SETPOINTS MODE
5-5
Setpoint Name
Factory Default
Range
Step
1. User Level setpoints.
User Level
Advanced.
Basic/Advanced
Security Feature
Disabled.
Enabled/Disabled
Setpoint Access
Enabled.
Enabled/Disabled
Change Access Code
No.
Yes/No
2. Phase Current setpoints.
Phase CT Rating Primary
100 A.
10 to 5000A
5A
Phase Timed O/C Pickup
100% CT.
25 to 250%
1%
Phase O/C Curve Shape
EXTREM INV.
MOD INV, NORMAL INV, VERY INV, EXTREM INV, and
CUSTOM
Phase O/C Time Dial
1.
1 to 32
1
Phase O/C Trip Relay
Trip. (Trip&Aux1 for 575)
Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2 (575: Trip, Trip&Aux1, Aux2)
Phase O/C Alarm
Disabled.
Enabled/Disabled
Phase O/C Alarm Level
1.5 × P/U
0.5 to 3
0.1
Phase O/C Alarm Delay
1 Sec.
1 to 255 sec
1 sec
Phase O/C Alarm Relay
Aux1. (Aux2 for 575)
Aux1, Aux2, and Aux1&2 (575: None, Aux1, Aux2,
Aux1&2)
Phase Inst Trips
Enabled.
Enabled/Disabled
Phase Inst Trip Level
3.0 × P/U (565)
1 to 18
0.5
Phase Inst Trip Delay
Inst. (565)
0 (Inst.) to 40 cycles
1 cycle
Phase Inst Trip Relay
Trip. (565)
Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2
Phase HISET Inst Trips
Enabled.
Enabled/Disabled
Phase HISET Inst Trip
3.0
×
P/U
1 to 18
0.5
Phase HISET Inst Delay
Inst.
0 (Inst.) to 40 cycles
1 cycle
Phase HISET Inst Relay
Trip & Aux1.
Trip, Trip&Aux1, Aux2
Phase Autoblock Inst HISET
Disabled.
Enabled/Disabled
Ph. Autoblock HISET After Recl.
#4.
1 to 4
1
Phase LOSET Inst Trips
Enabled.
Enabled/Disabled
Phase LOSET Inst Trip
2.0
×
P/U
1 to 18
0.5
Phase LOSET Inst Delay
Inst.
0 (Inst.) to 40 cycles
1 cycle
Phase LOSET Inst Relay
Trip & Aux 1.
Trip, Trip&Aux1, Aux2
Phase Autoblock Inst LOSET
Disabled.
Enabled/Disabled
Ph. Autoblock LOSET After Recl.
#4
1 to 4
Trip Time (Sec) × P/U
1.0
0.1 to 1092.2 sec
0.1 sec
3. Ground Current setpoints.
Ground Current Sensing
Enabled.
Enabled/Disabled
Sensing System
Residual.
Residual/Zero Seq
CT Ratio Primary
100 A.
10 to 5000A
5A
Ground Timed O/C Pickup
40% CT.
5 to 100%
1%
Gnd O/C Curve Shape
EXTREM INV.
MOD INV, NORMAL INV, VERY INV, EXTREM INV, and
CUSTOM
Ground O/C Time Dial
1.
1 to 32
1
Ground O/C Relay
Trip. (Trip&Aux1 for 575)
Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2 (575: Trip, Trip&Aux1, Aux2)
Ground O/C Alarm
Disabled.
Enabled/Disabled
Gnd O/C Alarm Level
1.5 × P/U
0.5 to 1
0.1
1 to 3
0.5
Gnd O/C Alarm Delay
1 Sec.
1 to 255 sec
1 sec
Gnd O/C Alarm Relay
Aux1. (Aux2 for 575)
Aux1, Aux2, and Aux1&2 (575: None, Aux1, Aux2,
Aux1&2)
Ground Inst Trips
Enabled.
Enabled/Disabled
Gnd Inst Trip Level
3.0 × P/U
1 to 7
0.5
(575)
U
|
V
|
W
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......