTD 7 Trip Voting 0 13 1 F122 1 24CA RRTD 3 RTD 7 Tri...

Page 89: ...RTD 10 Alarm Relays 0 7 1 F113 1 2526 RRTD 3 RTD 10 Alarm Level 1 200 1 C F1 130 2527 Record RRTD 3 RTD 10 Alarms as Events 0 1 1 F103 0 2528 RRTD 3 RTD 10 Trip 0 2 1 F115 0 2529 Enable RRTD 3 RTD 10 Trip Voting 0 13 1 F122 1 252A RRTD 3 RTD 10 Trip Relays 0 7 1 F111 1 252B RRTD 3 RTD 10 Trip Level 1 200 1 C F1 130 252C RRTD 3 RTD 10 RTD Type 0 3 1 F120 0 2530 First Character of RRTD 3 RTD 10 Name...

Page 90: ... 1 Application 0 4 1 F121 0 2601 RRTD 4 RTD 1 High Alarm 0 2 1 F115 0 2602 RRTD 4 RTD 1 High Alarm Relays 0 7 1 F113 2 2603 RRTD 4 RTD 1 High Alarm Level 1 200 1 C F1 130 2604 RRTD 4 RTD 1 Alarm 0 2 1 F115 0 2605 RRTD 4 RTD 1 Alarm Relays 0 7 1 F113 1 2606 RRTD 4 RTD 1 Alarm Level 1 200 1 C F1 130 2607 Record RRTD 4 RTD 1 Alarms as Events 0 1 1 F103 0 2608 RRTD 4 RTD 1 Trip 0 2 1 F115 0 2609 Enabl...

Page 91: ...RTD 4 Alarm 0 2 1 F115 0 2665 RRTD 4 RTD 4 Alarm Relays 0 7 1 F113 1 2666 RRTD 4 RTD 4 Alarm Level 1 200 1 C F1 130 2667 Record RRTD 4 RTD 4 Alarms as Events 0 1 1 F103 0 2668 RRTD 4 RTD 4 Trip 0 2 1 F115 0 2669 Enable RRTD 4 RTD 4 Trip Voting 0 13 1 F122 1 266A RRTD 4 RTD 4 Trip Relays 0 7 1 F111 1 266B RRTD 4 RTD 4 Trip Level 1 200 1 C F1 130 266C RRTD 4 RTD 4 RTD Type 0 3 1 F120 0 2670 First Ch...

Page 92: ... 0 1 1 F103 0 26C8 RRTD 4 RTD 7 Trip 0 2 1 F115 0 26C9 Enable RRTD 4 RTD 7 Trip Voting 0 13 1 F122 1 26CA RRTD 4 RTD 7 Trip Relays 0 7 1 F111 1 26CB RRTD 4 RTD 7 Trip Level 1 200 1 C F1 130 26CC RRTD 4 RTD 7 RTD Type 0 3 1 F120 0 26D0 First Character of RRTD 4 RTD 7 Name 32 127 1 F1 R 26D3 8th Character of RRTD 4 RTD 7 Name 32 127 1 F1 Reserved RRTD 4 RTD 8 26E0 RRTD 4 RTD 8 Application 0 4 1 F121...

Page 93: ...l 1 200 1 C F1 130 272C RRTD 4 RTD 10 RTD Type 0 3 1 F120 0 2730 First Character of RRTD 4 RTD 10 Name 32 127 1 F1 R 2733 8th Character of RRTD 4 RTD 10 Name 32 127 1 F1 Reserved RRTD 4 RTD 11 2740 RRTD 4 RTD 11 Application 0 4 1 F121 0 2741 RRTD 4 RTD 11 High Alarm 0 2 1 F115 0 2742 RRTD 4 RTD 11 High Alarm Relays 0 7 1 F113 2 2743 RRTD 4 RTD 11 High Alarm Level 1 200 1 C F1 130 2744 RRTD 4 RTD 1...

Page 94: ...ration 0 1 1 F161 1 27A6 Aux1 Relay Operation 0 1 1 F161 1 27A7 Aux2 Relay Operation 0 1 1 F161 0 Reserved RRTD 2 OUTPUT RELAY SETUP 27B0 Trip Relay Reset Mode 0 2 1 F117 0 27B1 Alarm Relay Reset Mode 0 2 1 F117 0 27B2 Aux 1 Relay Reset Mode 0 2 1 F117 0 27B3 Aux 2 Relay Reset Mode 0 2 1 F117 0 27B4 Trip Relay Operation 0 1 1 F161 0 27B5 Alarm Relay Operation 0 1 1 F161 1 27B6 Aux1 Relay Operation...

Page 95: ...200 2805 Enable Analog Output 2 0 1 1 F103 0 2806 Assign Analog Output 2 Output Range 0 2 1 F26 0 2807 Assign Analog Output 2 Parameter 12 24 1 F127 13 2808 Analog Output 2 Minimum 40 200 1 F4 40 2809 Analog Output 2 Maximum 40 200 1 F4 200 280A Enable Analog Output 3 0 1 1 F103 0 280B Assign Analog Output 3 Output Range 0 2 1 F26 0 280C Assign Analog Output 3 Parameter 12 24 1 F127 13 280D Analog...

Page 96: ...F26 0 2851 Assign Analog Output 4 Parameter 12 24 1 F127 13 2852 Analog Output 4 Minimum 40 200 1 F4 40 2853 Analog Output 4 Maximum 40 200 1 F4 200 2854 Reserved RRTD 1 DIGITAL INPUT 2 2860 1st 2nd Character of Digital Input 2 Name 32 127 1 F22 GE 2865 11th 12th Character of Digital Input 2 Name 32 127 1 F22 GE 2870 Digital Input 2 Type 0 1 1 F116 0 2871 Reserved 2872 Digital Input 2 Alarm 0 2 1 ...

Page 97: ...ital Input 1 Alarm Delay 1 50000 1 100ms F2 50 28D5 Digital Input 1 Alarm Events 0 1 1 F103 0 28D6 Digital Input 1 Trip 0 2 1 F115 0 28D7 Digital Input 1 Trip Relays 0 6 1 F111 0 28D8 Digital Input 1 Trip Delay 1 50000 1 100ms F2 50 28D9 Digital Input 1 Assignable Function 0 3 1 F163 0 Reserved RRTD 1 DIGITAL INPUT 6 28E0 1st 2nd Character of Digital Input 6 Name 32 127 1 F22 GE 28E5 11th 12th Cha...

Page 98: ... 1 F22 GE 2945 11th 12th Character of Digital Input 5 Name 32 127 1 F22 GE 2950 Digital Input 5 Type 0 1 1 F116 0 2951 Reserved 2952 Digital Input 5 Alarm 0 2 1 F115 0 2953 Digital Input 5 Alarm Relays 0 6 1 F113 0 2954 Digital Input 5 Alarm Delay 1 50000 1 100ms F2 50 2955 Digital Input 5 Alarm Events 0 1 1 F103 0 2956 Digital Input 5 Trip 0 2 1 F115 0 2957 Digital Input 5 Trip Relays 0 6 1 F111 ...

Page 99: ...Input 6 Trip Delay 1 50000 1 100ms F2 50 29B9 Digital Input 6 Assignable Function 0 3 1 F163 0 Reserved RRTD 2 DIGITAL INPUT 3 29C0 1st 2nd Character of Digital Input 3 Name 32 127 1 F22 GE 29C5 11th 12th Character of Digital Input 3 Name 32 127 1 F22 GE 29D0 Digital Input 3 Type 0 1 1 F116 0 29D1 Reserved 29D2 Digital Input 3 Alarm 0 2 1 F115 0 29D3 Digital Input 3 Alarm Relays 0 6 1 F113 0 29D4 ...

Page 100: ...ital Input 4 Alarm Relays 0 6 1 F113 0 2A34 Digital Input 4 Alarm Delay 1 50000 1 100ms F2 50 2A35 Digital Input 4 Alarm Events 0 1 1 F103 0 2A36 Digital Input 4 Trip 0 2 1 F115 0 2A37 Digital Input 4 Trip Relays 0 6 1 F111 0 2A38 Digital Input 4 Trip Delay 1 50000 1 100ms F2 50 2A39 Digital Input 4 Assignable Function 0 3 1 F163 0 Reserved RRTD 3 DIGITAL INPUT 1 2A40 1st 2nd Character of Digital ...

Page 101: ...L INPUT 2 2AA0 1st 2nd Character of Digital Input 2 Name 32 127 1 F22 GE 2AA5 11th 12th Character of Digital Input 2 Name 32 127 1 F22 GE 2AB0 Digital Input 2 Type 0 1 1 F116 0 2AB1 Reserved 2AB2 Digital Input 2 Alarm 0 2 1 F115 0 2AB3 Digital Input 2 Alarm Relays 0 6 1 F113 0 2AB4 Digital Input 2 Alarm Delay 1 50000 1 100ms F2 50 2AB5 Digital Input 2 Alarm Events 0 1 1 F103 0 2AB6 Digital Input 2...

Page 102: ...1 1 F103 0 2B16 Digital Input 1 Trip 0 2 1 F115 0 2B17 Digital Input 1 Trip Relays 0 6 1 F111 0 2B18 Digital Input 1 Trip Delay 1 50000 1 100ms F2 50 2B19 Digital Input 1 Assignable Function 0 3 1 F163 0 Reserved RRTD 4 DIGITAL INPUT 6 2B20 1st 2nd Character of Digital Input 6 Name 32 127 1 F22 GE 2B25 11th 12th Character of Digital Input 6 Name 32 127 1 F22 GE 2B30 Digital Input 6 Type 0 1 1 F116...

Page 103: ...e Trip Relay Duration 0 300 1 s F1 0 2B82 Force AUX1 Relay 0 2 1 F150 0 2B83 Force AUX1 Relay Duration 0 300 1 s F1 0 2B84 Force AUX2 Relay 0 2 1 F150 0 2B85 Force AUX2 Relay Duration 0 300 1 s F1 0 2B86 Force Alarm Relay 0 2 1 F150 0 2B87 Force Alarm Relay Range 0 300 1 s F1 0 Reserved RRTD 4 TEST OUPUT RELAYS 2B90 Force Trip Relay 0 2 1 F150 0 2B91 Force Trip Relay Duration 0 300 1 s F1 0 2B92 F...

Page 104: ...2C0C First Character of Counter Unit Name 32 127 1 F1 U 2C12 Counter Type 0 1 1 F114 0 2C13 Digital Counter Alarm 0 2 1 F115 0 2C14 Assign Alarm Relays 0 6 1 F113 0 2C15 Counter Alarm Level 0 65535 1 F1 100 2C17 Reserved 2C18 Record Alarms as Events 0 1 1 F103 0 Reserved RRTD 3 DIGITAL COUNTER 2C20 First Character of Counter Name 32 127 1 F1 G 2C2C First Character of Counter Unit Name 32 127 1 F1 ...

Page 105: ... Reserved WAVEFORM CAPTURE MOTOR START DATA LOGGER 30EF Buffer Memory Access Type 0 2 1 F184 0 Trace Memory 30F0 Trace Memory Clear Date N A N A N A N A F18 N A 30F2 Trace Memory Clear Time N A N A N A N A F19 N A 30F4 Trace Memory Triggers Since Last Clear 0 65535 1 F1 0 30F5 Trace Memory Buffer Selector 0 3 1 F1 0 Motor Start Log Buffer Selector 0 6 1 F1 0 None Selected 30F6 Trace Memory Channel...

Page 106: ... Log 9 16 Start Stop Method 0 FFFF N A F191 N A 3274 Log 17 24 Start Stop Method 0 FFFF N A F191 N A 3275 Log 25 32 Start Stop Method 0 FFFF N A F191 N A 3276 Log 33 40 Start Stop Method 0 FFFF N A F191 N A 3277 Log 41 48 Start Stop Method 0 FFFF N A F191 N A 3278 Log 49 50 Start Stop Method 0 FFFF N A F191 N A DATA LOGGER DATA 3280 Data Log Memory Access Block Number 0 255 1 F1 0 3281 Data Log Re...

Page 107: ...302 F13 16 bits INSTALLED OPTIONS xxxx xxxx xxxx xxx1 Profibus DP 0 Not Installed 1 Installed xxxx xxxx xxxx xx1x Fiber Optic 0 Not Installed 1 Installed xxxx xxxx xxxx x1xx Metering 0 Not Installed 1 Installed xxxx xxxx xxxx 1xxx Backspin 0 Not Installed 1 Installed xxxx xxxx xxx1 xxxx Local RTD 0 Not Installed 1 Installed xxxx xxxx xx1x xxxx Power Supply Type 0 LO 1 HI xxxx xxxx 1xxx xxxx Modbus...

Page 108: ...F21 16 bits 2 s COMPLEMENT SIGNED VALUE 2 DECIMAL PLACES Power Factor Example Power Factor of 0 87 lag is used as 87 i e 0057 0 Leading Power Factor Negative 0 Lagging Power Factor Positive F22 16 bits TWO 8 BIT CHARACTERS PACKED INTO 16 BIT UNSIGNED Example String AB stored as 4142 hex MSB First Character LSB Second Character F23 16 Bits UNSIGNED VALUE For 1A 5 A CT 1Decimal Place For 50 0 025 A ...

Page 109: ...served 10 Clear RTD Maximums 11 Reset Motor Info 12 Clear Reset all Data 20 Block Unblock Protection Functions 21 Force Output Relays F85 Unsigned 16 bit integer WAVEFORM CAPTURE TRIGGER CAUSE 0 None 1 Manual 2 Automatic F100 Unsigned 16 bit integer TEMPERATURE DISPLAY UNITS 0 Celsius 1 Fahrenheit F101 Unsigned 16 bit integer BAUD RATE 0 1200 baud 1 2400 baud 2 4800 baud 3 9600 baud 4 19200 baud F...

Page 110: ...CONNECTION TYPE 0 None 1 Open Delta 2 Wye F107 Unsigned 16 bit integer NOMINAL FREQUENCY 0 60 Hz 1 50 Hz 2 Variable F108 Unsigned 16 bit integer REDUCED VOLTAGE STARTING TRANSITION ON 0 Current Only 1 Current or Timer 2 Current and Timer F109 Unsigned 16 bit integer STARTER STATUS SWITCH 0 Starter Aux a 52a 1 Starter Aux b 52b F110 Unsigned 16 bit integer EMERGENCY RESTART SWITCH INPUT FUNCTION 0 ...

Page 111: ... ALARM RELAYS 0 None 1 Alarm 2 Aux1 3 Aux2 4 Alarm Aux1 5 Alarm Aux2 6 Aux1 Aux2 7 Alarm Aux1 Aux2 F114 Unsigned 16 bit integer COUNTER TYPE 0 Increment 1 Decrement F115 Unsigned 16 bit integer ALARM TRIP TYPE SELECTION 0 Off 1 Latched 2 Unlatched F116 Unsigned 16 bit integer SWITCH TYPE 0 Normally Open 1 Normally Closed F117 Unsigned 16 bit integer RESET MODE 0 All Resets 1 Remote Reset Only 2 Lo...

Page 112: ...0 Ohm Platinum 1 120 Ohm Nickel 2 100 Ohm Nickel 3 10 Ohm Copper F121 Unsigned 16 bit integer RTD APPLICATION 0 None 1 Stator 2 Bearing 3 Ambient 4 Other F122 Unsigned 16 bit integer LOCAL REMOTE RTD VOTING SELECTION 0 Off 1 RTD 1 2 RTD 2 3 RTD 3 4 RTD 4 5 RTD 5 6 RTD 6 7 RTD 7 8 RTD 8 9 RTD 9 10 RTD 10 11 RTD 11 12 RTD 12 13 All Stator Table CG 11 Memory Map Data Formats Sheet 6 of 27 CODE TYPE D...

Page 113: ...nsigned 16 bit integer ALARM STATUS 0 Off 1 Not Active 2 Timing Out 3 Active 4 Latched F124 Unsigned 16 bit integer PHASE ROTATION AT MOTOR TERMINALS 0 ABC 1 ACB F125 Unsigned 16 bit integer STARTER TYPE 0 Breaker 1 Contactor Table CG 11 Memory Map Data Formats Sheet 7 of 27 CODE TYPE DEFINITION ...

Page 114: ...Voltage 5 BC Line Voltage 6 CA Line Voltage 7 Average Line Voltage 8 Phase AN Voltage 9 Phase BN Voltage 10 Phase CN Voltage 11 Average Phase Voltage 12 Hottest Stator RTD 13 Local RTD 1 14 Local RTD 2 15 Local RTD 3 16 Local RTD 4 17 Local RTD 5 18 Local RTD 6 19 Local RTD 7 20 Local RTD 8 21 Local RTD 9 22 Local RTD 10 23 Local RTD 11 24 Local RTD 12 25 Power Factor Table CG 11 Memory Map Data F...

Page 115: ...VE STYLE 0 Standard 1 Custom F130 Unsigned 16 bit integer DIGITAL INPUT PICKUP TYPE 0 Over 1 Under F131 Unsigned 16 bit integer INPUT SWITCH STATUS 0 Open 1 Closed F133 Unsigned 16 bit integer MOTOR STATUS 0 Stopped 1 Starting 2 Running 3 Overloaded 4 Tripped F134 Unsigned 16 bit integer CAUSE OF EVENT 0 No Event 1 Forced Setpoints Dump 2 Speed Switch Trip 3 Differential Switch Trip 4 Reserved 5 S...

Page 116: ...rip 17 Single Phasing Trip 18 Ground Fault Trip 19 Ground Fault Backup Trip 20 Overload Block F134 Con t 21 Acceleration Timer Trip 22 Start Inhibit Block 23 Starts Hour Block 24 Time Between Starts Block 25 Restart Block 26 Backspin Block 27 Single Shot Restart 28 Undervoltage Trip 29 Overvoltage Trip 30 Voltage Phase Reversal Trip 31 Underfrequency Trip 32 Overfrequency Trip 33 Lead Power Factor...

Page 117: ...3 RTD5 Trip 44 RTD6 Trip 45 RTD7 Trip F134 Con t 46 RTD8 Trip 47 RTD9 Trip 48 RTD10 Trip 49 RTD11 Trip 50 RTD12 Trip 51 Reserved 52 Reserved 53 Spare Switch Alarm 54 Emergency Switch Alarm 55 Diff Switch Alarm 56 Speed Switch Alarm 57 Reset Switch Alarm 58 Reserved 59 Thermal Capacity Alarm 60 Overload Alarm 61 Mechanical Jam Alarm 62 Undercurrent Alarm Table CG 11 Memory Map Data Formats Sheet 11...

Page 118: ...ower Factor Alarm 70 Lag Power Factor Alarm 71 Positive Kvar Alarm 72 Negative Kvar Alarm 73 Underpower Alarm 74 Reverse Power Alarm 75 RTD1 Alarm 76 RTD2 Alarm 77 RTD3 Alarm 78 RTD4 Alarm 79 RTD5 Alarm 80 RTD6 Alarm F134 con t 81 RTD7 Alarm 82 RTD8 Alarm 83 RTD9 Alarm 84 RTD10 Alarm 85 RTD11 Alarm 86 RTD12 Alarm 87 RTD1 Hi Alarm 88 RTD2 Hi Alarm 89 RTD3 Hi Alarm Table CG 11 Memory Map Data Format...

Page 119: ...Lost RTD Comm Alarm 101 Low RTD Alarm 102 Trip Counter Alarm 103 Current Demand Alarm 104 Kw Demand Alarm 105 Kvar Demand Alarm 106 Kva Demand Alarm 107 Digital Counter Alarm 108 Service Alarm 109 Control Power Lost 110 Control Power App 111 Emergency Restart Closed 112 Emergency Restart Open 113 Start While Blocked 114 Reserved 115 Breaker Failure 116 Welded Contactor 117 Incomplete Sequence Trip...

Page 120: ...RTD7 Trip 128 RRTD1 RTD8 Trip 129 RRTD1 RTD9 Trip 130 RRTD1 RTD10 Trip 131 RRTD1 RTD11 Trip 132 RRTD1 RTD12 Trip 133 RRTD2 RTD1 Trip 134 RRTD2 RTD2 Trip F134 con t 135 RRTD2 RTD3 Trip 136 RRTD2 RTD4 Trip 137 RRTD2 RTD5 Trip 138 RRTD2 RTD6 Trip 139 RRTD2 RTD7 Trip 140 RRTD2 RTD8 Trip 141 RRTD2 RTD9 Trip 142 RRTD2 RTD10 Trip 143 RRTD2 RTD11 Trip 144 RRTD2 RTD12 Trip 145 RRTD3 RTD1 Trip Table CG 11 M...

Page 121: ...55 RRTD3 RTD11 Trip F134 Con t 156 RRTD3 RTD12 Trip 157 RRTD4 RTD1 Trip 158 RRTD4 RTD2 Trip 159 RRTD4 RTD3 Trip 160 RRTD4 RTD4 Trip 161 RRTD4 RTD5 Trip 162 RRTD4 RTD6 Trip 163 RRTD4 RTD7 Trip 164 RRTD4 RTD8 Trip 165 RRTD4 RTD9 Trip 166 RRTD4 RTD10 Trip 167 RRTD4 RTD11 Trip 168 RRTD4 RTD12 Trip 169 RRTD1 RTD1 Alarm 170 RRTD1 RTD2 Alarm 171 RRTD1 RTD3 Alarm 172 RRTD1 RTD4 Alarm 173 RRTD1 RTD5 Alarm ...

Page 122: ... Alarm 184 RRTD1 RTD4 Hi Alarm 185 RRTD1 RTD5 Hi Alarm 186 RRTD1 RTD6 Hi Alarm 187 RRTD1 RTD7 Hi Alarm 188 RRTD1 RTD8 Hi Alarm F134 con t 189 RRTD1 RTD9 Hi Alarm 190 RRTD1 RTD10 Hi Alarm 191 RRTD1 RTD11 Hi Alarm 192 RRTD1 RTD12 Hi Alarm 193 RRTD1 Open RTD Alarm 194 RRTD1 Low RTD Alarm 195 RRTD2 RTD1 Alarm 196 RRTD2 RTD2 Alarm 197 RRTD2 RTD3 Alarm 198 RRTD2 RTD4 Alarm 199 RRTD2 RTD5 Alarm 200 RRTD2...

Page 123: ...211 RRTD2 RTD5 Hi Alarm 212 RRTD2 RTD6 Hi Alarm 213 RRTD2 RTD7 Hi Alarm 214 RRTD2 RTD8 Hi Alarm 215 RRTD2 RTD9 Hi Alarm 216 RRTD2 RTD10 Hi Alarm 217 RRTD2 RTD11 Hi Alarm 218 RRTD2 RTD12 Hi Alarm 219 RRTD2 Open RTD Alarm 220 RRTD2 Low RTD Alarm 221 RRTD3 RTD1 Alarm 222 RRTD3 RTD2 Alarm 223 RRTD3 RTD3 Alarm 224 RRTD3 RTD4 Alarm 225 RRTD3 RTD5 Alarm 226 RRTD3 RTD6 Alarm 227 RRTD3 RTD7 Alarm 228 RRTD3...

Page 124: ...TD3 RTD7 Hi Alarm 240 RRTD3 RTD8 Hi Alarm 241 RRTD3 RTD9 Hi Alarm 242 RRTD3 RTD10 Hi Alarm F134 con t 243 RRTD3 RTD11 Hi Alarm 244 RRTD3 RTD12 Hi Alarm 245 RRTD3 Open RTD Alarm 246 RRTD3 Low RTD Alarm 247 RRTD4 RTD1 Alarm 248 RRTD4 RTD2 Alarm 249 RRTD4 RTD3 Alarm 250 RRTD4 RTD4 Alarm 251 RRTD4 RTD5 Alarm 252 RRTD4 RTD6 Alarm 253 RRTD4 RTD7 Alarm 254 RRTD4 RTD8 Alarm 255 RRTD4 RTD9 Alarm 256 RRTD4 ...

Page 125: ...RTD4 RTD9 Hi Alarm 268 RRTD4 RTD10 Hi Alarm F134 Ctd 269 RRTD4 RTD11 Hi Alarm 270 RRTD4 RTD12 Hi Alarm 271 RRTD4 Open RTD Alarm 272 RRTD4 Low RTD Alarm 273 Power Failure 274 Software Reset 275 Clock Failure 276 A D Failure 277 Autorestart Attempt 278 Autorestart Success 279 Autorestart Aborted 1 280 Autorestart Aborted 2 281 Autorestart Aborted 3 282 Autorestart Aborted 4 283 Autorestart Aborted 5...

Page 126: ...omms Reset 287 RTD 1 Open Alarm 288 RTD 2 Open Alarm F134 Ctd 289 RTD 3 Open Alarm 290 RTD 4 Open Alarm 291 RTD 5 Open Alarm 292 RTD 6 Open Alarm 293 RTD 7 Open Alarm 294 RTD 8 Open Alarm 295 RTD 9 Open Alarm 296 RTD 10 Open Alarm Table CG 11 Memory Map Data Formats Sheet 20 of 27 CODE TYPE DEFINITION ...

Page 127: ...k Short Circuit and Backup 50 310 Unblock Short Circuit and Backup 50 311 Block Overload Alarm 51 312 Unblock Overload Alarm 51 313 Block Ground Fault 51G 314 Unblock Ground Fault 51G 315 Block Starts Per Hour and Time Between Starts 66 316 Unblock Starts Per Hour and Time Between Starts 66 317 Profibus Loss of Communications 318 UVR Trip 319 UVR Undervoltage On 320 UVR Undervoltage Off 321 UVR In...

Page 128: ...signed 16 Bit Integer CHANNEL TYPE 0 RS 485 1 Fiber Optic F152 Unsigned 16 Bit Integer NUMBER OF RECORDS 0 1 64 cycles 1 2 32 cycles 2 4 16 cycles 3 8 8 cycles F156 Unsigned 16 Bit Integer REMOTE RTD COMMUNICATION STATUS 0 Remote RTD Module Communication Lost 1 Remote RTD Communication on Line F157 Unsigned 16 Bit Integer DIFFERENTIAL SWITCH INPUT FUNCTION 0 OFF 1 Differential Switch 2 General Swi...

Page 129: ...1 Starter Status Switch 2 General Switch 3 Digital Counter 4 Waveform Capture 5 DeviceNet Control 6 Reserved 7 Reserved F160 Unsigned 16 Bit Integer RESET SWITCH INPUT FUNCTION 0 OFF 1 Reset Switch 2 General Switch 3 Digital Counter 4 Waveform Capture 5 DeviceNet Control 6 Speed Switch1 7 Reserved F161 Unsigned 16 Bit Integer OUTPUT RELAY FAILSAFE CODE 0 Failsafe 1 Non Failsafe F162 Unsigned 16 Bi...

Page 130: ...TUS 0x0001 Ethernet Connection OK 0x0002 IP Configuration OK 0x0004 IP Address Error 0x0008 Communications Module Error 0x0010 Network Activity Present F165 Unsigned 16 Bit Integer OVERALL HOTTEST STATOR RTD OWNER 0 No RTDs programmed or available 1 Remote RTD 1 2 Remote RTD 2 3 Remote RTD 3 4 Remote RTD 4 5 Local 369 F166 Unsigned 16 Bit Integer ENERGY UNIT DISPLAY 0 Mega 1 Kilo Table CG 11 Memor...

Page 131: ... and Aux1 and Aux2 14 Alarm and Aux1 and Aux2 15 All Relays F180 Unsigned 16 Bit Integer ANSI IEEE DEVICE 0 37 Undercurrent Underpower 1 46 Current Unbalance 2 48 Incomplete Sequence 3 49 Thermal Model 4 50 Short Circuit and Backup 5 51 Overload Alarm 6 51G Ground Fault 7 66 Starts Per Hour Time Between Starts F181 Unsigned 16 Bit Integer OUTPUT RELAY TYPE 0 Latched 1 Pulsed F182 Unsigned 16 Bit I...

Page 132: ...1 Speed 1 Low Speed 2 Speed 2 High Speed F187 16 bitS START STOP DATA LOG COMMAND 0 None Select Command 1 Start Log 2 Stop Log F188 16 bitS DATA LOG RECORDING TYPE 0 Run To Fill 1 Circulate F189 SEE TABLE 9 12 BELOW F190 16 bitS DATA LOG STATUS 0 Stopped 1 Running F191 16 bits DATA LOG START STOP METHOD xxxx xxxx xxxx xxx1 Log 1 9 17 25 33 41 49 Start Method xxxx xxxx xxxx xx1x Log 1 9 17 25 33 41...

Page 133: ...s Switch xxxx xxxx xxxx xx1x Speed Switch xxxx xxxx xxxx x1xx Spare Switch xxxx xxxx xxxx 1xxx Differential Switch xxxx xxxx xxx1 xxxx Emergency Switch xxxx xxxx xx1x xxxx Remote Reset Switch xxxx xxx1 xxxx xxxx Trip Relay Status xxxx xx1x xxxx xxxx Alarm Relay Status xxxx x1xx xxxx xxxx Aux1 Relay Status xxxx 1xxx xxxx xxxx Aux2 Relay Status F193 Bitmask RRTD DIGITAL INPUT AND OUTPUT RELAY STATUS...

Page 134: ...F1 9 Unbalanced Biased Motor Load F3 10 Ground Current F23 11 Vab F1 12 Vbc F1 13 Vca F1 14 Average Line Voltage F1 15 Van F1 16 Vbn F1 17 Vcn F1 18 Average Phase Voltage F1 19 System Frequency F3 20 Power Factor F21 21 Real Power kW F4 22 Real Power hp F1 23 Reactive Power F4 24 Apparent Power F1 25 Positive MegaWatthours F1 26 Positive Megavarhours F1 27 Negative Megavarhours F1 28 Positive Kilo...

Page 135: ...ower Demand F1 50 Peak Apparent Power Demand F1 51 RRTD 1 RTD 1 Temperature F4 52 RRTD 1 RTD 2 Temperature F4 53 RRTD 1 RTD 3 Temperature F4 54 RRTD 1 RTD 4 Temperature F4 55 RRTD 1 RTD 5 Temperature F4 56 RRTD 1 RTD 6 Temperature F4 57 RRTD 1 RTD 7 Temperature F4 58 RRTD 1 RTD 8 Temperature F4 59 RRTD 1 RTD 9 Temperature F4 60 RRTD 1 RTD 10 Temperature F4 61 RRTD 1 RTD 11 Temperature F4 62 RRTD 1...

Page 136: ...0 Temperature F4 85 RRTD 3 RTD 11 Temperature F4 86 RRTD 3 RTD 12 Temperature F4 87 RRTD 4 RTD 1 Temperature F4 88 RRTD 4 RTD 2 Temperature F4 89 RRTD 4 RTD 3 Temperature F4 90 RRTD 4 RTD 4 Temperature F4 91 RRTD 4 RTD 5 Temperature F4 92 RRTD 4 RTD 6 Temperature F4 93 RRTD 4 RTD 7 Temperature F4 94 RRTD 4 RTD 8 Temperature F4 95 RRTD 4 RTD 9 Temperature F4 96 RRTD 4 RTD 10 Temperature F4 97 RRTD ...

Reviews: