___________________________________________________________Chapter 1 – Introduction, Page 1-5
Specifications (Cont.)
The Modules and After Filters shall be mounted into slide tracks to prevent air bypass around the ends. The
Modules and After Filters shall be removable through side access doors with lift and turn latches.
___Media Panel type – The odor control media shall be com- pressed into Media Panels that slide into Media
Modules. The Modules shall be mounted into slide tracks to prevent air bypass around the ends. The
Modules and shall be re- movable through side access doors with lift and turn latches
.
___(
optional)
The unit shall be equipped with a 30% pleated media After Filter located immediately
downstream of the Media Models.
___The unit shall be equipped with a Single Pass Media Bed.
___The unit shall be equipped with a Double Pass Media Bed.
___The unit shall be equipped with a Triple Pass Media Bed.
Spray Odor Control
The unit shall be provided with a spray odor control system utilizing an odor neutralizer chemical. The
odor spray control cabinet shall be mounted on the side of the unit and shall contain a liquid spray
compressor piped to the spray nozzle in the fan plenum, adjustable delay timers with fuse protected
circuitry factory wired to the unit electrical panel. The cabinet shall include one 5 gallon container of
Gaylord Formula GS-710 Odor Neutralizer. The cabinet shall contain a heater to prevent freezing of the
odor neutralizer, if mounted outdoors.
Exhaust Fan Options
___Exhaust Fan (Standard Centrifugal Fan)
The unit shall include a centrifugal exhaust fan. The exhaust fan shall be an SWSI up-blast arrangement #9 or
#10 with a non-overloading BI or AF wheel. The motor, drives, bearings and fan mounting base shall be
located out of the exhaust air stream as required by the IMC (International Mechanical Code) and NFPA-96.
The fan shall be AMCA certified and bear the AMCA seal for performance. The fan housing shall be
constructed of heavy gauge steel. The fan bearings shall be heavy duty self-aligning pillow block type rigidly
mounted on heavy structural steel supports. The motor shall be P.E. rated, ODP three phase mounted on a
common base with the fan and shall be pre-wired to the electrical cabinet located on the unit. The electrical
cabinet shall include a disconnect switch, motor starter, overloads and fuses. The factory provided drive
assembly shall be adjustable pitch on 5 HP and smaller, fixed pitch on 7.5 HP and larger. It shall also be sized for
a minimum
1.5 service factor. After final system balancing, fixed pitch sheaves shall be provided and
installed by the air balancing contractor to provide proper flow at actual installed conditions.
___Exhaust Fan (Optional Tubular Fan)
The unit shall include a tubular centrifugal exhaust fan. The exhaust fan shall be an arrangement #10 with a non-
overloading BI, AF wheel. The motor, drives, bearings and fan mounting
base shall be located out of the exhaust
air stream as required
by the IMC (International Mechanical Code) and NFPA-96. The fan shall be AMCA
certified and bear the AMCA seal for performance. The fan housing shall be constructed of heavy gauge steel.
The fan bearings shall be heavy duty rigidly mounted on heavy structural steel supports. The motor shall be
P.E. rated, ODP three phase mounted on a common base with the fan and shall be pre-wired to the electrical
cabinet located on the unit. The electrical cabinet shall include a disconnect switch, motor starter, overloads and
fuses. The factory provided drive assembly shall be adjustable pitch on 5 HP and smaller and fixed pitch on 7.5
HP and larger. It shall also be sized for a minimum 1.5 service factor. After final system balancing, fixed
pitch sheaves shall be provided and installed by the air balancing contractor to provide proper flow at actual
installed conditions.