5-23
Location
Message Line
Description
S 4.7
BLOCK GND TRIPS
DISABLED
If this function is assigned, all ground tripping is blocked for the length of
time the external switch is active.
S 4.8
DEFINITE TIME #1
ALARM DISABLED
This function will assign a time delayed alarm to the selected switch. The
switch will then have to be held active for the programmed delay time
before an alarm occurs.
Message S 4.9 and S 4.10 will only appear if the Definite Time function in message S 4.8 is assigned to a switch.
S 4.9
DEFINITE TIME #1
DELAY 1 SEC
This message asks for any time delay needed on the operation of the
switch. This means that if one of the internal relays is to be energized by
this switch it will only be energized if the switch is activated for the assigned
time. The range for this setpoint is 1 to 255 seconds, in steps of 1 second.
S 4.10
DEFINITE TIME #1
RELAY AUX2
The switch being configured can be used to activate one of the internal
relays in the 565 Relay. This message is asking you to select the relay or
relays which the definite time function will activate. There are two relays to
which the signal can be sent, called Aux.1 and 2. See Relay selection
section for details of how to make this selection.
S 4.11
DEFINITE TIME #2
ALARM DISABLED
This function will assign a time delayed alarm to the selected switch. The
switch will then have to be held active for the programmed delay time
before an alarm occurs.
Messages S 4.12 and S 4.13 will only appear if the Definite Time function in message S 4.11 is assigned to a switch.
S 4.12
DEFINITE TIME #2
DELAY 1 SEC
Enter the amount of time the above switch must be active before an alarm
will occur.
S 4.13
DEFINITE TIME #2
RELAY AUX2
Enter which output relay will activate when the above alarm occurs.
S 4.14
EXTERNAL TRIP #1
DISABLED
If this function is assigned to a switch then it will cause the input to act as
an external trip for the feeder breaker. External trip devices are called “3T”
devices.
Messages S 4.15 and S 4.16 will appear only if the External Trip function in message S 4.14 is assigned to a switch.
S 4.15
EXTERNAL TRIP #1
RELAY TRIP&AUX1
Enter which output relay will activate when the above trip occurs.
L
A
L
A
L
A
L
A
L
A
L
A
L
A
L
A
(575)
EXTERNAL TRIP
DISABLED
(575)
EXTERNAL TRIP
RELAY TRIP&AUX1
SETPOINTS MODE - CONFIGURATION
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......