GALAXY 635-SERIES DRM BOARD – TERMINAL PINOUT

 

GCS-HW-0117-SG-RDRWIR-QRG

 

www.

galaxysys

.com

 

Page 9 of 10 

 

12.0

 

635-DRM (PN 20-0235-10) – FULL SECTION TERMINAL PINOUT 

Each Reader Section has the following terminals… 

READER WIRING (9-PIN CONNECTOR)  

 

5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet.   

 

Reader may require separate power supply if the current draw is over 150 milliamps.  

 

Ground the Drain-wire at one end only - at the DRM Board (GND). 

 

Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs). 

 

635-DRM (Terminal Functions) 

Wiegand  

ABA 

LED

 

(LED control line) 

LED Control  

LED Control  

D 1

 

(Data 1) 

DATA 1 

DATA 

VDC

 

+12 VDC  (For +5VDC use Regulator PN 92-3001-05) 

VDC 

VDC 

GND

 

(Power Supply Ground ) 

GND 

GND 

D 0

 

 

(Data 0) 

DATA 0 

CLOCK 

unused 

 

 

 

DOOR CONTACT & REX MOTION DETECT (9-PIN CONNECTOR) 

 

2-conductor, 22 AWG, overall shielded (for Door Contact).   

 

4-conductor, 22 AWG; overall shielded (for REX/Motion Detector). for Door Contact 

 

Separate Power Supply for REX/Motion Sensor. 

 

Ground all Drain-wires at one end only - at the DRM Board (GND). 

 

Refer to device manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs). 

 

635-DRM (Terminal Functions)

 

Device State

  

COM 

(Common)

 

LED Control  

CNT 

(Door Contact)

 

NC Normally Closed Contact = Door Closed/Contact Closed 

REX

 

Request to Exit (motion sensor) 

NO Normally Open = Momentary Push Button 

 

LOCK RELAY CONNECTOR (RLY-1) 

 

2-conductor, Minimum 18 AWG for LOCK (Manufacturer’s specs for wire gauge may supersede Galaxy’s instructions).   

 

Separate Power Supply required for Lock – follow manufacturer’s requirements for lock power supply. 

 

Relay is Form-C SPDT Dry, (Rated max. 24v, 1.5 Amps)  

 

635-DRM RELAY-1  

LOCK DEVICE 

COM 

COMMON

 

NC

 = Normally Closed >

 

Land lock wiring according to  

NO

 = Normally Open   >

 

Manufacturer’s instructions. 

 

RELAY-2 CONNECTOR – OPTIONAL OUTPUT   

 

For optional output (i.e. piezo, bell, buzzer) 

 

Relay is Form-C SPDT Dry, (Rated max. 24v, 1.5 Amps)  

 

Relay-2 (mode/timers/event-triggers) must be configured for desired behavior in SG Reader Properties 

 

635 DRM RELAY-2  

DEVICE 

  MODES

*

 

Available Events  

COM 

COMMON

 

 

  FOLLOWS  

 Door Forced Open 

 Valid Unlock 

NC

 = Normally Closed > 

Land wiring according to 

 

  TIMED 

 Door Open Too Long 

 Duress 

NO

 = Normally Open   > 

Manufacturer’s instructions 

 

  SCHEDULED  

 Invalid Access Attempt 

 Passback 

 

 

 

  LATCHED 

Note: the events you can select will vary depending on 
which mode is chosen. 

 

 

 

 

*

 

Timers affect behavior.

 

 

 

Summary of Contents for 635-DRM

Page 1: ...VDC GND Power Supply Ground GND D 0 Data 0 DATA 0 2 0 ABA Reader Cable Specs Wiring 5 conductor 22 AWG overall shielded max cable distance is 500 feet Reader will require separate power supply if the...

Page 2: ...Board Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only high Mode 2 Card Pin low 635 DRM Terminal Functions PN...

Page 3: ...a LED1 to the NO leg of Relay 2 The COM leg of Relay 2 must be tied to DRM GND Set Relay 2 for Timed Mode 1 to 2 secs and Valid Unlock checkbox must be checked in System Galaxy Reader Properties 6 0 I...

Page 4: ...Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only Mode 2 Card Pin 635 DRM Terminal Functions PN 20 0235 10 SCM R...

Page 5: ...ader The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz STid PC2 Smart Cards Do not mix non mobile STid R...

Page 6: ...m PC2 smart cards but cannot read the secure area The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz MIFA...

Page 7: ...en you add the 635 Series Clusters into the SG Loop Cluster Properties screen do the following On the Advanced tab set the Card Data Mode droplist to Extended Card 256 Bits On the LED Options tab set...

Page 8: ...Module PN 20 0235 10 Min Board Requirement 635 DSI Board Dual Serial Interface PN 20 0655 10 for Mode Factor Control READER MODES FACTORS Mode 1 Card Only Mode 2 Card Pin Mode 3 Card Pin Bio 635 DRM...

Page 9: ...s instructions for wiring manufacturer s specs may supersede Galaxy specs 635 DRM Terminal Functions Device State COM Common LED Control CNT Door Contact NC Normally Closed Contact Door Closed Contac...

Page 10: ...m controller 22 AWG 2 conductor overall shielded wired normally closed NC Lock Hardware 500 ft from controller 18 AWG 2 conductor minimum shielded Separate Power Supply Refer to manufacturer s instruc...

Reviews: