A maximum of 32 GLB-wallboxes may be connected together by a shielded twisted pair cable, which
is connected to the terminal labelled ‘Data Link’.
The Data Link cable must be electrically terminated in the first and last wallboxes, via switch SW1 (DIP
6) on the main board. In the below example, the switch SW1 (DIP 6) is to be set to ‘ON’ in wallboxes
no. 1 and 5, and ‘OFF’ in the remaining boxes. To verify that the master wallbox is defined as master,
ensure the switch SW1 (DIP 5) is set to ‘ON’ mode.
FUSE 2AT
SW2
SW1
SW3
DIP 6: Termination resistor ‘Datalink’ ON=activated: OFF=deactivated
DIP 5: GLB mode ON=Master: OFF=Slave