____________________________________________________Chapter 5 – Odor Control Section, Page 5-7
Spray Odor Control
Setting the Timers
CAUTION: Always de-energize the ClearAir Unit before opening the Electrical and Timer Control Panel
inside the Odor Spray Cabinet.
The Spray Odor Control unit operates on spray-on and spray-off
timed cycles while the ClearAir Unit is in
the “Fan On” mode. To adjust the Cycle Timer and Spray Timer, open the Spray Odor Cabinet, and
remove the screwed-in-place timer control cover plate. Adjust as necessary for satisfactory odor
control as follows:
Cycle Timer
To set the “Off” period, turn the dial to the desired off time interval.
Spray Timer
To set the “On” period, turn the dial to the desired on time interval.
Spray Odor Control - Maintenance
Compressor
The air pressure is factory set at 20 psi. If the solution is not being pulled up through the pick-up tube
adjust the pressure slightly up or down until the climbs up the tube.
Nozzle
To obtain the best performance from your nozzle, it may become necessary to clean it periodically.
The nozzle may become clogged and cease spraying due to factors such as dust, foreign particles
accumulated in the orifice, and/or leakage in the air or liquid section of the nozzle.
Figure 5-7-1
Cycle Timer
Figure 5-7-2
Spray Timer