5-47
Location
Message Line
Description
S 11.11
POWER FACTOR
TRIP DISABLED
This message allows the user to enable or disable the trip feature for the
Power Factor.
Messages S 11.12 to S 11.15 appear only if the Power Factor Trip feature has been enabled in message S 11.11.
S 11.12
P/F LEADING TRIP
LEVEL 0.70
The leading trip level is chosen here. The range is 0 to 1 in steps of 0.05.
S 11.13
P/F LAGGING TRIP
LEVEL 0.70
The lagging trip level is chosen here. The range is 1 to 0 in steps of 0.05.
S 11.14
P/F TRIP DELAY
1.0 SEC
The delay time before a trip is given can be selected here. Range is 1 - 127
sec. in steps of 0.5 sec.
S 11.15
P/F TRIP RELAY
AUX1
This message indicates which relay will be activated when the trip level is
exceeded.
S 11.16
FREQUENCY ALARM
DISABLED
This message allows the user to enable or disable the frequency alarm
feature.
Messages S 11.17 to S 11.20 appear only if the Frequency Alarm feature has been enabled in message S 11.16.
S 11.17
UNDER FREQ ALARM
LEVEL 58.0 Hz
The under frequency alarm level is chosen here. The range is 40 - 60 Hz
in steps of 0.1.
S 11.18
OVER FREQ ALARM
LEVEL 62.0 Hz
The over frequency alarm level is chosen here. The range is 50 - 72 Hz in
steps of 0.1.
S 11.19
FREQUENCY ALARM
DELAY 5.0 SEC
The delay time before an alarm is given can be selected here. Range is 1
- 127 sec. in steps of 0.5 sec.
S 11.20
FREQUENCY ALARM
RELAY AUX1
This message indicates which relay will be activated when the alarm level
is exceeded.
S 11.21
FREQUENCY TRIP
DISABLED
This message allows the user to enable or disable the frequency trip
feature.
Messages S 11.22 to S 11.25 appear only if the Frequency Trip feature has been enabled in message S 11.21.
S 11.22
UNDER FREQ. TRIP
LEVEL 56.0 Hz
The under frequency trip level is chosen here. The range is 40 - 60 Hz in
steps of 0.1.
S 11.23
OVER FREQ. TRIP
LEVEL 64.0 Hz
The over frequency trip level is chosen here. The range is 50 - 72 Hz in
steps of 0.1.
SETPOINTS MODE - MTM METERING
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......