4-7
Location
Message Line
Description
A 5.1
ACTUAL VALUES
PRE-TRIP DATA
The actual values page 5 header. This page displays the cause of the
current alarm and the cause of the last trip. It also gives data on the
condition of the feeder when a trip was last initiated by the 565/575 Relay.
This page can be viewed immediately after an alarm or trip to determine its
cause. Also, if an overcurrent trip has occurred, then the phase currents
can be inspected to check which phase or phases caused this.
A 5.2
ALARM: PHASE O/C
This message will only appear if the condition causing the alarm is present.
In this case the current in any or all of the phases is exceeding the phase
alarm limit set up in setpoints mode.
ALARM: GROUND
O/C
This message indicates that the present alarm is caused by the ground
current exceeding the limits specified in setpoints mode.
ALARM: OVERVOLT
This message indicates that the present alarm is caused by the voltage
sensed between phases or between a phase and the neutral line rose
above the limits specified in setpoints mode.
ALARM: UNDERVOLT
This message indicates that the present alarm is caused by the voltage
sensed between phases or between a phase and the neutral line dropped
below the limits specified in setpoints mode.
ALARM: ANALOG
INPUT
This message indicates that the present alarm is caused by the analog
input exceeding the limits specified in setpoints mode.
ALARM:
ACCUMULATED KA
This message indicates that the present alarm is caused by the Accumu-
lated KA exceeding the limits specified in setpoints mode.
SWITCH ALARM 1
This message indicates that the present alarm is caused by the external
switch programmed to create a Definite Time alarm.
ALARM: AMPS
DEMAND
This message indicates that the present alarm is caused by the Amps
Demand exceeding the limits specified in setpoints mode.
ALARM: KW DEMAND
This message indicates that the present alarm is caused by the kW
Demand exceeding the limits specified in setpoints mode.
** 565 requires
Option Card **
ALARM: KVAR
DEMAND
This message indicates that the present alarm is caused by the kVAR
Demand exceeding the limits specified in setpoints mode.
** 565 requires
Option Card **
ALARM: POWER
FACTOR
This message indicates that the present alarm is caused by the MTM
Power Factor exceeding the limits specified in setpoints mode.
** 565
requires Option Card **
ALARM: FREQUENCY
This message indicates that the present alarm is caused by the MTM
Frequency exceeding the limits specified in setpoints mode.
** 565 re-
quires Option Card **
ALARM: BREAKER
DISCREPANCY
This message indicates that the present alarm is caused by the feeder
breaker not responding within the time limit specified in setpoints mode.
ACTUAL VALUES MODE - PRE-TRIP DATA
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......