FEATURE INFORMATION
565/575 DATA FORMATS (REVISION E2.73)
FORMAT
APPLICABLE BITS
DEFINITION
CODE
F1
16 bits
MULTILIN PRODUCT DEVICE CODE
0000 0000 0001 0010 (BIN) or 0012 (HEX)
18 (DEC) = 565 Feeder Management Relay
0000 0000 0011 1010 (BIN) or 003A (HEX)
58 (DEC) = 575 Feeder Management Relay
F2
16 bits
565/575 HARDWARE REVISION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = Undefined
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = A
0000 0000 0000 0010 (BIN) or 0002 (HEX)
02 (DEC) = B
0000 0000 0000 0011 (BIN) or 0003 (HEX)
03 (DEC) = C
0000 0000 0000 0100 (BIN) or 0004 (HEX)
04 (DEC) = D
0000 0000 0000 0101 (BIN) or 0005 (HEX)
05 (DEC) = E
:
:
0000 0000 0001 1010 (BIN) or 001A (HEX)
26 (DEC) = Z
F3
16 bits
565/575 FIRMWARE REVISION
0000 XXXX 0000 0000 (BIN) or 0X00 (HEX)
Major Revision Digits (0 through 9 only)
0000 0000 XXXX 0000 (BIN) or 00X0 (HEX)
Minor Revision Digits (0 through 9 only)
0000 0000 0000 XXXX (BIN) or 000X (HEX)
Ultra Minor Revision Digits (0 through 9 only)
0000 0010 0111 0011 (BIN) or 0273 (HEX)
Example: Revision 2.73 Stored As 0273 (HEX)
F4
16 bits
565/575 FIRMWARE MODIFICATION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
000 (DEC) = No Modification (Standard Feeder Management Relay)
0000 0001 0010 1011 (BIN) or 012B (HEX)
299 (DEC) = Modification 299
F5
16 bits
START OF EVENT QUEUE (POINTER TO MOST RECENT EVENT)
0000 0000 XXXX XXXX (BIN) or 00XX (HEX)
Points To Most Recent Event Record Number (0 through 39 only)
XXXX XXXX 0000 0000 (BIN) or XX00 (HEX)
Wrap Around Counter Incremented Every 40 Events
0000 0000 0000 0000 (BIN) or 0000 (HEX)
000 (DEC) = No. Of Events Register At 74 (HEX) Points To Most Recent Event Record
0000 0000 0000 0001 (BIN) or 0001 (HEX)
001 (DEC) = Points To Event Record 01 As The Most Recent Event
0000 0000 0000 0010 (BIN) or 0002 (HEX)
002 (DEC) = Points To Event Record 02 As The Most Recent Event
0000 0000 0000 0011 (BIN) or 0003 (HEX)
003 (DEC) = Points To Event Record 03 As The Most Recent Event
:
:
0000 0000 0010 0111 (BIN) or 0027 (HEX)
039 (DEC) = Points To Event Record 39 As The Most Recent Event
0000 0001 0000 0000 (BIN) or 0100 (HEX)
256 (DEC) = Points To Event Record 40 As The Most Recent Event
0000 0001 0000 0001 (BIN) or 0101 (HEX)
257 (DEC) = Points To Event Record 01 As The Most Recent Event
F6
16 bits
565/575 TRIP STATUS
0000 0000 0000 0000 (BIN) or 0000 (HEX)
0 (DEC) = 565/575 Not Tripped Since Last Reset
0000 0000 0000 0001 (BIN) or 0001 (HEX)
1 (DEC) = 565/575 Tripped Since Last Reset
F7
16 bits
BREAKER POSITION STATUS
0000 0000 0001 0000 (BIN) or 0010 (HEX)
16 (DEC) = Breaker Open
0000 0000 0010 0000 (BIN) or 0020 (HEX)
32 (DEC) = Breaker Closed
F8
16 bits
ALARM STATUS I
0000 0000 0000 0001 (BIN) or 0001 (HEX)
001 (DEC) = Undefined
0000 0000 0000 0010 (BIN) or 0002 (HEX)
002 (DEC) = MTM Communication Alarm
0000 0000 0000 0100 (BIN) or 0004 (HEX)
004 (DEC) = Switch Alarm 2
0000 0000 0000 1000 (BIN) or 0008 (HEX)
008 (DEC) = Trip Coil Supervision Alarm
0000 0000 0001 0000 (BIN) or 0010 (HEX)
016 (DEC) = Frequency Alarm
0000 0000 0010 0000 (BIN) or 0020 (HEX)
032 (DEC) = Power Factor Alarm
0000 0000 0100 0000 (BIN) or 0040 (HEX)
064 (DEC) = KVAR Demand Alarm
0000 0000 1000 0000 (BIN) or 0080 (HEX)
128 (DEC) = KW Demand Alarm
Note: Multiple Alarms Can Be Reported
F9
16 bits
ALARM STATUS II
0000 0000 0000 0001 (BIN) or 0001 (HEX)
001 (DEC) = Amps Demand Alarm
0000 0000 0000 0010 (BIN) or 0002 (HEX)
002 (DEC) = Accumulated KA Alarm
0000 0000 0000 0100 (BIN) or 0004 (HEX)
004 (DEC) = Overvoltage Alarm
0000 0000 0000 1000 (BIN) or 0008 (HEX)
008 (DEC) = Undervoltage Alarm
0000 0000 0001 0000 (BIN) or 0010 (HEX)
016 (DEC) = Analog In Alarm
0000 0000 0010 0000 (BIN) or 0020 (HEX)
032 (DEC) = Switch Alarm 1
0000 0000 0100 0000 (BIN) or 0040 (HEX)
064 (DEC) = Ground Alarm
0000 0000 1000 0000 (BIN) or 0080 (HEX)
128 (DEC) = Phase Alarm
Note: Multiple Alarms Can Be Reported
F10
16 bits
EXTERNAL SWITCH STATUS
0000 0000 0000 0001 (BIN) or 0001 (HEX)
001 (DEC) = External Switch 1 Active (N/O Switch Is Closed) or (N/C Switch Is Open)
0000 0000 0000 0010 (BIN) or 0002 (HEX)
002 (DEC) = External Switch 2 Active (N/O Switch Is Closed) or (N/C Switch Is Open)
0000 0000 0000 0100 (BIN) or 0004 (HEX)
004 (DEC) = External Switch 3 Active (N/O Switch Is Closed) or (N/C Switch Is Open)
0000 0000 0000 1000 (BIN) or 0008 (HEX)
008 (DEC) = External Switch 4 Active (N/O Switch Is Closed) or (N/C Switch Is Open)
0000 0000 0001 0000 (BIN) or 0010 (HEX)
016 (DEC) = External Switch 5 Active (N/O Switch Is Closed) or (N/C Switch Is Open)
0000 0000 0010 0000 (BIN) or 0020 (HEX)
032 (DEC) = External Switch 6 Active (N/O Switch Is Closed) or (N/C Switch Is Open)
0000 0000 0100 0000 (BIN) or 0040 (HEX)
064 (DEC) = External Switch 7 Active (N/O Switch Is Closed) or (N/C Switch Is Open)
0000 0000 1000 0000 (BIN) or 0080 (HEX)
128 (DEC) = External Switch 8 Active (N/O Switch Is Closed) or (N/C Switch Is Open)
Note: Multiple Switches Can Be Reported
F11
16 bits
OUTPUT CONTACT STATUS
0000 0000 0000 0001 (BIN) or 0001 (HEX)
001 (DEC) = Aux 3 Relay Is Or Has Been Activated By A Trip Since Last Reset (*)
0000 0000 0000 0010 (BIN) or 0002 (HEX)
002 (DEC) = Aux 2 Relay Is Or Has Been Activated By A Trip Since Last Reset (*)
0000 0000 0000 0100 (BIN) or 0004 (HEX)
004 (DEC) = Aux 1 Relay Is Or Has Been Activated By A Trip Since Last Reset (*)
0000 0000 0000 1000 (BIN) or 0008 (HEX)
008 (DEC) = Trip Relay Is Or Has Been Activated By A Trip Since Last Reset (*)
6-24
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......