5-21
Location
Message Line
Description
S 3.19
GND LOSET INST
TRIPS ENABLED
Set to ENABLED to enable loset ground element.
Messages S 3.20 to S 3.24 will only appear if ENABLED is selected in message S 3.19.
S 3.20
GND LOSET INST
TRIP 2.0 X P/U
Same as GND HISET INST TRIP feature.
Range: 1.0–7.0, increments of 0.5.
S 3.21
GND LOSET INST
DELAY INST
Same as GND HISET INST TRIP DELAY.
Range: 0–40 cycles.
S 3.22
GND LOSET INST
RELAY TRIP&AUX1
Select the desired output contact(s) to activate on a GND LOSET INST
trip.
S 3.23
GND AUTOBLK INST
LOSET DISABLED
This setpoint allows the user to enable or disable the ground autoblock
loset feature.
Message S 3.24 will only appear if ENABLED is selected in message S 3.23.
S 3.24
GND AUTOBLK LOSET
AFTER RECL.# 4
The G/F LOSET INST TRIP will be blocked after the selected reclosure
shot.
Messages S 3.25 and 3.26 will only appear if CUSTOM CURVE1 was selected in message S 3.6.
S 3.25
TRIP TIME (SEC)
1.03 xPU= 1.0
The trip time for the first breakpoint of the programmable curve for ground
current protection is entered here. The breakpoints are multiples of the
pickup current.
The remainder of the messages in this section are identical to those in the phase current programmable curve setup. Follow
all the same steps until message S 3.18 appears. When the time for this multiple of pickup is entered and stored, pressing the
PAGE key will cause the display to move to the next page of setpoints mode.
NOTE: When the overload is greater than eight times pickup, the 575 will cause a Ground Timed Overcurrent Trip in the time
programmed for an eight times overload. This is regardless of how the Custom Curve is programmed for overloads greater
than eight times pickup.
S 3.26
TRIP TIME (SEC)
20.0 xPU= 1.0
The trip time for the last breakpoint, a current of 20 times the pickup level
is entered here.
S 3.27
GROUND CURRENT
END OF PAGE
The last line of page 3, setpoints. Press the PAGE key to view page 4.
L
A
L
A
SETPOINTS MODE - GROUND CURRENT
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......